Roof Construction BAL-29 Building Codes & Rules


- Comply with Bushfire Construction Requirements with Tools™: BAL-29 requirements, fire danger insights, & detailed guidance for walls, roof, guttering & more!


Roofing Durability

Eaves Penetrations


  • Equipped with Ember Guard, protection Screens & comprehensively Sealed[1][2][3]


Eaves Penetrations RULES


NCC 2022 V1


All Building Classes


NCC 2022 H7D4 [2019 3.10.5]


May 2023



AS 3959:2018, 3.10

AS 3959:2018, 7.6.6 (d)

AS 3959:2018, 7.6.6 (e)

AS 3959:2018, 7.6.6 (f)

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to NCC Specification 1, NCC Part G5, & AS 3959
  • Seal Roof penetrations with non-combustible materialAS 3959:2018, 3.10
  • Equipped with Ember Guard, protection Screens & comprehensively SealedAS 3959:2018, 7.6.6 (d)
  • Joints to be comprehensively sealedAS 3959:2018, 7.6.6 (e)
  • Corrosion-resistant Steel or Bronze Perforated Sheet or Mesh withAS 3959:2018, 7.6.6 (f)
  • ≤ 2mm aperture size or opening

AS 3959:2018, 7.6.6 (d)

AS 3959:2018, 7.6.6 (e)

AS 3959:2018, 7.6.6 (f)

Eaves


  • Bushfire-resisting Timber, or[1]
  • ≥ 4.5mm thk Fibre-cement[2]


Bushfire Resisting Timber BAL-29


NCC 2022 V2


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, F4

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to NCC Specification 1, NCC Part G5, & AS 3959
  • Bushfire-resisting Timber to AS 3959
  • Timber species per AS 3959
  • Any solid, laminated, treated, or reconstituted Timber meeting BAL-29 complianceAS 3959:2018, F4

Eaves Lining RULES


NCC 2022 V1


All Building Classes


NCC 2022 H7D4 [2019 3.10.5]


May 2023



AS 3959:2018, 7.6.6 (c) (i)

AS 3959:2018, 7.6.6 (c) (ii)

AS 3959:2018, 7.6.6 (f)

AS 3959:2018, 7.6.6 (c) (ii)

AS 3959:2018, 7.6.6 (c) (i)

Sarking


  • Roofs need a full layer of Sarking[1][2]
  • Turned up into Gutters & Valleys[3]
  • Continuous over Ridge[4]


Sarking RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 3.6.1

NSW RFS 2019 PBP, 7.5.2

NSW RFS 2019 PBP, 7.5.2

AS 3959:2018, 3.10

AS 3959:2018, 7.6.2

AS 3959:2018, 7.6.3 (a)

AS 3959:2018, 7.6.2 (c)

AS 3959:2018, 7.6.2 (b)

Sarking

Fascia

Joint Strip

Sarking

Battens

Eaves Lights

Fully Sealed

BAL-29 Certified

Roof Ventilator

Fixings on every corrugation

Turn Sarking into Gutter

Fire Resistant Foam Filler Strips

  • Provides additional weather & ember protection

Eaves Vent

Fixings on every 2nd corrugation

Fire Resistant Foam Filler Strips

  • Provides additional weather & ember protection

Walls & Floors



Fascias


  • Bushfire-resisting Timber, or[1]
  • 450mm CTS if constructed with Metal[2]


Fascias & Bargeboards RULES


NCC 2022 V1


All Building Classes


NCC 2022 H7D4 [2019 3.10.5]


May 2023



AS 3959:2018, 7.6.6 (b) (ii)

AS 3959:2018, 7.6.6 (b) (i)

Bushfire Resisting Timber BAL-29


NCC 2022 V2


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, F4

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to NCC Specification 1, NCC Part G5, & AS 3959
  • Bushfire-resisting Timber to AS 3959
  • Timber species per AS 3959
  • Any solid, laminated, treated, or reconstituted Timber meeting BAL-29 complianceAS 3959:2018, F4

AS 3959:2018, 7.6.6 (b) (i)

AS 3959:2018, 7.6.6 (b) (ii)

AS 3959:2018, 3.10

Flammability Index ≤ 5AS 3959:2018, 3.10

Roof Framing

Ridge Capping

Mineral Wool Insulation

Fully Sarked

Storm Moulds

Eaves Lining

Gutter


  • Non-combustible[1]
  • Sealed with Flashing[2]


Guttering RULES


NCC 2022 V4


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 7.6.7

AS 3959:2018, 6.6.2

AS 3959:2018, 6.6.7

AS 3959:2018, 7.6.7

AS 3959:2018, 7.6.7

AS 3959:2018, 7.6.7

Exhaust

  • Cooking & Bathroom exhausts to Duct externally through Wall or Eaves to minimise condensation

Roof Penetrations


  • Sealed with non-combustible materials[1]
  • Openings screened[2]


Penetration RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 7.6.5 (a)

AS 3959:2018, 7.6.5 (b)

AS 3959:2018, 7.6.5 (f)

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to NCC Specification 1, NCC Part G5, & AS 3959
  • Sealed with non-combustible materialAS 3959:2018, 7.6.5 (a)
  • Openings screenedAS 3959:2018, 7.6.5 (b) 
  • Evaporative CoolersAS 3959:2018, 7.6.5 (f)
  • Non-combustible Butterfly Closers near the Roof or
  • Covers with corrosion-resistant Mesh or Perforated sheet
  • ≤ 2mm aperture size or opening

Screen RULES


NCC 2022 V4


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 3.6

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to NCC Specification 1, NCC Part G5, & AS 3959
  • Corrosion-resistant Steel or Bronze Perforated Sheet or Mesh with
  • ≤ 2mm aperture size or openingAS 3959:2018, 3.6

AS 3959:2018, 7.6.5 (a)

AS 3959:2018, 7.6.5 (b)

Roof


  • Non-combustible materials[1]
  • Junctions sealed[2]


Screen RULES


NCC 2022 V4


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 3.6

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to NCC Specification 1, NCC Part G5, & AS 3959
  • Corrosion-resistant Steel or Bronze Perforated Sheet or Mesh with
  • ≤ 2mm aperture size or openingAS 3959:2018, 3.6

Roofing RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 7.6.1 (a)

AS 3959:2018, 7.6.1 (b)

AS 3959:2018, 7.6.1 (c)

AS 3959:2018, 7.6.1 (e)

AS 3959:2018, 7.6.1 (e)


AS 3959:2018, 7.6.1 (a)

AS 3959:2018, 7.6.1 (b)