Wall (Plasterboard) Building Codes & Rules


- Optimise your Plasterboard Walls with Tools™. Ensure NCC compliance for framing centres, fasteners, adhesive, and butt joints.


Butt Joint


  • Try to avoid Butt Joints by using full length Plasterboard sheets
  • Joints on studs are not acceptable for exposed single skin walls


Butt Joint BEST PRACTICE


NCC 2022 V1


Butt Joint FINISHES


NCC 2022 V2


  • Try to avoid Butt Joints by using full length Plasterboard sheets
  • Joints on studs are not acceptable for exposed single skin walls

≥ 200

Nogging

≥ 6

≥ 5

Equal

Butt Joint

Temporary Batten

Nail Packer

Back Blocking

≥ 10

Temporary Offcuts

for alignment and spacing from floor

≥ 10

≤ 300

≥ 200

Adhesive

Equal Spacing

Along Vertical Side

Equal Spacing

Along Vertical Side

One Fixing at Each Stud Along Horizontal Side

Clearance

From floor level

Temporary

Fastener

every 2nd Stud

Temporary

Fastener

every 2nd Stud

Sealant

Temporary

Fastener

every 2nd Stud

Acoustic Sealant

Fasteners


  • ≥ 10mm from sheet edges
  • On every Stud to Manufacturer's recommendations


Fixings SPACING


NCC 2022 V3


Fasteners & Adhesive

  • Adhesive daubs should be applied only on the sheet field along the studs
  • ≥ 200mm from plasterboard fixing point & edges
  • ≤ 300mm centres
  • Temporary fastener left in place for 24h for better adhesion of plasterboard on studs
  • Fasteners should be placed along sheet perimeter at
  • ≥ 10mm from sheet edges
  • Along vertical sheet edges with equal spacing depending on manufacturer recommendations
  • Along horizontal sheet edges on each stud

Screws or Nails Only

  • ≥ 10mm from sheet edge
  • Along vertical sheet edges with equal spacing depending on manufacturer recommendations
  • Along horizontal sheet edges on each stud
  • ≥ 10mm from sheet edges
  • On every Stud to Manufacturer's recommendations

Adhesive


  • ≤ 300mm centres
  • ≥ 200mm from Fasteners


Fixings SPACING


NCC 2022 V3


Fasteners & Adhesive

  • Adhesive daubs should be applied only on the sheet field along the studs
  • ≥ 200mm from plasterboard fixing point & edges
  • ≤ 300mm centres
  • Temporary fastener left in place for 24h for better adhesion of plasterboard on studs
  • Fasteners should be placed along sheet perimeter at
  • ≥ 10mm from sheet edges
  • Along vertical sheet edges with equal spacing depending on manufacturer recommendations
  • Along horizontal sheet edges on each stud

Screws or Nails Only

  • ≥ 10mm from sheet edge
  • Along vertical sheet edges with equal spacing depending on manufacturer recommendations
  • Along horizontal sheet edges on each stud
  • ≤ 300mm centres
  • ≥ 200mm from Fasteners

Plasterboard Ceiling

Partition Types


null


Partiton TYPES


NCC 2022 V3


null

Framing Centres


  • Dependent on wind category


Framing RULES


NCC 2022 V3


  • Dependent on wind category

≥ 10

≥ 10

Equal

Wall Lining Installation

≤ 300

≤ 300

Plasterboard Stud Wall FRL