Atrium (Compartmentation and Separation) Building Codes & Rules


- Atrium : Tools™ simplifies the National Construction Code (NCC) with interactive graphics, including deemed to comply & best practices.


NCC 2022 Vol 1, G3D2

≥ Ø 6mNCC 2022 Vol 1, G3D2

NCC 2022 Vol 1, Glossary

Definition of an AtriumNCC 2022 Vol 1, Glossary

  • ≥ 2 storeys connected within a clear building space with
  • > 50% enclosure by a Roof or Floor above of the area of any Storey within
  • Includes any adjacent non-fire separated areas
  • Excludes shafts, stairwells, or ramp wells

NCC 2022 Vol 1, G3D3

≤ 3.5mNCC 2022 Vol 1, G3D3

NCC 2022 Vol 1, G3D5

≥ 1mNCC 2022 Vol 1, G3D5

NCC 2022 Vol 1, G3D2

Atrium WellNCC 2022 Vol 1, G3D2

  • ≥ 6m Ø Clear Cylinder width throughout the Well

Open space or Road

NCC 2022 Vol 1, G3D5

BalconyNCC 2022 Vol 1, G3D5

  • Non-combustible
  • Solid construction

NCC 2022 Vol 1, S31C7

NCC 2022 Vol 1, S31C15

NCC 2022 Vol 1, S31C19 (a)

NCC 2022 Vol 1, G3D8

Fire and Smoke Protection

NCC 2022 Vol 1, G3D7

Atrium EgressNCC 2022 Vol 1, G3D7

  • ≥ 2 Exits per area

Storey 1

Storey 2

Storey 3

Storey 4

Storey 5

NCC 2022 Vol 1, G3D3

Atrium SeparationNCC 2022 Vol 1, G3D3

  • ≤ 3 Storeys (consecutive) allowed to have Bounding Wall setback > 3.5m if one of those Storeys has direct access to Open Space or Road

NCC 2022 Vol 1, G3D3

> 3.5mNCC 2022 Vol 1, G3D3

NCC 2022 Vol 1, S31C4

Atrium FloorNCC 2022 Vol 1, S31C4

  • Protected by quick response sidewall & overhead sprinklers as required to provide full coverage

Area & Volume Measurement


  • Area = all Floors measured from the internal finished face of the Bounding Construction or any external walls[1]
  • Storeys with Balcony Width ≤ 3.5m to Bounding Wall excluded[2]
  • Volume = total space measured from the internal finished face of the Bounding Construction or any external walls[3]
  • Excludes the space within an Atrium Well above the Atrium Floor[4]


Compartmentation Area & Volume RULES


NCC 2022 V1


Class 2 to 9


NCC 2022, G3D3 & C3D3


May 2023



NCC 2022 Vol 1, C3D4

NCC 2022 Vol 1, C3D6

NCC 2022 Vol 1, C3D3

NCC 2022 Vol 1, Glossary

NCC 2022 Vol 1, Glossary

NCC 2022 Vol 1, G3D3

NCC 2022 Vol 1, C3D3 (3)

Atrium Cover


  • Roof or Floor of Storey Above
  • FRL as per table, or
  • Sprinklered[1]


Atrium Fire Sprinkler RULES


NCC 2022 V1


Class 2 to 9


NCC 2022, S31C3, S31C4


May 2023



NCC 2022 Vol 1, S31C4

NCC 2022 Vol 1, S31C3 (2)

NCC 2022 Vol 1, S31C3 (1)

NCC 2022 Vol 1, S31C3 (1)

  • Roof protected by Sprinklers if not FRL protected, butNCC 2022 Vol 1, S31C4
  • Exempt from being Sprinklered if distance above the Atrium Floor or any Storey with > 3.5m Bounding Wall setback isNCC 2022 Vol 1, S31C3 (2)
  • < 12m in Class 2, 3, 5 or 9 part of a building
  • < 20m in Class 6, 7 or 8 part of a building
  • 79 to 100°C temperature rated Roof SprinklersNCC 2022 Vol 1, S31C3 (1)
  • Floor of Atrium protected by quick response sidewall & overhead sprinklers as required to provide full coverageNCC 2022 Vol 1, S31C3 (1)

Atrium Roof FRL RULES


NCC 2022 V1


Class 2 to 9


NCC 2022, G3D6


May 2023



NCC 2022 Vol 1, G3D6 (a)

NCC 2022 Vol 1, G3D6 (b)

NCC 2022 Vol 1, S31C3 (1)

NCC 2022 Vol 1, G3D4 (a)

NCC 2022 Vol 1, G3D4 (a) (ii)

NCC 2022 Vol 1, G3D4 (b)

Bounding Walls

  • 60/60/60 FRL WallNCC 2022 Vol 1, G3D4 (a)
  • Unless higher requirement due to Type of Construction
  • From Floor to underside of Roof or Floor above
  • -/60/30 FRL Automatic or Self-closing Fire DoorsNCC 2022 Vol 1, G3D4 (a) (ii)
  • Fixed Safety Glass or Wired Safety GlassNCC 2022 Vol 1, G3D4 (b)
  • Automatic or Self-closing Smoke Doors
  • ≥ -/60/30 FRL Wall in ceiling space
  • Wall Wetting Sprinklers to NCC 2022 Specification 31

Type A Construction

Compartmentation & Separation