Stairs (Maintenance Access) Building Codes & Rules


- Design safe maintenance stairs for plant rooms: 600 mm width, 600 mm landings, guardrails, non‑slip treads, and durable materials.


AS 1657:2018, 4.5

Protective MeshAS 1657:2018, 4.5

  • Required where
  • Space below is accessible
  • Walkway surface is grated or perforated
  • ≤ 15mm gaps to prevent falling debris

AS 1657:2018, 6.2.1.2 (b)

≤ 450AS 1657:2018, 6.2.1.2 (b)

AS 1657:2018, 5.5

≥ 100AS 1657:2018, 5.5

AS 1657:2018, 6.2.1.2 (b)

≤ 450AS 1657:2018, 6.2.1.2 (b)

AS 1657:2018, 7.2.1

20° to 45°AS 1657:2018, 7.2.1

AS 1657:2018, 5.5

≤ 10AS 1657:2018, 5.5

AS 1657:2018, 6.2.1.1

900

to

1mAS 1657:2018, 6.2.1.1

Toeboard

AS 1657:2018, 7.2.1

≥ 600AS 1657:2018, 7.2.1

AS 1657:2018, 5.6.2

900

to

1.1mAS 1657:2018, 5.6.2

AS 1657:2018, 8.3

AS 1657:2018, 8.2

Label InstallationAS 1657:2018, 8.3

  • ≥ 7 years labels life expectancy
  • Durable & clearly readable with informational requirements -
  • Name of Installer, Manufacturer & Certifier
  • Installation & Inspection Date
  • Note compliance with Manufacturer’s Recommendations & AS 1657:2018
  • Non-conformance will be noted on the certificate, with a label affixed if the installation fails to meet the standard

Label DocumentationsAS 1657:2018, 8.2

  • Documentation requirements such
  • Listing of any unique components' Serial Numbers,
  • Any special provisional use such training, add'l equipment, etc.
  • Mandated Inspection, Testing, & Servicing schedule
  • Other additional relevant information
  • Conforming statement with AS 1657 & other relevant standards

AS 1657:2018, 7.2.2

Flight 2 to 18 RisersAS 1657:2018, 7.2.2

AS 1657:2018, 7.2.3.2

≤ 30AS 1657:2018, 7.2.3.2

AS 1657:2018, 7.2.1

≥ 550AS 1657:2018, 7.2.1

AS 1657:2018, 3.1.5

2m clearAS 1657:2018, 3.1.5

AS 1657:2018, 7.2.2

Stairs FlightAS 1657:2018, 7.2.2

  • 2 to 18 risers in a single flight
  • ≤ 36 Riser Fall Risk limited by
  • ≥ 2m landing length
  • Barrier
  • ≥ 90° direction change

AS 1657:2018, 7.2.3

Treads & RisersAS 1657:2018, 7.2.3

  • 130 to 225mm Riser
  • 215 to 355mm Going
  • ± 5mm overall Tolerance
  • Slip-resistant material

AS 1657:2018, 7.2.3

RAS 1657:2018, 7.2.3

AS 1657:2018, 7.2.3

GAS 1657:2018, 7.2.3

Nosing Line

AS 1657:2018, 6.2.1.4

Stairs Guardrail InfillAS 1657:2018, 6.2.1.4

  • Constructed from
  • Pipe,
  • Solid or Perforated Plate,
  • Expanded Mesh,
  • Weldmesh, or
  • Other material with same characteristics
  • ≤ 0.2 m² mesh opening
  • Free from sharp edges

Fall

Handrail

Protective Mesh

AS 1657:2018, 7.2.4

LandingsAS 1657:2018, 7.2.4

  • ≥ 600mm length
  • ≥ 600mm standing space
  • free from door swings and any obstructions

AS 1657:2018, 6.2.1.2 (c)

≤ 560AS 1657:2018, 6.2.1.2 (c)

AS 1657:2018, 6.2.1.1

≥ 50AS 1657:2018, 6.2.1.1

AS 1657:2018, 7.2.6

Gap between HandrailsAS 1657:2018, 7.2.6

  • 50 to 100 Vertical closure bend
  • ≥ 100 Continuous Top & Intermediate Railing

Any Direction

AS 1657:2018, 4.1.1

≤ 3°AS 1657:2018, 4.1.1

Maintenance Access Selector

Handrail


  • ≥ 1m stairs width[1]
  • Provide handrails on both sides
  • Free from obstructions


Handrail RULES


NCC 2022 V2


All Building Classes


NCC 2022 Vol 1, D3D22 [2019 D2.18]


May 2023



NCC 2022 Vol 1, D3D22

AS 1657:2018, 5.6

  • Dimension and clearances for Handrails to the NCCNCC 2022 Vol 1, D3D22
  • Handrail Profile may beAS 1657:2018, 5.6
  • 900 to 1100mm height from Walkway surface
  • ≥ 50mm clearance from adjacent structure
  • ≥ 240mm clearance for longitudinal movement
  • Ø 30 to 65mm if circular, or
  • 30 to 60mm width if square or rectangular, where
  • Sum of height and width between 70 to 100mm
  • Round edges fixed in place to prevent injuries
  • Clearance as per image below

AS 1657:2018, 7.2.6

Headroom


  • Should allow passage of a person standing upright[1]


Headroom RULES


NCC 2022 V1


All Building Classes


NCC 2022 Vol 1, D3D23 [2019 D2.18]


May 2023



NCC 2022 Vol 1, D3D23

AS 1657:2018, 3.1.5

  • Height for Headroom to the NCCNCC 2022 Vol 1, D3D23
  • ≥ 2m above finished floor levelAS 1657:2018, 3.1.5
  • Increased where helmets are worn, while
  • < 2m above finished floor level as a limited exception
  • Padding, highlighting, signage, or additional lighting should be provided

AS 1657:2018, 3.1.5

Guardrailing


  • Not required if permanent Structure ≤ 100mm from walkway[1]
  • Toeboard installed where no permanent structures within 10mm of edges[2]


Toeboard RULES


NCC 2022 V2


All Building Classes


NCC 2022 Vol 1, D3D23 [2019 D2.18]


May 2023



NCC 2022 Vol 1, D3D23

AS 1657:2018, 5.5

  • Requirements for Toeboard to the NCCNCC 2022 Vol 1, D3D23
  • Installed on edge of a Walkway whereAS 1657:2018, 5.5
  • There is no permanent structure within 10mm of Walkway edge
  • An object could fall below and to the side of the Walkway
  • ≤ 10mm Walkway edge clearance from any structure
  • ≤ 10mm Gap between underside of Toeboard and Walkway Surface
  • ≥ 100mm Distance between top of toe board and permanent structure

Guardrailing RULES


NCC 2022 V2


All Building Classes


NCC 2022 Vol 1, D3D23 [2019 D2.18]


May 2023



NCC 2022 Vol 1, D3D23

AS 1657:2018, 5.4.1

AS 1657:2018, 6.2.1.1

AS 1657:2018, 5.4.1

  • Requirements for Guardrailing to the NCCNCC 2022 Vol 1, D3D23
  • Must be installed on all sides of a walkway to prevent people from reaching adjacent area, if adjacent areaAS 1657:2018, 5.4.1
  • Has ≥ 12° slope, or
  • Is not fit for walking on
  • ≥ 900mm above the floorAS 1657:2018, 6.2.1.1, or
  • ≥ 1m to provide additional safety
  • Significant fall height or strong wind forces

ExceptionsAS 1657:2018, 5.4.1

  • Points of access from Stairways & Ladder
  • Permanent structure ≤ 100mm from the edge of the Walkway
  • ≤ 300mm above an adjacent safe area &
  • ≤ 3° cross-slope to Walkway,
  • ≤ 12° downslope to adjacent area, &
  • ≥ 2m width of adjacent area

AS 1657:2018, 7.2.5

AS 1657:2018, 6.1.2