Wall & Floor Construction BAL-FZ Building Codes & Rules


- Comply with Bushfire Construction Requirements with Tools™: BAL-FZ requirements, fire danger insights, & detailed guidance for walls, roof, guttering & more!


Tools™ Best Practice

10 to 15Tools™ Best Practice

Allow for drainage

Vent

WH

AS 3959:2018, 9.4.2

Industry Recommendation

Movement Joint

AS 3959:2018, 9.6.6 (f)

Joints may be sealed with plastic joining strips, or timber storm mouldsAS 3959:2018, 9.6.6 (f)

Angle

Sarking

Cladding

Sarking

Sill Flashing

DPC /

Flashing

Sill

Drip Line

Flashing

Cavity

Closer

WH

Tools™ Best Practice

Impact protective layer preferredTools™ Best Practice

Tools™ Best Practice

SarkingTools™ Best Practice

  • ≥ 150mm horizontal lap
  • Vertical lap over 2 studs

Sarking

Tools™ Best Practice

≥ 150Tools™ Best Practice

Tools™ Best Practice

≥ 150Tools™ Best Practice

Lap & Tape

Lap & Tape

Floor Framing

Wall Framing

WH

Cladding Wall Construction

Masonry Veneer Construction

Doors & Windows


  • -/30/- FRL[1][2][3] system, or
  • System to AS 1530.8.2[4][5][6]
  • Fully seal with non-combustible trims, mouldings & sealants[7][8]


Door RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 9.5.4 (a)

AS 3959:2018, 9.5.4 (b) (i) (A)

AS 3959:2018, 9.5.4 (b) (i) (B)

AS 3959:2018, 9.5.4 (b) (ii)

AS 3959:2018, 9.5.4 (b) (iii)

AS 3959:2018, 9.5.4 (b) (iv)

NCC 2022 Vol 2, H7D4

NCC 2022 Vol 1, G5

Screen RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 9.5.2

AS 3959:2018, 9.5.2

NCC 2022 Vol 1, G5

NCC 2022 Vol 2, H7D4

Bushfire Shutter RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 9.5.1 (b)

AS 3959:2018, 9.5.1 (a)

AS 3959:2018, 9.5.1 (a)

AS 3959:2018, 9.5.1 (a)

NCC 2022 Vol 2, H7D4

NCC 2022 Vol 1, G5

Windows & Glazed Doors RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 9.5.3 (a)

AS 3959:2018, 9.5.3 (b) (i)

AS 3959:2018, 9.5.3 (b) (ii)

NCC 2022 Vol 1, G5

NCC 2022 Vol 2, H7D4

Gaps RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 3.6.2

NCC 2022 Vol 1, G5

NCC 2022 Vol 2, H7D4

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to NCCAS 3959:2018, 3.6.2NCC 2022 Vol 1, G5
  • Gaps to Doors & Windows Opening detailsNCC 2022 Vol 2, H7D4
  • Door
  • ≤ 2mm aperture size of Door Ember Screens, tight closed fit
  • Seal gaps at Jambs, Head, & Sill with Draught Seals & Excluders
  • Window
  • ≤ 2mm aperture size of Window Screens, tight fit to Frames
  • Compliance with AS 2047 ensures Windows meet Gap protection requirements

AS 3959:2018, 9.5.4 (b) (i) (A)

AS 3959:2018, 9.5.4 (b) (i) (B)

AS 3959:2018, 9.5.5 (b) (i) (A)

AS 3959:2018, 9.5.5 (b) (i) (B)

AS 3959:2018, 9.5.4

AS 3959:2018, 9.5.5

AS 3959:2018, 9.5.3 (b) (i)

AS 3959:2018, 9.5.3 (b) (ii)

Vents & Weepholes


  • Screened[1]
  • ≤ 1.2m Weephole spacing[2][3]


Weephole RULES


NCC 2022 V4


Class 1 & 10


NCC 2022 H1D5 & HP5.7.5

[2019 3.3.1-3.3.3, 3.3.5-3.3.6, 3.3.5.9]


May 2023



AS 3700:2018, 4.7.2

NCC 2022 Vol 2, H1D5

NCC 2022 HP, 5.7.5

Vent & Weepholes RULES


NCC 2022 V1


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 9.4.3

NCC 2022 Vol 1, G5

NCC 2022 Vol 2, H7D4

AS 3700:2018, 4.7.2

AS 3959:2018, 9.4.3

NCC 2022 HP, 5.7.5 (1) (b)

Floors


  • 30/30/30 FRL[1] & non-combustible material, or
  • ≥ 30 mins RISF[2], or
  • System to AS 1530.8.2[3]


Subfloor Support RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 9.2 (a)

AS 3959:2018, 9.2 (b)

NCC 2022 Vol 2, H7D4

NCC 2022 Vol 1, G5

AS 3959:2018, 9.2

AS 3959:2018, 9.3.2.1

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to NCCAS 3959:2018, 9.2 (a)AS 3959:2018, 9.2 (b)
  • Combustible materials stored in the Subfloor space are susceptible to ember intrusion & pose a fire hazard to the building's structureNCC 2022 Vol 2, H7D4
  • Enclosed SubfloorNCC 2022 Vol 1, G5
  • No construction requirements if the Subfloor supports are enclosed & protected with a BAL-FZ compliant Wall
  • Unenclosed Subfloor
  • Protection for support Posts, Columns, Stumps, Piers, & Poles to have
  • 30/-/- FRL non-combustible structure, orAS 3959:2018, 9.2
  • System to AS 1530.8.2AS 3959:2018, 9.3.2.1

Deck & Landings RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 9.7.2.4 (a)

AS 3959:2018, 9.7.3.3 (a)

AS 3959:2018, 9.7.2.1 (a)

AS 3959:2018, 9.7.3

AS 3959:2018, 9.7.3.1 (a)

AS 3959:2018, 9.7.3.2 (a)

NCC 2022 Vol 2, H7D4

NCC 2022 Vol 1, G5

Floor RULES


NCC 2022 V2


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


Dec 2020 to Current



AS 3959:2018, 9.3.1

AS 3959:2018, 9.3.2.1

AS 3959:2018, 9.3.2.2

NCC 2022 Vol 1, G5

NCC 2022 Vol 2, H7D4

AS 3959:2018, 9.3.2.2 (a)

AS 3959:2018, 9.3.2.2 (b)

AS 3959:2018, 9.3.2.2 (c)

Cladding


  • -/30/30 FRL[1] or
  • System to AS 1530.8.2[2]
  • Metal, Fibre-cement or other non-combustible material[3]


Wall RULES


NCC 2022 V1


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 9.4.1 (b)

AS 3959:2018, 9.4.2

NCC 2022 Vol 1, G5

NCC 2022 Vol 2, H7D4

AS 3959:2018, 9.4.1 (a)

AS 3959:2018, 9.4.1 (c)

Jointing RULES


NCC 2022 V3


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 9.4.2

NCC 2022 Vol 1, G5

NCC 2022 Vol 2, H7D4

AS 3959:2018, 9.4.1 (c)

AS 3959:2018, 9.4.1 (b)

AS 3959:2018, 9.4.1 (c)

Roof Construction BAL-FZ

AS 3959:2018, 9.2 (a)

AS 3959:2018, 9.2 (b)

Sub-floor Support

AS 3959:2018, 9.6.6 (c) (i)

AS 3959:2018, 9.6.6 (c) (ii)

Eaves -/30/30 FRLAS 3959:2018, 9.6.6 (c) (i) or

System to AS 1530.8.2AS 3959:2018, 9.6.6 (c) (ii)

MR

FR Plasterboard

MR

FR Plasterboard

AS 3959:2018, 9.6.6 (c) (i)

AS 3959:2018, 9.6.6 (c) (ii)

Eaves -/30/30 FRLAS 3959:2018, 9.6.6 (c) (i) or

System to AS 1530.8.2AS 3959:2018, 9.6.6 (c) (ii)

Informative

CondensationInformative

  • Ensure Cavity ventilation
  • Consider condensation management for local Climate Zone

Sarking


  • ≤ 5 flammability index[1]
  • Walls & Roof fully sarked[2][3][4]


Sarking RULES


NCC 2022 V1


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 3.10

NCC 2022 Vol 1, G5

NCC 2022 Vol 2, H7D4

AS 3959:2018, 3.10

AS 3959:2018, H2 (f)

AS 3959:2018, 9.6.2 (a)

AS 3959:2018, 9.6.3 (a)

AS 3959:2018, 3.6.1

Masonry


  • 30/30/30, or -/30/30 FRL[1]
  • System to AS 1530.8.2[2]


Wall RULES


NCC 2022 V1


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 9.4.1 (b)

AS 3959:2018, 9.4.2

NCC 2022 Vol 1, G5

NCC 2022 Vol 2, H7D4

AS 3959:2018, 9.4.1 (a)

AS 3959:2018, 9.4.1 (c)

Vent & Weepholes RULES


NCC 2022 V1


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 9.4.3

NCC 2022 Vol 1, G5

NCC 2022 Vol 2, H7D4

AS 3959:2018, 9.4.1 (c)

AS 3959:2018, 9.4.1 (b)

Enclosed Sub-floor


  • Prevents the need to protect floor framing[1]
  • Reduces build-up of leaf litter & other materials that increase risk[2]


Enclosed Sub-floor


NCC 2022 V1


Tools™ Best Practice

Tools™ Best Practice