Construction Requirements BAL-19 Building Codes & Rules


- Comply with Bushfire Construction Requirements with Tools™: BAL-19 requirements, fire danger insights, & detailed guidance for walls, roof, guttering & more!


Permanently Closed Window

Self-closing

Fire Door

Garage Door

NSW RFS 2019 PBP, 7.6

Fencing

-/60/60 FRL

AS 3959:2018, 3.2.1 (a) (i)

-/60/30 FRLAS 3959:2018, 3.2.1 (a) (i)

Bushfire Shutter (optional)

AS 3959:2018, 3.2.3 (a)

> 6mAS 3959:2018, 3.2.3 (a)

AS 3959:2018, 3.2.1 (a)

-/60/60 FRLAS 3959:2018, 3.2.1 (a)

Wall

AS 3959:2018, 3.2.1 (a) (ii)

-/60/- FRLAS 3959:2018, 3.2.1 (a) (ii)

AS 3959:2018, 3.2.1

Wall & Openings Fire Separated from GarageAS 3959:2018, 3.2.1

  • Only if the attached Garage is not constructed to BAL requirements

Eaves & Fascias


Change the description


Change the description

Fire Door

Skylights


  • Sealed & of Grade A Safety Glass[1]


Skylight RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.6.5 (e)

AS 3959:2018, 6.6.5

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • SkylightAS 3959:2018, 6.6.5 (e)
  • Sealed / fully flashed with non-combustible material
  • Grade A safety glass to AS 1288
  • Polymer skylight allowed with Grade A safety glass diffuser below glazing
  • Insulated glazing unit requires ≥ 4mm thick Grade A toughened safety glass to outer panel
  • Tubular SkylightsAS 3959:2018, 6.6.5
  • Flashing may consist of fire-retardant materials
  • ≤ 5 Flammability Index of under-flashing

AS 3959:2018, 6.6.5

Windows & Glazed Doors


  • Openable Screens[1]
  • ≥ 5mm Toughened Glazing[2]


Ember Holding Surface


NCC 2022 V3


  • Remember
  • Embers can blow & accumulate against a vertical building element causing it to ignite
  • Any surface including ground, deck, or roof can hold embers if < 18° slope & if > 110mm width

Screen RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 3.6.1

AS 3959:2018, 6.4.3

Bushfire Resisting Timber BAL-19


NCC 2022 V3


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to NCC Specification 1, NCC Part G5, & AS 3959
  • Bushfire-resisting Timber to AS 3959
  • Timber species per AS 3959
  • Any solid, laminated, treated, or reconstituted timber meeting BAL-19 compliance

Window RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.5.3 (c) (i)

AS 3959:2018, 6.5.3 (c) (v)

AS 3959:2018, 6.5.3 (c) (iii)

AS 3959:2018, 6.5.3 (a)

AS 3959:2018, 6.5.3 (b)

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • GlazingAS 3959:2018, 6.5.3 (c) (i)
  • ≥ 5mm toughened glass for glazing < 400mm above a deck, ground, or other ember-holding surfaces
  • If double-glazed, apply to outer pane
  • Glass blocks
  • AS 1288 compliant annealed glass allowed for other windows
  • FramesAS 3959:2018, 6.5.3 (c) (v)
  • Frames to be metal, bushfire-resisting timber, allowed timber species, or metal-reinforced uPVC
  • Metal reinforcement to be of aluminium, stainless steel, or corrosion-resistant steel
  • ScreensAS 3959:2018, 6.5.3 (c) (iii)
  • Screen to openable panels
  • If annealed, externally screen both fixed & openable portions
  • Metal, bushfire-resisting timber, or allowed timber species
  • No requirements on window if
  • Protected by a bushfire shutter, orAS 3959:2018, 6.5.3 (a)
  • Protected by screensAS 3959:2018, 6.5.3 (b)

AS 3959:2018, 6.5.3 (c) (v)

AS 3959:2018, 6.5.3 (c) (iii)

Fire-stopping Penetrations

Roofing


  • Assembly[1]
  • Non-combustible materials
  • Fully sarked, junctions sealed
  • Vents fitted with ember guards


Eaves & Fascia RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.6.6

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • Roof ComponentsAS 3959:2018, 6.6.6
  • Gables constructed as per wall requirements
  • Fit openings for ventilation of eaves, with ember guards & protect with screens
  • Seals to be of corrosion-resistant aluminium, bronze, or steel
  • Seal joints with timber storm moulds or plastic joining strips

Tiled Roof RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.6.2

AS 3959:2018, 6.6.2

Roofing RULES


NCC 2022 V1


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.6.1

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • RoofingAS 3959:2018, 6.6.1
  • Non-combustible cover
  • Seal Roof/Roof & Roof/Wall junctions, or
  • Backed with a breathable sarking or mesh
  • Fit roof ventilation openings with non-combustible ember guards, or screens
  • Evaporative coolers AS/NZS 60335.2.98 compliant
  • If with an internal damper preventing ember entry, does not require external screening

Guttering RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.6.7

Penetration RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.6.5

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • Roof PenetrationAS 3959:2018, 6.6.5
  • Sealed with non-combustible material
  • Openings screened
  • ≥ 4mm toughened Grade A safety glass for overhead glazing 
  • Fit evaporative coolers with non-combustible butterfly closers, or
  • Non-combustible covers with screens ≤ 2mm aperture size or opening

Screen RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 3.6.1

AS 3959:2018, 6.4.3

Skylight RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.6.5 (e)

AS 3959:2018, 6.6.5

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • SkylightAS 3959:2018, 6.6.5 (e)
  • Sealed / fully flashed with non-combustible material
  • Grade A safety glass to AS 1288
  • Polymer skylight allowed with Grade A safety glass diffuser below glazing
  • Insulated glazing unit requires ≥ 4mm thick Grade A toughened safety glass to outer panel
  • Tubular SkylightsAS 3959:2018, 6.6.5
  • Flashing may consist of fire-retardant materials
  • ≤ 5 Flammability Index of under-flashing

Metal Sheet Roof RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.6.3

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • Sheet RoofsAS 3959:2018, 6.6.3
  • Fully sarked over battens
  • Insulation blankets with foil backing can be placed above the battens
  • Seal gaps along fascia, ridges, hips, & wall lines by any of the following
  • Mesh or perforated screen
  • Mineral wool
  • Non-combustible material

AS 3959:2018, 6.6.1

  • AssemblyAS 3959:2018, 6.6.1
  • Non-combustible materials
  • Fully sarked, junctions sealed
  • Vents fitted with ember guards

Decks & Landing


  • Fully enclosing a sub-floor will provide protection[1]
  • Non-combustible material[2]


Deck & Landing RULES


NCC 2022 V4


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.7.1

AS 3959:2018, 6.7.2.4

AS 3959:2018, 6.7.2.1

NSW RFS 2019 PBP, 7.5.2

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • Decking may be spacedAS 3959:2018, 6.7.1 & has no requirements unless < 300mm horizontally & < 400mm vertically from a glazed Window or DoorAS 3959:2018, 6.7.2.4, then must be
  • Non-combustible material
  • Bushfire-resisting Timber
  • Allowed Timber Species
  • If Enclosing Walls are constructed & ≤ 400mm from groundAS 3959:2018, 6.7.2.1
  • Non-combustible material, or
  • Bushfire-resisting Timber, or
  • Allowed Timber Species

NSW Enhanced RULESNSW RFS 2019 PBP, 7.5.2

  • Decks, Landings & Stairs must be constructed to BAL-29 requirements
  • All elements must be
  • Non-combustible material, or
  • Bushfire-resisting Timber

Bushfire-resisting Timber BAL-19


NCC 2022 V4


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, F4

AS 3959:2018, E1

AS 3959:2018, 1.5.5

AS 3959:2018, 6.7.2.4

AS 3959:2018, 6.3.2.1

Penetrations


  • Protection[1]
  • Sealed with non-combustible materials
  • Screen all openings


Penetration RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.6.5

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • Roof PenetrationAS 3959:2018, 6.6.5
  • Sealed with non-combustible material
  • Openings screened
  • ≥ 4mm toughened Grade A safety glass for overhead glazing 
  • Fit evaporative coolers with non-combustible butterfly closers, or
  • Non-combustible covers with screens ≤ 2mm aperture size or opening

Screen RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 3.6.1

AS 3959:2018, 6.4.3

AS 3959:2018, 6.6.5

Doors, Frames, Sidelights


  • Doors with seals all round[1]
  • Non-combustible Panels[2]
  • Framing materials[3]
  • Metal
  • Bushfire-resistant timber
  • Allowed timber species
  • Metal-reinforced uPVC
  • ≥ 5mm Toughened Glass[4]


Door RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.5.4 (c) (v)

AS 3959:2018, 6.5.4 (c) (vii)

AS 3959:2018, 6.5.4 (c) (i)

AS 3959:2018, 6.5.4 (c) (ii)

AS 3959:2018, 6.5.4 (c) (iv)

AS 3959:2018, 6.5.4 (a)

AS 3959:2018, 6.5.4 (b)

Bushfire-resisting Timber BAL-19


NCC 2022 V4


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, F4

AS 3959:2018, E1

AS 3959:2018, 1.5.5

Screen RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 3.6.1

AS 3959:2018, 6.4.3

AS 3959:2018, 6.5.4 (c) (v)

AS 3959:2018, 6.5.4 (c) (i) (A)

AS 3959:2018, 6.5.4 (c) (iv)

AS 3959:2018, 6.5.4 (c) (ii)

Garage & Carport Under


  • All elements to BAL-19 Rules[1], or
  • Fire separated


Carport or Garage Under or Partially Under a Building


NCC 2022 V2


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 3.2.2 (a)

AS 3959:2018, 3.2.2 (b)

AS 3959:2018, 3.2.2

AS 3959:2018, 3.2.2

Floor & Balcony


  • Fully enclosing the sub-floor will provide protection[1]
  • Non-combustible materials if unenclosed[2]


Unenclosed Sub-floor RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.2

AS 3959:2018, 6.3.2.2 (a) (i)

AS 3959:2018, 6.3.2.2 (a) (ii)

Bushfire-resisting Timber BAL-19


NCC 2022 V4


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, F4

AS 3959:2018, E1

AS 3959:2018, 1.5.5

Sub-floor Support RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.2

AS 3959:2018, 6.2

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • Unenclosed SubfloorAS 3959:2018, 6.2
  • Non-combustible material
  • Bushfire-resisting timber or approved timber species
  • Avoid storing combustible materials in the Subfloor space
  • No requirements when Subfloor space is enclosed withAS 3959:2018, 6.2
  • BAL-19 compliant Wall, or
  • Protected by screens

Fully-enclosed Sub-floor RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.3.2.1

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • No requirements when subfloor is enclosed withAS 3959:2018, 6.3.2.1
  • BAL-19 compliant wall, or
  • Protected by screens
  • ≤ 2mm aperture size or opening
  • Aluminium, bronze, or corrosion-resistant steel

Ember Holding Surface


NCC 2022 V3


  • Remember
  • Embers can blow & accumulate against a vertical building element causing it to ignite
  • Any surface including ground, deck, or roof can hold embers if < 18° slope & if > 110mm width

Screen RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 3.6.1

AS 3959:2018, 6.4.3

Wall Construction RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.4.1

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • External Wall ≤ 400mm from Ground or DecksAS 3959:2018, 6.4.1
  • Wall must be fully sarked
  • ≥ 90mm thk Non-combustible materials
  • Masonry Wall
  • Precast Concrete Wall
  • Earth Wall (Mud Brick)
  • ≥ 90mm thk Timber logs (≥ 680kg/m³ density)
  • Cladding secured to the exterior of a timber or steel-framed wall.
  • Non-combustible material
  • ≥ 6mm Fibre-cement
  • Bushfire-resisting Timber
  • Approved Timber Species
  • Steel sheeting
  • Any combination of the options above

AS 3959:2018, 6.3.2.2

AS 3959:2018, 6.3.2.1

Wall Lining Installation (FRL)

Eaves & Fascia


  • Roof Components[1]
  • Gables shall follow same rules as per Fire Wall
  • Eaves penetrations screened
  • Joints sealed


Eaves & Fascia RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.6.6

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • Roof ComponentsAS 3959:2018, 6.6.6
  • Gables constructed as per wall requirements
  • Fit openings for ventilation of eaves, with ember guards & protect with screens
  • Seals to be of corrosion-resistant aluminium, bronze, or steel
  • Seal joints with timber storm moulds or plastic joining strips

Screen RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 3.6.1

AS 3959:2018, 6.4.3

AS 3959:2018, 6.6.6

  • Roof ComponentsAS 3959:2018, 6.6.6
  • Gables shall follow same rules as per Fire Wall
  • Eaves penetrations screened
  • Joints sealed

Sarking


  • ≤ 5 Flammability Index[1]
  • Roofs need a full layer of Sarking[2]


Sarking RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 3.10

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • SarkingAS 3959:2018, 3.10
  • ≤ 5 Flammability Index
  • Non-combustible material
  • Continuous to the outside to walls & roof
  • Type of Sarking varies on structural location, consulting a professional is recommended

AS 3959:2018, 3.10

AS 3959:2018, 6.6

Walls


  • Non-combustible material[1]
  • Bushfire-resisting Timber[2]
  • Joints sealed or covered[3]


Jointing RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.4.2

Bushfire-resisting Timber BAL-19


NCC 2022 V4


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, F4

AS 3959:2018, E1

AS 3959:2018, 1.5.5

Ember Holding Surface


NCC 2022 V3


  • Remember
  • Embers can blow & accumulate against a vertical building element causing it to ignite
  • Any surface including ground, deck, or roof can hold embers if < 18° slope & if > 110mm width

Vent & Weephole RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.4.3

Wall Construction RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.4.1

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • External Wall ≤ 400mm from Ground or DecksAS 3959:2018, 6.4.1
  • Wall must be fully sarked
  • ≥ 90mm thk Non-combustible materials
  • Masonry Wall
  • Precast Concrete Wall
  • Earth Wall (Mud Brick)
  • ≥ 90mm thk Timber logs (≥ 680kg/m³ density)
  • Cladding secured to the exterior of a timber or steel-framed wall.
  • Non-combustible material
  • ≥ 6mm Fibre-cement
  • Bushfire-resisting Timber
  • Approved Timber Species
  • Steel sheeting
  • Any combination of the options above

AS 3959:2018, 6.4.1 (a)

AS 3959:2018, 6.4.1 (c) (iii)

AS 3959:2018, 6.4.2

Detached Structure


  • > 6m separation[1], or
  • Same Fire-resisting construction[2], or
  • Main Building protected by[3]
  • ≥ –/60/60 FRL Non-loadbearing wall
  • ≥ 60/60/60 FRL Loadbearing wall
  • –/60/30 FRL Self-closing fire door
  • –/60/– FRL permanently closed Window


Detached Structure RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 3.2.3

AS 3959:2018, 3.2.3 (a)

AS 3959:2018, 3.2.3 (b)

AS 3959:2018, 3.2.3 (c)

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • The main building can be protected by having the detached structure with equivalent fire-resisting construction as the main building, orAS 3959:2018, 3.2.3
  • Separation from Main BuildingAS 3959:2018, 3.2.3 (a)
  • ≥ 6m horizontal distance, or
  • Fire Wall protecting main buildingAS 3959:2018, 3.2.3 (b)
  • ≥ 60/60/60 Loadbearing wall
  • ≥ -/60/60 Non-loadbearing wall
  • -/60/30 self-closing Fire Door
  • -/60/- permanently closed window & other openings
  • Masonry WallAS 3959:2018, 3.2.3 (c)
  • ≥ 90mm thk leaf
  • Masonry, masonry-veneer, or earth
  • Openings protected as above
  • Fire Doors & Windows to comply to AS 1905.1 & AS 1530.4

AS 3959:2018, 3.2.3 (a)

AS 3959:2018, 3.2.3

AS 3959:2018, 3.2.3 (b)

Vent & Weepholes


  • Use rust-proof screens for Vents[1]
  • Non-combustible access door[2]


Door RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.5.4 (c) (v)

AS 3959:2018, 6.5.4 (c) (vii)

AS 3959:2018, 6.5.4 (c) (i)

AS 3959:2018, 6.5.4 (c) (ii)

AS 3959:2018, 6.5.4 (c) (iv)

AS 3959:2018, 6.5.4 (a)

AS 3959:2018, 6.5.4 (b)

Vent & Weephole RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.4.3

AS 3959:2018, 6.4.3

AS 3959:2018, 6.5.4 (c) (i) (A)

Attached Structure


  • Same fire-resisting construction as Main Building[1] or
  • Main Building is protected by[2]
  • ≥ –/60/60 FRL Non-loadbearing wall
  • ≥ 60/60/60 FRL Loadbearing wall
  • –/60/30 FRL self-closing fire door
  • –/60/– FRL permanently closed Window


Attached Structure RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 3.2.1

AS 3959:2018, 3.2.2

AS 3959:2018, 3.2.1 (b)

AS 3959:2018, 3.2.1 (a)

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • The main building can be protected by having the attached structure with equivalent fire resisting construction as the main building, orAS 3959:2018, 3.2.1
  • Fire Wall required if structure is a garageAS 3959:2018, 3.2.2
  • Openings protected byAS 3959:2018, 3.2.1 (b)
  • ≥ 60/60/60 FRL Loadbearing wall
  • ≥ –/60/60 FRL Non-loadbearing wall
  • –/60/30 FRL Self-closing Fire Door
  • –/60/– FRL permanently closed window
  • Masonry WallAS 3959:2018, 3.2.1 (a)
  • ≥ 90mm thk leaf
  • Masonry, masonry-veneer, or earth
  • Openings protected as above
  • Fire Doors & Windows to comply to AS 1905.1 & AS 1530.4

AS 3959:2018, 3.2.1

AS 3959:2018, 3.2.1 (a)

  • Same fire-resisting construction as Main BuildingAS 3959:2018, 3.2.1 or
  • Main Building is protected byAS 3959:2018, 3.2.1 (a)
  • ≥ –/60/60 FRL Non-loadbearing wall
  • ≥ 60/60/60 FRL Loadbearing wall
  • –/60/30 FRL self-closing fire door
  • –/60/– FRL permanently closed Window

Verandah or Awning Roof


  • Relation to main roof[1]
  • If part of main roof space, requirements as per main roof
  • If separated, non-combustible cover


Tiled Roof RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.6.2

AS 3959:2018, 6.6.2

Ancillary Roofing RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.6.4

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • Carport, Overhead Awning, & Verandah RoofsAS 3959:2018, 6.6.4
  • If part of main roof, shall follow main roof requirements
  • If separated from main roof, a non-combustible cover shall be used & shall follow wall requirements

Post RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.7.5

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • Verandah Posts may be ofAS 3959:2018, 6.7.5
  • Timber installed on galvanised mounting shoes or stirrups
  • With a clearance ≥ 75mm above the surrounding ground level, or
  • If < 400mm above deck or ground level, must be of either
  • Non-combustible material, or
  • Bushfire-resisting timber, or
  • Allowed timber species

Metal Sheet Roof RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.6.3

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • Sheet RoofsAS 3959:2018, 6.6.3
  • Fully sarked over battens
  • Insulation blankets with foil backing can be placed above the battens
  • Seal gaps along fascia, ridges, hips, & wall lines by any of the following
  • Mesh or perforated screen
  • Mineral wool
  • Non-combustible material

AS 3959:2018, 6.6.4

  • Relation to main roofAS 3959:2018, 6.6.4
  • If part of main roof space, requirements as per main roof
  • If separated, non-combustible cover

Bushfire Shutter


  • Made of materials resistant to combustion[1]
  • Optional & removes window & door requirements[2][3]
  • ≤ 2mm aperture gaps, slots, or screen[4]


Bushfire Shutter RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.5.3

AS 3959:2018, 3.7

AS 3959:2018, 6.5.1

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • OptionalAS 3959:2018, 6.5.3
  • If not installed, window & door assemblies shall comply with corresponding BAL requirements
  • Bushfire ShutterAS 3959:2018, 3.7AS 3959:2018, 6.5.1
  • ≥ 1 to be openable from inside to allow escape
  • Must cover the entire window or door assembly
  • Able to be closed manually in case of power failure
  • ≤ 2mm gap to wall, frame, & sill
  • ≤ 20% perforated area, uniformly distributed, with ≤ 2mm apertures

Bushfire-resisting Timber BAL-19


NCC 2022 V4


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, F4

AS 3959:2018, E1

AS 3959:2018, 1.5.5

Screen RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 3.6.1

AS 3959:2018, 6.4.3

AS 3959:2018, 6.5.1 (a)

AS 3959:2018, 3.7

AS 3959:2018, 6.5.3

AS 3959:2018, 6.5.4

Services


  • Metal for Plumbing above ground[1]
  • Power lines to be buried[2]


Utility Service RULES


NCC 2022 V1


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

NSW RFS 2019 PBP, 5.3.3

AS 3959:2018, 6.8

AS/NZS 1596:2014, 4.4.12

NSW RFS 2019 PBP, 5.3.3

NSW RFS 2019 PBP, 5.3.3

AS 3959:2018, 6.8

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1NCC 2022 Vol 2, H7D4
  • Water Supply
  • Metal above-ground Water Pipes, Taps, Storage TankNSW RFS 2019 PBP, 5.3.3
  • Fire Hydrants prohibited on road carriagewayAS 3959:2018, 6.8
  • Gas Services
  • Steel or Copper above-ground Gas PipesAS/NZS 1596:2014, 4.4.12
  • ≥ 0.9mm wall thickness (Gas regulations may require thicker)
  • ≥ 400mm extension inside the building
  • ≥ 100mm underground extension
  • Refer to local Gas regulations for additional information
  • Bottled Gas InstallationNSW RFS 2019 PBP, 5.3.3NSW RFS 2019 PBP, 5.3.3
  • Shield or locate away from building
  • Away from flammable materials
  • Connections are made of metal
  • Polymer-sheathed flexible gas supply lines are prohibited
  • Electricity ServicesAS 3959:2018, 6.8
  • Power lines to be buried where applicable
  • Overhead lines
  • 30m Pole spacing
  • Refer to ISSC3 for Managing Vegetation Near Power Lines

AS 3959:2018, 6.8

NSW RFS 2019 PBP, 5.3.3

Garage Doors


  • Non-combustible materials[1]
  • ≤ 5 Flammability Index to seals[2]
  • Use screens to cover the ventilation slots[3]


Bushfire-resisting Timber BAL-19


NCC 2022 V4


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, F4

AS 3959:2018, E1

AS 3959:2018, 1.5.5

Garage Doors RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.5.6

AS 3959:2018, 6.5.6 (b)

AS 3959:2018, 6.5.6 (c)

AS 3959:2018, 6.5.6 (d)

Screen RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 3.6.1

AS 3959:2018, 6.4.3

AS 3959:2018, 6.5.6 (a) (i)

AS 3959:2018, 6.5.6 (c)

AS 3959:2018, 6.5.6 (d)

Guttering & Downpipes


  • Box Gutter non-combustible & fully flashed[1]
  • Turn sarking into Gutter[2]


Guttering RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]


May 2023



NCC 2022 Vol 1, G5D1

NCC 2022 Vol 2, H7D4

AS 3959:2018, 6.6.7

AS 3959:2018, 6.6.7

AS 3959:2018, 6.6