AS 1657:2018, 7.4.7 (g)
AS 1657:2018, 7.4.8.1
AS 1657:2018, 7.4.3.5
AS 1657:2018, 7.4.8.1
AS 1657:2018, 7.4.8.1
AS 1657:2018, 7.4.7 (g)
AS 1657:2018, 7.4.3.4
AS 1657:2018, 7.3.6 (b)
AS 1657:2018, 7.4.8.1
AS 1657:2018, 7.4.5 (d)
AS 1657:2018, 7.4.3.1
AS 1657:2018, 7.4.2.1
AS 1657:2018, 7.4.3.2 (a)
AS 1657:2018, 2.2 (e)
AS 1657:2018, 7.3.6 (a)
AS 1657:2018, 7.4.5 (a)
AS 1657:2018, 7.3.2
AS 1657:2018, 7.4.8.2
AS 1657:2018, 4.1.1
Bottom Rung
- ≤ 90% reduction to rung spacing allowed for tolerance[1]
- Measured from centre line
Rung RULES
NCC 2022 V1
All Building Classes
NCC 2022 D2D21, D2D22, I1D6, I3D5
[2019 D1.16 - 17, H1.6, H3.5]
May 2023
AS 1657:2018, 7.4.3.1
AS 1657:2018, 7.4.3.2 (a)
AS 1657:2018, 7.4.3.2 (b)
AS 1657:2018, 7.4.3.4
AS 1657:2018, 7.4.3.1
- Access to a service platform, rigging loft, and the like, to comply to NCC Parts D2, I1, I3, & AS 1657
- Ø 20 to 50mm, top may be flattenedAS 1657:2018, 7.4.3.1
- R = 250 to 300mmAS 1657:2018, 7.4.3.2 (a) evenly spaced, measure
- to centreline
- spacing, not riser height
- R can reduce if ladder length ≤ 1mAS 1657:2018, 7.4.3.2 (b)
- R at base can be reduced by ≤ 90%AS 1657:2018, 7.4.3.4
- ± 5mm tolerance allowed ± 2mm preferred
- Top rung level with Landing
- Slip-resistant to top surfaceAS 1657:2018, 7.4.3.1
- Corrugated, knurled
- Coated
- If Steel
- Hot-dip galvanised or
- Coated with corrossion-resistant material
- Fastened securely & fixed in place
AS 1657:2018, 7.4.3.4
Step Through Access
- ≥ 1m extension of Stiles[1]
- 525 to 675mm between Stiles[2]
- No or 50 to 100mm gap Rung to Landing[3]
- 50mm hand clearance around Stiles[4]
Top Access RULES
NCC 2022 V1
All Building Classes
NCC 2022 D2D21, D2D22, I1D6, I3D5
[2019 D1.16 - 17, H1.6, H3.5]
May 2023
AS 1657:2018, 7.4.8.1
AS 1657:2018, 7.4.8.2
- Access to a service platform, rigging loft, and the like, to comply to NCC Parts D2, I1, I3, & AS 1657
- Fixed ladders must allow for safe access at Landings
- Step through ladders must be wider between stilesAS 1657:2018, 7.4.8.1
- ≥ 1m extension of Stiles
- 525 to 675mm clearance
- 50mm hand clearance around Stiles (ladder brackets & cage fixings may intrude)
- Side Access part of ladder must be consistent with belowAS 1657:2018, 7.4.8.2
- ≥ 1m extension of Rungs & Stiles
- 90 to 175mm gap between Stile & Landing
AS 1657:2018, 7.4.8.1
AS 1657:2018, 7.4.8.1
AS 1657:2018, 7.4.8.1
AS 1657:2018, 7.4.8.1
Fall Risk
- > 6m fall risk requires a Ladder Cage[1]
Fall Prevention RULES
NCC 2022 V1
All Building Classes
NCC 2022 D2D21, D2D22, I1D6, I3D5
[2019 D1.16 - 17, H1.6, H3.5]
May 2023
AS 1657:2018, 7.4.7 (b)
AS 1657:2018, 7.4.7 (c)
AS 1657:2018, 7.4.7 (d)
AS 1657:2018, 7.4.7 (a)
- Access to a service platform, rigging loft, and the like, to comply to NCC Parts D2, I1, I3, & AS 1657
- Fall arrest system to AS/NZS 1891 may be used where a cage is not practical
- Fall risk should take into account if possible to fall past the bottom landing
- Ladder cage shall
- not allow Ø 150mm sphere to pass throughAS 1657:2018, 7.4.7 (b)
- extend 1m above top landing or to height of guardrailAS 1657:2018, 7.4.7 (c)
- terminate 2m to 2.2m above bottom landingAS 1657:2018, 7.4.7 (d)
- have no internal projectionsAS 1657:2018, 7.4.7 (a)
AS 1657:2018, 7.3.2
Stile
- Ø 40 to 80mm cross sectional profile[1]
- 50mm clearance[2]
Stile RULES
NCC 2022 V1
All Building Classes
NCC 2022 D2D21, D2D22, I1D6, I3D5
[2019 D1.16 - 17, H1.6, H3.5]
May 2023
AS 1657:2018, 7.4.2.1
AS 1657:2018, 7.4.2.2
- Access to a service platform, rigging loft, and the like, to comply to NCC Parts D2, I1, I3, & AS 1657
- 375 to 525mm clearance between StilesAS 1657:2018, 7.4.2.1
- Cross sectional profile may be any shape provided it fits within a Ø 40 to 80mm circleAS 1657:2018, 7.4.2.2
AS 1657:2018, 7.4.2.2
AS 1657:2018, 7.4.8.1
Landings
- ≥ 900mm Length[1]
- ≥ 600mm Width[2]
- ≤ 6m between landings[3]
Landing RULES
NCC 2022 V3
All Building Classes
NCC 2022 D2D21, D2D22, D3D15, I1D6, I3D5
[2019 D1.16 - 17, D2.14, H1.6, H3.5]
May 2023
AS 1657:2018, 4.1.1
AS 1657:2018, 5.1.1 (b)
AS 1657:2018, 7.3.6 (c)
AS 1657:2018, 3.2.3.2
AS 1657:2018, 3.2.3.4
AS 1657:2018, 4.5
AS 1657:2018, 5.5
- Access to a service platform, rigging loft, and the like, to comply to NCC Parts D2, D3, I1, I3, & AS 1657
- ≤ 3° slope in any directionAS 1657:2018, 4.1.1
- ≤ 7° allowed where fixed to a sloping RoofAS 1657:2018, 5.1.1 (b)
- ≥ 2m headroomAS 1657:2018, 7.3.6 (c)
- ≤ 10mm gap between floor panelsAS 1657:2018, 3.2.3.2
- ≤ 45mm openings in floor grate (≤ 5000mm² opening area)AS 1657:2018, 3.2.3.4
- Protect area below a platform from falling objects
- > Ø15mm through Floor GratingAS 1657:2018, 4.5 or 12mm square mesh suspended below
- ≤ 10mm gap to side of floor with a Toe board or other permanent structure besideAS 1657:2018, 5.5
AS 1657:2018, 7.3.6 (a)
AS 1657:2018, 7.3.6 (b)
AS 1288:2006, 7.3.6
AS 1657:2018, 3.1.5
Side Access
- Shown dashed
- ≥ 1m extension of Rungs & Stiles[1]
- 375 to 525mm between stiles[2]
- 90 to 175mm gap from Stile to Landing[3]
Top Access RULES
NCC 2022 V1
All Building Classes
NCC 2022 D2D21, D2D22, I1D6, I3D5
[2019 D1.16 - 17, H1.6, H3.5]
May 2023
AS 1657:2018, 7.4.8.1
AS 1657:2018, 7.4.8.2
- Access to a service platform, rigging loft, and the like, to comply to NCC Parts D2, I1, I3, & AS 1657
- Fixed ladders must allow for safe access at Landings
- Step through ladders must be wider between stilesAS 1657:2018, 7.4.8.1
- ≥ 1m extension of Stiles
- 525 to 675mm clearance
- 50mm hand clearance around Stiles (ladder brackets & cage fixings may intrude)
- Side Access part of ladder must be consistent with belowAS 1657:2018, 7.4.8.2
- ≥ 1m extension of Rungs & Stiles
- 90 to 175mm gap between Stile & Landing
AS 1657:2018, 7.4.8.2
AS 1657:2018, 7.4.2.1
AS 1657:2018, 7.4.8.2
Rungs
- Ø 20 to 50mm[1]
- Top slip resistant
- R = 250 to 300mm equally spaced[2]
- Top rung level with Landing
Rung RULES
NCC 2022 V1
All Building Classes
NCC 2022 D2D21, D2D22, I1D6, I3D5
[2019 D1.16 - 17, H1.6, H3.5]
May 2023
AS 1657:2018, 7.4.3.1
AS 1657:2018, 7.4.3.2 (a)
AS 1657:2018, 7.4.3.2 (b)
AS 1657:2018, 7.4.3.4
AS 1657:2018, 7.4.3.1
- Access to a service platform, rigging loft, and the like, to comply to NCC Parts D2, I1, I3, & AS 1657
- Ø 20 to 50mm, top may be flattenedAS 1657:2018, 7.4.3.1
- R = 250 to 300mmAS 1657:2018, 7.4.3.2 (a) evenly spaced, measure
- to centreline
- spacing, not riser height
- R can reduce if ladder length ≤ 1mAS 1657:2018, 7.4.3.2 (b)
- R at base can be reduced by ≤ 90%AS 1657:2018, 7.4.3.4
- ± 5mm tolerance allowed ± 2mm preferred
- Top rung level with Landing
- Slip-resistant to top surfaceAS 1657:2018, 7.4.3.1
- Corrugated, knurled
- Coated
- If Steel
- Hot-dip galvanised or
- Coated with corrossion-resistant material
- Fastened securely & fixed in place
AS 1657:2018, 7.4.3.1
AS 1657:2018, 7.4.3.2 (a)