Metal Cladding Building Codes & Rules


- Metal cladding requires precision. Learn how to manage drainage, fixings, and material compatibility to prevent costly mistakes and ensure long-term durability.


AS 4200.2:2017, 3.7.1 (a) (i)

≥ 150AS 4200.2:2017, 3.7.1 (a) (i)

Industry Recommendation

10Industry Recommendation

Industry Recommendation

100Industry Recommendation

AS 1562.1:2018, 4.4

FixingsAS 1562.1:2018, 4.4

  • Only use fixings that are recommended in the system design
  • Place fixings in the middle of supports
  • If hook bolts, near the top edge
  • If assembly includes washers, must be
  • Compatible with sheeting
  • Able to withstand wind loads
  • Ensure sheets won't be deformed when piercing holes for fasteners
  • Manufacturer tools may be provided for safe hole punching

Insulation

Open Horizontal Profile Cladding

Manufacturer's Requirement

Metal Cladding Location in Various EnvironmentsManufacturer's Requirement

  • Install 100 to 200m away from
  • Breaking waves, to prevent exposure to corrosive salt spray
  • Sources of industrial emissions, where air quality is generally improved

Internal Corner Flashing

Ground Flashing

Fully

Sarked

Manufacturer's Recommendation

Spacing to follow

Cladding RequirementManufacturer's Recommendation

Head

Flashing

Cavity

Closer

Framing Overview (Light Steel)

External Corner Flashing

Sill

Flashing

Jamb

Flashing

Metal Stud

Batten

Batten

Industry Recommendation

110Industry Recommendation

NCC 2022 Vol 2, H1D7 (5)

AS 1562.1:2018, 4.8

Flashings

Manufacturer's Requirement

Top Plate Moisture BarrierManufacturer's Requirement

  • Separates dissimilar Roof / Wall framing materials (eg when installing a Timber Roof Frame onto Light Steel Frame Walls
  • Not required for Metal Wall to Metal Roof Frames

Finished Ground


  • ≥ 100mm to well-drained areas[1]
  • ≥ 50mm to impermeable areas[2]
  • ≥ 150mm to any other areas[3]
  • ≥ 50mm extension below the bearer[4]


Cladding to Ground CLEARANCE


NCC 2022 V2


All Building Classes


NCC 2022 7.5.7 [2019 3.5.4.7]


May 2023



NCC 2022 HP, 7.5.7 (1)

NCC 2022 HP, 7.5.7 (2)

  • ClearanceNCC 2022 HP, 7.5.7 (1)
  • ≥ 100mm in well-drained areas
  • Low rainfall intensity areas or sandy
  • ≥ 50mm above impermeable areas that slope away from the building
  • ≥ 150mm in any other case
  • ExtensionNCC 2022 HP, 7.5.7 (2)
  • ≥ 50mm wall cladding extension below the bearer or lowest horizontal part of the suspended floor framing

NCC 2022 HP, 7.5.7 (1) (a)

NCC 2022 HP, 7.5.7 (1) (b)

NCC 2022 HP, 7.5.7 (1) (c)

NCC 2022 HP, 7.5.7 (2)

Framing Overview (Timber)

Industry Recommendation

Insulating Metal Pipes in Cold ClimateIndustry Recommendation

  • Reduces heat loss
  • to 4°F increase in water temperature, as compared to uninsulated pipes
  • Allows for lower temperature setting
  • Mitigates risk of frozen pipes
  • Some options may be to utilize
  • Pipe sleeve
  • Heat tape
  • Heat cable

NCC 2022 HP, 10.8.1

Warm Weather Vapour Barrier on External WallsNCC 2022 HP, 10.8.1

  • ≥ 0.143 µg/N.s vapour permeance in Climate Zones 4 & 5
  • To comply with AS 4200.1 & AS 4200.2

Under-Sill

Flashing

Manufacturer's Requirement

Bottom Plate Moisture BarrierManufacturer's Requirement

  • Install an impermeable membrane beneath perimeter bottom plates which are fixed on concrete slabs
  • Extend to weatherside flange
  • Pre-made adhesive membranes
  • Preferred way of protection
  • ≥ 10mm extension on both sides of bottom plate
  • For other types of membranes
  • Compliant to AS 2870 or AS/NZS 2904, or
  • CodeMark Certified

Manufacturer's Recommendation

Open Profile Metal CladdingManufacturer's Recommendation

  • Has open ribs or gaps that let air pass through
  • Corrugated & trapezoidal profiles
  • Vertical
  • Attach directly to wall frame
  • Allows air to flow & water to drain
  • Horizontal
  • Install on vertical battens to allow ventilation & drainage behind the cladding
  • Provide insulation between cladding & steel frame to reduce heat transfer

Closed Vertical Profile Cladding

Manufacturer's Recommendation

Closed Profile Metal Cladding Manufacturer's Recommendation

  • Has limited airflow underneath
  • Standing Seam profile
  • Horizontal & Vertical
  • Install battens for airflow & drainage
  • For vertical cladding, install packers to keep assembly secure & dry

Open Horizontal Profile Cladding

Open Vertical Profile Cladding

NCC 2022 HP, 10.8.1

Cold Weather Vapour Barrier on External WallsNCC 2022 HP, 10.8.1

  • ≥ 1.14 µg/N.s vapour permeance in Climate Zones 6, 7 & 8
  • To Comply with AS 4200.1 & AS 4200.2

Closed Horizontal

Profile Cladding

Sarking

Batten Packing

Overlap

Thermal Breaks


  • R ≥ 0.2 for thermal breaks to prevent thermal bridging[1]
  • Install insulating strips between metal frames & cladding[2]


Metal-framed Wall Thermal Break Requirement RULES


NCC 2022 V1


Class 1 & 10a


NCC 2022 HP Part 13.2.5 [2019: 3.12.1.4]


May 2023



NCC 2022 HP, 13.2.5 (5)

NCC 2022 HP, 13.2.5 (5) (a)

NCC 2022 HP, 13.2.5 (5) (b)

NCC 2022 HP, 13.2.5 (5) (b)

NCC 2022 HP, 13.2.5 (5)

NCC 2022 HP, 13.2.5 (6)

Metal-Framed Wall Thermal Bridging Methods


NCC 2022 V3


Class 1 & 10a


NCC 2022 Part 13.2.5 [2019: 3.12.1.4]


May 2023



NCC 2022 HP, 13.2.5 (4) (b)

NCC 2022 HP, 13.2.5 (4)

  • Thermal Bridging in a Metal-framed wall to be achieved according to type of constructionNCC 2022 HP, 13.2.5 (4) (b)
  • Concrete Block Walls with Internal Lining
  • Lightweight Construction
  • Masonry Veneer, or
  • Choose one of the pre-defined solutions for External Wall for Thermal Bridging MitigationNCC 2022 HP, 13.2.5 (4)

NCC 2022 HP, 13.2.5 (5)