Walkways
Clear width measure between Guardrailings, Structures, or width of walking surface[1] Ensure crossfall for water drainage [2] Provide protection for Ramps ≥ 18m [3] Walkways CLEARANCES NCC 2022 V1 All Building Classes
NCC 2022 Vol 1, D3D23 [2019 D2.18]
May 2023
AS 1657:2018, 5.1.3 NCC 2022 Vol 1, D3D23 Clear Width NCC 2022 Vol 1, D3D23
≥ 600mm with no edge protection ≥ 550mm with Guardrailing on both sides ≥ 600mm with a permanent structure on one or both sides within 100mm from the Walkway Measured between structures, or From the inside of any Guardrails Slope RULES NCC 2022 V2 All Building Classes
NCC 2022 Vol 1, D3D23 [2019 D2.18]
May 2023
NCC 2022 Vol 1, D3D23 AS 1657:2018, 5.1.1 AS 1657:2018, 5.4.2 Walkways AS 1657:2018, 5.1.1
≤ 3° Slope in all directions to allow water drainageRamp
≥ 18m Ramp Length requires Fall & Roll ProtectionAS 1657:2018, 5.4.2 Barrier, or ≥ 2m Landing, or90° nom change in direction with Guardrailing installed15° to 20° must provide HandrailAS 1657:2018, 5.4.2 AS 1657:2018, 5.1.3 AS 1657:2018, 5.1.1 Handrail
Required for ramp with slope 15° to 20° [1] Handrail RULES NCC 2022 V2 All Building Classes
NCC 2022 Vol 1, D3D22 [2019 D2.18]
May 2023
NCC 2022 Vol 1, D3D22 AS 1657:2018, 5.6 Dimension and clearances for Handrails to the NCCNCC 2022 Vol 1, D3D22 Handrail Profile may beAS 1657:2018, 5.6 900 to 1100mm height from Walkway surface≥ 50mm clearance from adjacent structure≥ 240mm clearance for longitudinal movementØ 30 to 65mm if circular, or30 to 60mm width if square or rectangular, where Sum of height and width between 70 to 100mm Round edges fixed in place to prevent injuries Clearance as per image below AS 1657:2018, 5.4.2 Headroom
Should allow passage of a person standing upright[1] Headroom RULES NCC 2022 V1 All Building Classes
NCC 2022 Vol 1, D3D23 [2019 D2.18]
May 2023
NCC 2022 Vol 1, D3D23 AS 1657:2018, 3.1.5 Height for Headroom to the NCCNCC 2022 Vol 1, D3D23 ≥ 2m above finished floor levelAS 1657:2018, 3.1.5 Increased where helmets are worn, while < 2m above finished floor level as a limited exception Padding, highlighting, signage, or additional lighting should be provided AS 1657:2018, 3.1.5 AS 1657:2018, 5.1.1 (b) AS 1657:2018, 5.1.1 (b) AS 1657:2018, 7.2.1 AS 1657:2018, 3.1.5 Guardrailing
Not required if permanent Structure ≤ 100mm from walkway[1] Toeboard installed where no permanent structures within 10mm of edges [2] Toeboard RULES NCC 2022 V2 All Building Classes
NCC 2022 Vol 1, D3D23 [2019 D2.18]
May 2023
NCC 2022 Vol 1, D3D23 AS 1657:2018, 5.5 Requirements for Toeboard to the NCCNCC 2022 Vol 1, D3D23 Installed on edge of a Walkway whereAS 1657:2018, 5.5 There is no permanent structure within 10mm of Walkway edge An object could fall below and to the side of the Walkway ≤ 10mm Walkway edge clearance from any structure≤ 10mm Gap between underside of Toeboard and Walkway Surface≥ 100mm Distance between top of toe board and permanent structureGuardrailing RULES NCC 2022 V2 All Building Classes
NCC 2022 Vol 1, D3D23 [2019 D2.18]
May 2023
NCC 2022 Vol 1, D3D23 AS 1657:2018, 5.4.1 AS 1657:2018, 6.2.1.1 AS 1657:2018, 5.4.1 Requirements for Guardrailing to the NCCNCC 2022 Vol 1, D3D23 Must be installed on all sides of a walkway to prevent people from reaching adjacent area, if adjacent areaAS 1657:2018, 5.4.1 Has ≥ 12° slope, or Is not fit for walking on ≥ 900mm above the floor AS 1657:2018, 6.2.1.1 , or ≥ 1m to provide additional safety Significant fall height or strong wind forces Exceptions AS 1657:2018, 5.4.1
Points of access from Stairways & Ladder Permanent structure ≤ 100mm from the edge of the Walkway ≤ 300mm above an adjacent safe area &≤ 3° cross-slope to Walkway,≤ 12° downslope to adjacent area, &≥ 2m width of adjacent areaAS 1657:2018, 7.2.5 AS 1657:2018, 6.1.2 Redirecting... (5)