Combustible Cladding
≥ 30% of PE (Polyethylene) on ACP (Aluminium Composite Panel) are banned to use in any exterior cladding [1] Type B Construction as defined in Building Code of Australia[2] Combustible Cladding (Type B Construction) NCC 2022 V1 Class 2 to 9
NCC 2022 C1P2 (1)
NCC 2022 C2D10 (1)
May 2023
NSW Fair Trading NCC 2022 Vol 1, C1P2 (1) NCC 2022 Vol 1, C2D10 (1) Type B Construction as defined in Building Code of AustraliaNSW Fair Trading ≥ 2 storeys on Class 2, 3 & 9 Building≥ 3 storeys on Class 5, 6, 7 & 8 BuildingFire Resistance on a building must have elements to avoid the spread of fire on NCC 2022 Vol 1, C1P2 (1) Exits, Sole-occupancy Units & Public Corridors, Between Buildings, Within the Building Non-combustible Building Element & their Components for Type A or B Construction NCC 2022 Vol 1, C2D10 (1) External walls & Common walls includes Facade covering, Framing & insulation The Flooring & Floor framing of lift pits Fire-resistant non-loadbearing internal walls Non-combustible Building Elements NCC 2022 V3 Class 2 to 9
NCC 2022 C2D10 (5)
NCC 2022 C2D10 (6)
May 2023
NCC 2022 Vol 1, C2D10 (5) NCC 2022 Vol 1, C2D10 (6) Non-combustible Material that entirely composed of itselfNCC 2022 Vol 1, C2D10 (5) Concrete, Steel, Masonry, Aluminium, AAC (Autoclaved Aerated Concrete), Iron, Terracotta, Porcelain, Ceramic, Natural stone, Copper, Zinc, Lead, Bronze, Brass Anywhere a non-combustible material is needed, the following materials can be usedNCC 2022 Vol 1, C2D10 (6) Plasterboard Perforated gypsum lath with a normal paper finish Fibrous plaster sheet Fibre-reinforced cement sheeting Pre-finished metal sheeting ≤ 1mm thk ≤ 0 Spread-of Flame Index Sarking type materials≤ 1mm thk ≤ 5 Flammability IndexBonded Laminated Materials Non-combustible laminas Adhesive layers ≤ 1mm thk ≤ 2mm total thickness ≤ 0 Spread of Flame Index≤ 3 Smoke Developed IndexNSW Fair Trading NSW Fair Trading ≥ 30% of PE (Polyethylene) on ACP (Aluminium Composite Panel) are banned to use in any exterior cladding NSW Fair Trading Type B Construction as defined in Building Code of AustraliaNSW Fair Trading Non-Loadbearing Building Element
Balcony & Verandah
FRL required if part of the only path leading to the building exitNCC 2022 Vol 1, S5C21 NCC 2022 Vol 1, S5C21 NCC 2022 Vol 1, S5C6 (5) Balconies & Verandahs NCC 2022 Vol 1, S5C6 (5)
FRL required for structure if part of the only path leading to the building exitRefer to Floor, External Walls & Columns for equivalent FRL requirements NCC 2022 Vol 1, S5C3 (1) S upport of Another Element NCC 2022 Vol 1, S5C3 (1)
Any element providing support to another element generally must equal in FRL &Non-combustibility Type A Construction
Type C Construction
Types of Construction
NCC 2022 Vol 1, C4D3 Compartmentation & Separation
Carpark
Elements with FRL as per main building[1] Carparking areas can be reduced FRL if separated from main building & sprinklered[2] Type B Construction Floor RULES NCC 2022 V4 Class 2 to 9
NCC 2022 S5C21 [2019 Spec 1.1: 4]
May 2023
NCC 2022 Vol 1, S5C21 (1) (f) NCC 2022 Vol 1, S5C21 (1) (f) NCC 2022 Vol 1, S5C21 (1) (g) NCC 2022 Vol 1, S5C21 (1) (f) NCC 2022 Vol 1, S5C21 (1) (g) FRL required to Class 2 or 3 (othe r than within a Sole Occupancy Unit)NCC 2022 Vol 1, S5C21 (1) (f) &Class 9a Health Care & Clas s 9b NCC 2022 Vol 1, S5C21 (1) (f) Floors & Beams that are between storeys, above parking, storage or any other ancillary space, Class 9c Floor, Beams & Columns that are above parking, storage or any other ancillary spaceNCC 2022 Vol 1, S5C21 (1) (g) Protect withNCC 2022 Vol 1, S5C21 (1) (f) NCC 2022 Vol 1, S5C21 (1) (g) A ceiling ≥ 60 minutes R esistance to the Incipient Spread of Fire (RISF) , or30/30/30 FRL , orIf combustible or metal protected from the underside with fire-protective covering Class 2 & 3 RECLASSIFICATION NCC 2022 V2 Class 2 & 3
NCC 2022 S5C9 [2019 Spec 1.1: 2.8]
May 2023
NCC 2022 Vol 1, S5C9 (1) NCC 2022 Vol 1, S5C9 (2) Class 7 is considered Class 2 (only for FRL requirements)NCC 2022 Vol 1, S5C9 (1)
If ≤ 4 storey building with Only one storey used as parking, or other ancillary purpose to Class 2 , & Remaining storeys are Class 2 Class 7 is considered Class 3 or mixed 2 & 3 (only for FRL requirements)NCC 2022 Vol 1, S5C9 (2)
If ≤ 3 storey building with Only one storey used as parking, or other ancillary purpose to Class 2 , & Remaining storeys are Class 3 or mixed 2 & 3 NCC 2022 Vol 1, S5C22 (3) NCC 2022 Vol 1, S5C22 (1) Bounding Walls
Walls bounding[1] Sole-occupancy Units Public corridors & lobbies Bounding Wall RULES NCC 2022 V2 All Building Classes
NCC 2022 S5C21 [2019 Spec 1.1: 4]
May 2023
NCC 2022 Vol 1, S5C21 (1) (c) NCC 2022 Vol 1, S5C21 (1) (c) (iv) NCC 2022 Vol 1, S5C21 (1) (c) (i) NCC 2022 Vol 1, S5C21 (1) (c) (ii) NCC 2022 Vol 1, S5C21 (1) (d) NCC 2022 Vol 1, S5C21 (1) (e) NCC 2022 Vol 1, S5C21 (1) (c) Must extend toNCC 2022 Vol 1, S5C21 (1) (c) Underside of 30/30/30 FRL NCC 2022 Vol 1, S5C21 (1) (c) (iv) floor above, or Underside of ceiling with a Resistance to the Incipient Spread of Fire (RISF) ≥ 60 minutes NCC 2022 Vol 1, S5C21 (1) (c) (i) , or Underside of roof covering if non-combustible, or ≥ 450mm NCC 2022 Vol 1, S5C21 (1) (c) (ii) above roof covering if combustibleIf Loadbearing constructed ofNCC 2022 Vol 1, S5C21 (1) (d) Concrete or Masonry Fire-protected timber (with limitations) FRL not requiredIf bounding a Sole Occupancy Unit (SOU) if is on topmost level & only unit in that levelNCC 2022 Vol 1, S5C21 (1) (e) Class 5, 6, 7, 8 or 9 building when in a Storey directly below a RoofNCC 2022 Vol 1, S5C21 (1) (c) NCC 2022 Vol 1, S5C21 (1) (a) Roof & Ceilings
FRL not required for Roof[1] Refer to Lift & Stair Shafts for enhanced requirements[2] Rooftop Structure RULES NCC 2022 V2 Class 2 to 9
NCC 2022 S5C6 [2019 Spec C1.1: 2.5]
May 2023
NCC 2022 Vol 1, S5C6 (3) No FRL requirements for the structure situated on a roof ifNCC 2022 Vol 1, S5C6 (3) Non-combustible Contains lift motor equipment, or Water tanks, or Ventilating system, or A/C chillers, or Window cleaning equipment, orOther non-combustible service units not containing flammable or combustible liquids or gases NCC 2022 Vol 1, S5C6 (3) NCC 2022 Vol 1, S5C21 (1) (a) Fire-Source Feature (FSF)
A possible fire-source where the spread of fire to the subject building is a risk[1] Allotment Boundary Adjacent building on the same allotment Fire Source Feature EXPOSURE NCC 2022 V4 Class 2 to 9
NCC 2022 C4D3 & S5C2 [2019 C3.2, Spec C1.1: 2.1]
May 2023
NCC 2022 Vol 1, Glossary NCC 2022 Vol 1, S5C2 (1) (a) NCC 2022 Vol 1, S5C2 (2) (a) NCC 2022 Vol 1, S5C2 (3) BoundariesNCC 2022 Vol 1, Glossary The far boundary of a road, river, lake or similar adjoining the allotment, or Rear & Side boundaries Elements below finished ground level at every relevant part of the boundary are not considered as exposed Adjacent Building (on same allotment)NCC 2022 Vol 1, S5C2 (1) (a) The external wall of a separate building (other than Class 10 ) > 15m above another building is not considered as exposedBarrier ElementNCC 2022 Vol 1, S5C2 (2) (a) 30/-/- FRL wall or similar that is not transparent or translucent can shield exposure to a Fire Source FeatureVarying Distance to FSF (Fire Source Feature)NCC 2022 Vol 1, S5C2 (3) FRL of any element must either beequal to the required FRL for the minimum distance of any part, or varying FRL dependant on the individual distance NCC 2022 Vol 1, Glossary A possible fire-source where the spread of fire to the subject building is a riskNCC 2022 Vol 1, Glossary Allotment Boundary Adjacent building on the same allotment Lift & Stair Shafts
Top & bottom enclosed by element with equal FRL [1] Support of a floor must not compromise the Shaft structure[2] Lift & Stair Shaft RULES NCC 2022 V1 Class 2 to 9
NCC 2022 S5C21 [2019 Spec 1.1: 4]
May 2023
NCC 2022 Vol 1, S5C21 (1) (d) NCC 2022 Vol 1, S5C21 (1) (b) NCC 2022 Vol 1, S5C21 (1) (c) (i) NCC 2022 Vol 1, S5C8 (2) (b) NCC 2022 Vol 1, S5C8 (2) (a) NCC 2022 Vol 1, S5C8 (1) NCC 2022 Vol 1, S5C21 (1) (b) (ii) Common & Fire Walls
Fire-resistant Barrier to prevent spread of fire between buildings or separate Fire Compartments[1] Common & Fire Wall RULES NCC 2022 V1 All Building Classes
NCC 2022 S5C21 [Spec C1.1: 4]
May 2023
NCC 2022 Vol 1, S5C21 (1) (c) NCC 2022 Vol 1, S5C21 (1) (d) NCC 2022 Vol 1, C3D8 (3) Fire-resistant Barrier to prevent spread of fire between buildings or separate Fire CompartmentsNCC 2022 Vol 1, C3D8 (3) Floors
FRL required between storeys & above parking & storage for most residential or public use buildings[1] [2] Type B Construction Floor RULES NCC 2022 V4 Class 2 to 9
NCC 2022 S5C21 [2019 Spec 1.1: 4]
May 2023
NCC 2022 Vol 1, S5C21 (1) (f) NCC 2022 Vol 1, S5C21 (1) (f) NCC 2022 Vol 1, S5C21 (1) (g) NCC 2022 Vol 1, S5C21 (1) (f) NCC 2022 Vol 1, S5C21 (1) (g) FRL required to Class 2 or 3 (othe r than within a Sole Occupancy Unit)NCC 2022 Vol 1, S5C21 (1) (f) &Class 9a Health Care & Clas s 9b NCC 2022 Vol 1, S5C21 (1) (f) Floors & Beams that are between storeys, above parking, storage or any other ancillary space, Class 9c Floor, Beams & Columns that are above parking, storage or any other ancillary spaceNCC 2022 Vol 1, S5C21 (1) (g) Protect withNCC 2022 Vol 1, S5C21 (1) (f) NCC 2022 Vol 1, S5C21 (1) (g) A ceiling ≥ 60 minutes R esistance to the Incipient Spread of Fire (RISF) , or30/30/30 FRL , orIf combustible or metal protected from the underside with fire-protective covering NCC 2022 Vol 1, S5C21 (1) (f) NCC 2022 Vol 1, S5C21 (1) (g) Mezzanine
Floor area of Mezzanine determines if required to have FRL [1] FRL of adjacent building elements may require upgrade[2] Mezzanine RULES NCC 2022 V3 Class 2 to 9
NCC 2022 S5C7 [2019 Spec C1.1: 2.6]
May 2023
NCC 2022 Vol 1, S5C7 (2) FRL is not required to a Mezzanine Floor or its support ifNCC 2022 Vol 1, S5C7 (2) Total Floor Area of all Mezzanines in a room is the lesser of ≤ 200m² or ≤ 1/3rd of the Floor Area, &FRL of each Wall & Column that supports another part of the building ≤ 6m from the Mezzanine is increased as per table belowNCC 2022 Vol 1, S5C7 (2) (a) NCC 2022 Vol 1, S5C7 (2) (b) Protection of Openings
If a wall requires an FRL , then any openings must also be protected[1] , & ≤ 1/3 Area of the external wall of the Storey is allowed to be an opening (Doors, Windows etc) [2] Class 9b Spectator Stand is excluded from this rule [3] Protection of Openings NCC 2022 V1 Class 2 to 9
NCC 2022 C4D5, S12 [2019 C3.4, S3.4]
1 May 2023
NCC 2022 Vol 1, C4D5 (1) (a) (ii) NCC 2022 Vol 1, C4D5 (1) (a) (i) NCC 2022 Vol 1, C4D5 (1) (b) (ii) NCC 2022 Vol 1, C4D5 (1) (b) (iii) NCC 2022 Vol 1, C4D5 (1) (c) (ii) NCC 2022 Vol 1, C4D3 (3) NCC 2022 Vol 1, C4D3 (3) NCC 2022 Vol 1, C4D3 (1) Internal Walls & Columns
Structure component of FRL required only[1] [2] Internal Loadbearing Element RULES NCC 2022 V2 Class 2 to 9
NCC 2022 S5C21 [2019 Spec 1.1: 4]
May 2023
NCC 2022 Vol 1, S5C21 (1) (d) NCC 2022 Vol 1, S5C21 (1) (e) NCC 2022 Vol 1, S5C21 (1) (c) NCC 2022 Vol 1, S5C21 (1) (c) NCC 2022 Vol 1, S5C21 (1) (d) External Walls & Columns
FRL varies dependant on distance from Fire-source Feature (FSF) [1] Non-combustible Curtain or Panel Walls do not require an FRL if sprinklered[2] External Wall & Column RULES NCC 2022 V2 Class 2 to 9
NCC 2022 S5C21 [2019 Spec 1.1: 4]
May 2023
NCC 2022 Vol 1, S5C21 (1) (a) NCC 2022 Vol 1, S5C21 (1) (a) NCC 2022 Vol 1, S5C6 (4) External Freestanding Column
FRL affected by distance from Fire-source Feature (FSF)[1] [2] External Column FRL NCC 2022 V2 Class 2 to 9
NCC 2022 S5C21 [2019 Spec 1.1: 4]
May 2023
NCC 2022 Vol 1, S5C21 (1) (a) NCC 2022 Vol 1, S5C21 (1) (a) NCC 2022 Vol 1, S5C21 (1) (a) NCC 2022 Vol 1, S5C21 (3) Redirecting... (5)