Roofing
Assembly[1] Non-combustible materials Fully sarked, junctions sealed Vents fitted with ember guards Eave & Fascia RULES NCC 2022 V2 All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
NSW RFS 2019 PBP, 7.5.2 AS 3959:2018, 7.6.6 (a) AS 3959:2018, 7.6.6 (b) (ii) AS 3959:2018, 7.6.6 (d) AS 3959:2018, 7.6.6 (e) AS 3959:2018, 7.6.6 (c) (i) NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 Metal Sheet Roofing RULES NCC 2022 V2 All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
AS 3959:2018, 7.6.3 (a) AS 3959:2018, 7.6.3 (b) NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 Guttering RULES NCC 2022 V3 All Building Classes
NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]
May 2023
NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, 7.6.7 Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 GutteringAS 3959:2018, 7.6.7 Install non-combustible valley leaf guards & Gutter Use metal or uPVC Gutters Except for Box Gutters Box Gutters to be non-combustible & fully flashed Roofing RULES NCC 2022 V2 All Building Classes
NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]
May 2023
AS 3959:2018, 7.6.1 (a) AS 3959:2018, 7.6.1 (b) AS 3959:2018, 7.6.1 (e) NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, 7.6.1 (c) AS 3959:2018, 7.6.1 (d) Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to the NCCAS 3959:2018, 7.6.1 (a) AS 3959:2018, 7.6.1 (b) Constructed with non-combustible materialsAS 3959:2018, 7.6.1 (e) Roof/Roof & Roof/Wall junctions sealed, orNCC 2022 Vol 1, G5D1 Reinforced with permeable sarking or mesh Fit non-combustible ember guards or screens on Roof Ventilation OpeningsNCC 2022 Vol 2, H7D4 Any pipe or conduit extending through the roof covering, to be non-combustibleAS 3959:2018, 7.6.1 (c) Evaporative Coolers to be AS/NZS 60335.2.98 complaintAS 3959:2018, 7.6.1 (d) Coolers with internal ember dampers, do not require external screens Skylight RULES NCC 2022 V2 All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
AS 3959:2018, 7.6.5 (c) AS 3959:2018, 7.6.5 (d) AS 3959:2018, 7.6.5 (d) AS 3959:2018, 7.6.5 (e) AS 3959:2018, 7.6.5 (g) AS 3959:2018, 7.6.5 (g) NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 Building elements within Bushfire-Prone Areas to be Bushfire Attack Resistant to the NCCAS 3959:2018, 7.6.5 (c) AS 3959:2018, 7.6.5 (d) Sealed & completely flashed with non-combustible material Grade A Safety Glass to AS 1288 AS 3959:2018, 7.6.5 (d) ≤ 18° horizontally, Single pane Glass, Ember Guards requiredAS 3959:2018, 7.6.5 (e) ≥ 2mm aperture & corrosion-resistant material of Ember Guards, if installedAS 3959:2018, 7.6.5 (g) Polymer Skylight allowed withAS 3959:2018, 7.6.5 (g) Grade A Safety Glass Diffuser belowIGUsNCC 2022 Vol 1, G5D1 ≥ 4mm thk Grade A Safety Glass Outer PanelTubular SkylightsNCC 2022 Vol 2, H7D4 Can be fire-retardant Under-flashing ≤ 5 Flammability IndexScreen RULES NCC 2022 V2 All Building Classes
NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]
May 2023
NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, 3.6.1 Tiled Roof RULES NCC 2022 V1 All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
AS 3959:2018, 7.6.2 (a) AS 3959:2018, 7.6.2 AS 3959:2018, 7.6.2 (b) AS 3959:2018, 7.6.2 (b) NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 Penetration RULES NCC 2022 V3 All Building Classes
NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]
May 2023
AS 3959:2018, 7.6.5 (a) AS 3959:2018, 7.6.5 (b) AS 3959:2018, 7.6.5 (f) NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, 7.6.1 AssemblyAS 3959:2018, 7.6.1 Non-combustible materials Fully sarked, junctions sealed Vents fitted with ember guards Vent & Weepholes
Vents screened[1] Non-combustible access door[2] Door RULES NCC 2022 V3 All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
AS 3959:2018, 7.5.4 (a) AS 3959:2018, 7.5.4 (b) AS 3959:2018, 7.5.4 (c) (i) (A) AS 3959:2018, 7.5.4 (c) (i) (B) AS 3959:2018, 7.5.4 (c) (i) (C) AS 3959:2018, 7.5.4 (c) (ii) AS 3959:2018, 7.5.4 (c) (v) AS 3959:2018, 7.5.4 (c) (iv) AS 3959:2018, 7.5.4 (c) (vi) AS 3959:2018, 7.5.4 (c) (vii) NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 Building elements within Bushfire-Prone Areas to be Bushfire Attack Resistant to the NCCAS 3959:2018, 7.5.4 (a) AS 3959:2018, 7.5.4 (b) Door Leaf Non-combustibleAS 3959:2018, 7.5.4 (c) (i) (A) Solid, laminated or reconstituted TimberAS 3959:2018, 7.5.4 (c) (i) (B) ≥ 35mm thk400mm above thresholdFully framed glazed panels withAS 3959:2018, 7.5.4 (c) (i) (C) Metal Bushfire-resistanting Timber Approved Timber species uPVC framing FramesAS 3959:2018, 7.5.4 (c) (ii) Metal, Bushfire-resisting Timber, Timber species, or Metal-reinforced uPVC Aluminum, Stainless Steel, or corrosion-resistant Steel as reinforcement Tight fitting to Door frame & abutting DoorAS 3959:2018, 7.5.4 (c) (v) Seals & Weather Strips all roundAS 3959:2018, 7.5.4 (c) (iv) GlazingAS 3959:2018, 7.5.4 (c) (vi) ≥ 6mm Toughened Grade A Safety Glass No requirements on door if Protected by a Bushfire ShutterAS 3959:2018, 7.5.4 (c) (vii) NCC 2022 Vol 1, G5D1 Protected by ScreensNCC 2022 Vol 2, H7D4 Screen RULES NCC 2022 V3 All Building Classes
NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]
May 2023
NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, 3.6.1 AS 3959:2018, 6.4.3 AS 3959:2018, 7.4.3 AS 3959:2018, 7.5.4 (c) (i) (A) Sarking
Where required[1] ≤ 5 flammability indexWalls & roof to be fully-sarked Sarking RULES NCC 2022 V3 All Building Classes
NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]
May 2023
NSW RFS 2019 PBP, 7.5.2 NSW RFS 2019 PBP, 7.5.2 AS 3959:2018, 3.10 NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, 3.10 AS 3959:2018, 3.6.1 Eaves & Fascias
Roof Components[1] Gables shall follow same rules as per Fire Wall Eaves penetrations screened Joints sealed Eave & Fascia RULES NCC 2022 V2 All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
NSW RFS 2019 PBP, 7.5.2 AS 3959:2018, 7.6.6 (a) AS 3959:2018, 7.6.6 (b) (ii) AS 3959:2018, 7.6.6 (d) AS 3959:2018, 7.6.6 (e) AS 3959:2018, 7.6.6 (c) (i) NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 Bushfire Resisting Timber BAL-29 NCC 2022 V3 All Building Classes
NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]
May 2023
NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, F4 AS 3959:2018, E1 AS 3959:2018, 1.5.5 AS 3959:2018, 7.1 Screen RULES NCC 2022 V2 All Building Classes
NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]
May 2023
NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, 3.6.1 AS 3959:2018, 7.6.6 Roof ComponentsAS 3959:2018, 7.6.6 Gables shall follow same rules as per Fire Wall Eaves penetrations screened Joints sealed Windows & Glazed Doors
Frame to be, metal, bushfire resisting timber, or metal reinforced uPVC[1] ≥ 5mm Grade A Toughened Glazing[2] Openable Screens[3] Bushfire Resisting Timber BAL-29 NCC 2022 V3 All Building Classes
NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]
May 2023
NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, F4 AS 3959:2018, E1 AS 3959:2018, 1.5.5 AS 3959:2018, 7.1 Window RULES NCC 2022 V3 All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
AS 3959:2018, 7.5.3 (a) AS 3959:2018, 7.5.3 (b) (i) AS 3959:2018, 7.5.3 (b) (v) AS 3959:2018, 7.5.3 (b) (ii) AS 3959:2018, 7.5.3 (b) (iii) AS 3959:2018, 7.5.3 (b) (v) NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 Building elements within Bushfire-Prone Areas to be Bushfire Attack Resistant to the NCCAS 3959:2018, 7.5.3 (a) AS 3959:2018, 7.5.3 (b) (i) Glazing ≥ 5mm thk Toughened Glass (outer pane only if double glazed) AS 3959:2018, 7.5.3 (b) (v) if ≤ 400mm from ground, above Deck, or Ember Holding Surface must be screenedAS 3959:2018, 7.5.3 (b) (ii) FramesAS 3959:2018, 7.5.3 (b) (iii) Metal, Bushfire-resisting Timber, or uPVC reinforced with Aluminum, Stainless Steel or corrosion-resistant Steel ScreensAS 3959:2018, 7.5.3 (b) (v) ≤ 2mm aperture or openingInternal or external open sections of Windows Fixed & opening sections for Windows External hardware to be MetalNCC 2022 Vol 1, G5D1 No requirements if protected by a BAL-29 Bushfire ShutterNCC 2022 Vol 2, H7D4 Ember holding surface NCC 2022 V2 Embers can blow & accumulate against a vertical building element causing it to ignite Any surface including Ground, Deck or Roof can hold embers if < 18° slope> 110mm widthAS 3959:2018, 7.5.3 (b) (iii) AS 3959:2018, 7.5.4 (c) (ii) AS 3959:2018, 7.5.3 (b) (v) Verandah or Awning Roof
Relation to main roof[1] If part of main roof space, requirements as per main roof If separated, non-combustible cover ≥ 6mm fibre-cement lining for combustible elementsMetal Sheet Roofing RULES NCC 2022 V2 All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
AS 3959:2018, 7.6.3 (a) AS 3959:2018, 7.6.3 (b) NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 Tiled Roof RULES NCC 2022 V1 All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
AS 3959:2018, 7.6.2 (a) AS 3959:2018, 7.6.2 AS 3959:2018, 7.6.2 (b) AS 3959:2018, 7.6.2 (b) NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 External Roofing RULES NCC 2022 V3 All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
AS 3959:2018, 7.6.4 (a) AS 3959:2018, 7.6.4 AS 3959:2018, 7.6.4 (b) (i) AS 3959:2018, 7.6.4 (b) (ii) AS 3959:2018, 7.6.4 (b) (iii) NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, 7.6.4 Relation to main roofAS 3959:2018, 7.6.4 If part of main roof space, requirements as per main roof If separated, non-combustible cover ≥ 6mm fibre-cement lining for combustible elementsDecks & Landing
Fully enclosing a subfloor will provide protection [1] [2] Non-combustible material[3] Bushfire Resisting Timber BAL-29 NCC 2022 V3 All Building Classes
NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]
May 2023
NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, F4 AS 3959:2018, E1 AS 3959:2018, 1.5.5 AS 3959:2018, 7.1 Decks and Landing RULES NCC 2022 V2 All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
AS 3959:2018, 7.7.2 NSW RFS 2019 PBP, 7.5.2 NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, 7.7.1 NSW Enhanced RULES AS 3959:2018, 7.7.1
Decks, Landings & Stairs must be constructed to BAL-29 requirements All elements must be Non-combustible material, or Bushfire-resisting Timber NSW RFS 2019 PBP, 7.4 AS 3959:2018, 7.7.2.4 (a) AS 3959:2018, 7.7.2 Attached Structure
Same fire resisting construction, or[1] Main building protected by[2] -/60/60 FRL wall-/60/30 FRL self-closing fire door-/60/- FRL permanently closed windowAttached Structure RULES NCC 2022 V1 All Building Classes
NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]
May 2023
NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, 3.2.1 (a) AS 3959:2018, 3.2.1 AS 3959:2018, 3.2.2 AS 3959:2018, 3.2.1 AS 3959:2018, 3.2.1 (a) Detached Structure
> 6m separation, or[1] Same fire resisting construction, or[2] Main building protected by[3] -/60/60 FRL Fire Wall -/60/30 FRL self-closing fire door -/60/60 FRL permanently closed window Detached Structure RULES NCC 2022 V2 All Building Classes
NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]
May 2023
NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, 3.2.3 (b) AS 3959:2018, 3.2.3 AS 3959:2018, 3.2.3 (a) AS 3959:2018, 3.2.3 (a) AS 3959:2018, 3.2.3 AS 3959:2018, 3.2.3 (b) Garage Doors
Non-combustible materials[1] ≤ 5 Flammability Index to seals[2] Ventilation slots if any, screened [3] Screen RULES NCC 2022 V2 All Building Classes
NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]
May 2023
NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, 3.6.1 Garage Door RULES NCC 2022 V3 All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
AS 3959:2018, 7.5.6 (a) (i) AS 3959:2018, 7.5.6 (a) (ii) AS 3959:2018, 7.5.6 (a) (iii) AS 3959:2018, 7.5.6 (b) AS 3959:2018, 7.5.6 (c) AS 3959:2018, 7.5.6 (e) NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 Building elements within Bushfire-Prone Areas to be Bushfire Attack Resistant to the NCCAS 3959:2018, 7.5.6 (a) (i) AS 3959:2018, 7.5.6 (a) (ii) Materials to be Non-combustibleAS 3959:2018, 7.5.6 (a) (iii) , or Bushfire-resting TimberAS 3959:2018, 7.5.6 (b) , or ≥ 6mm Fibre-cement SheetAS 3959:2018, 7.5.6 (c) Fitted with Guide Tracks, Weather Strips, Seals & BrushesAS 3959:2018, 7.5.6 (e) ≤ 5 F lammability IndexNCC 2022 Vol 1, G5D1 Ventilation protected by screensNCC 2022 Vol 2, H7D4 AS 3959:2018, 7.5.6 (a) (i) AS 3959:2018, 7.5.6 (c) AS 3959:2018, 7.5.6 (e) Bushfire Shutter
Non-combustible materials[1] Optional & removes window & door requirements[2] ≤ 2mm aperture gaps, slots, or screen[3] Bushfire Resisting Timber BAL-29 NCC 2022 V3 All Building Classes
NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]
May 2023
NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, F4 AS 3959:2018, E1 AS 3959:2018, 1.5.5 AS 3959:2018, 7.1 Screen RULES NCC 2022 V2 All Building Classes
NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]
May 2023
NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, 3.6.1 Bushfire Shutter MATERIALS NCC 2022 V2 All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
AS 3959:2018, 7.5.1 (a) AS 3959:2018, 7.5.1 (b) NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 Bushfire Shutter RULES NCC 2022 V3 All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
AS 3959:2018, 3.7 (d) AS 3959:2018, 3.7 (e) AS 3959:2018, 3.7 (f) AS 3959:2018, 3.7 (g) AS 3959:2018, 3.7 (g) AS 3959:2018, 3.7 AS 3959:2018, 3.7 (a) AS 3959:2018, 3.7 (b) NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 Building elements within Bushfire-Prone Areas to be Bushfire Attack Resistant to the NCCAS 3959:2018, 3.7 (d) AS 3959:2018, 3.7 (e) Protect Window & Door assemblyAS 3959:2018, 3.7 (f) AS 3959:2018, 3.7 (g) Non-removable & securely attached to the buildingAS 3959:2018, 3.7 (g) Able to be closed manually in case of power failureAS 3959:2018, 3.7 Gaps & Perforations ≤ 2mm gap to Wall, Frame, or SillAS 3959:2018, 3.7 (a) ≤ 20% perforated areaAS 3959:2018, 3.7 (b) ≤ 2mm aperture size openings, evenly distributedNCC 2022 Vol 1, G5D1 Safe Exit / EgressNCC 2022 Vol 2, H7D4 ≥ 1 to be openable from inside to allow escapeAS 3959:2018, 7.5.1 (a) AS 3959:2018, 3.6 AS 3959:2018, 7.5.3 Walls
Non-combustible material, or [1] Bushfire-resistant timber [2] Fully-sarked[3] Joints sealed or covered [4] Bushfire Resisting Timber BAL-29 NCC 2022 V3 All Building Classes
NCC 2022 G5D1 & H7D4 [2019 G5.0, 3.10.5]
May 2023
NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, F4 AS 3959:2018, E1 AS 3959:2018, 1.5.5 AS 3959:2018, 7.1 Wall Construction RULES NCC 2022 V4 All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, 7.4.1 Building elements within Bushfire-Prone Areas to be Bushfire Attack Resistant to the NCCNCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 External WallAS 3959:2018, 7.4.1 Wall must be fully sarked Composed of any of the following Non-combustible masonry or masonry veneer wall ≥ 90mm thk timber logs with ≥ 680 kg/m³ density at 12% moisture content Leaf of clay, blockwork, stone, concrete (incl aerated), or earth ≥ 6mm fibre-cementBushfire resisting timber Steel sheet Vents & Weepholes NCC 2022 V3 All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, 7.4.3 Of aluminium , bronze, or corrosion-resistant steel
Jointing RULES NCC 2022 V1 All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
NCC 2022 Vol 1, G5D1 NCC 2022 Vol 2, H7D4 AS 3959:2018, 7.4.2 AS 3959:2018, 7.4.1 (a) AS 3959:2018, 7.4.1 (c) (iii) AS 3959:2018, 7.4.3 AS 3959:2018, 3.10 Fire-stopping Penetrations