Compartmentation & Separation Building Codes & Rules


- Understand the key rules of compartmentation in high-risk buildings and discover how Tools™ can simplify compliance with easy-to-use, interactive graphics.


Fire Compartment 1

Fire Compartment 1

Fire Wall

Fire Wall

Fire Rated Floor

Fire Rated Floor

Fire Rated Floor

Smoke Door

Fire Compartment 1

NCC 2022 Vol 1, C3D7 (1) (a) (iii)

60/60/60 FRLNCC 2022 Vol 1, C3D7 (1) (a) (iii)

NCC 2022 Vol 1, C3D15

≤ 40mNCC 2022 Vol 1, C3D15

Fire Compartment 2

Fire Compartment 2

Substation

or MSB

Class 2 & 3

Public Corridor

Plant Room /

Lift Motor

NCC 2022 Vol 1, C3D9

Building Classifications in Same StoreyNCC 2022 Vol 1, C3D9

  • FRL as per highest Class requirement, or
  • Separated by a Fire Wall

NCC 2022 Vol 1, C3D10

Building Classifications in Different StoreysNCC 2022 Vol 1, C3D10

  • Floor separating between Storeys
  • Type A Construction
  • FRL as per Class of lower Storey
  • Type B & C Construction
  • ≥ 30/30/30 FRL, or
  • ≥ 60min RISF Floor / Ceiling system, or
  • Fire protective covering to underside of Floor system

NCC 2022 Vol 1, C3D11

Lifts & StairsNCC 2022 Vol 1, C3D11

  • Lift Shaft separated if connecting
  • ≥ 2 Storeys
  • ≥ 3 Storeys if Sprinklered
  • Separated from Stair if either is required to be in a Fire-resisting Shaft

NCC 2022 Vol 1, C3D14

AS/NZS 3013:2005, 3.1.2

Substation & MSBNCC 2022 Vol 1, C3D14AS/NZS 3013:2005, 3.1.2

  • ≥ 120/120/120 FRL separation
  • - /120/30 FRL Self closing Door
  • FRL not required to MSB if not maintaining Emergency Equipment
  • Emergency supply switchgear to be separated from non-emergency parts by metal partitions designed to minimise spread of a fault

Type of Construction

Type A Construction

Type C Construction

Lifts

Atrium

Large Isolated Building

Vertical Separation


  • Type A Construction[1]
  • ≥ 60/60/60 FRL between Storeys


Vertical Separation RULES


NCC 2022 V3


Class 2 to 9


NCC 2022, C3D7 [2019, C2.6]


May 23



NCC 2022 Vol 1, C3D7 (1)

NCC 2022 Vol 1, C3D7 (2)

  • External walls in Type A ConstructionNCC 2022 Vol 1, C3D7 (1)
  • A Building must have elements to prevent vertical spread of Fire between Storeys
  • Vertical separation is achieved by
  • ≥ 60/60/60 FRL & non-combustible Wall, Spandrel or Horizontal Projection separating each Storey, or
  • Building is Fully Sprinklered
  • Does not apply toNCC 2022 Vol 1, C3D7 (2)
  • Open-deck Carpark or open Spectator Stand
  • Openings within the same stairway
  • External Walls where FRL of Floors are not required for integrity & insulation

NCC 2022 Vol 1, C3D7 (1)

Type B Construction

Class 9 Buildings


  • Class 9a Health Care Building[1]
  • ≤ 2,000m² Patient Care Areas
  • ≤ 1,000m² Ward Areas


Health Care Building RULES


NCC 2022 V1


Class 9a


NCC 2022, C3D6 [2019, C2.5]


May 2023



Early Childhood Centre RULES


NCC 2022 V1


Class 9b


NCC 2022, C3D6(2) [2019 C2.5]


May 2023



Aged Care Building RULES


NCC 2022 V1


Class 9c


NCC 2022, C3D6(3) [2019, C2.5]


May 2023



NCC 2022 Vol 1, C3D6

  • Class 9a Health Care BuildingNCC 2022 Vol 1, C3D6
  • ≤ 2,000m² Patient Care Areas
  • ≤ 1,000m² Ward Areas

Plant Equipment


  •  High Risk Plant must be separated by[1]
  • 120/120/120 FRL unless
  • Higher FRL required by Type of Construction
  • Self closing Door
  • - /120/30
  • Lift Motor Room to Shaft
  • 120/ - / -


Plant Separation RULES


NCC 2022 V3


Class 2 to 9


NCC 2022, C3D13 [2019, C2.12]


1 May 2023



NCC 2022 Vol 1, C3D13

  • Plant required to be separatedNCC 2022 Vol 1, C3D13
  • Lift Machine Rooms
  • Machine room-less Lifts excluded
  • Emergency Generators
  • Boiler Rooms
  • Battery Systems if
  • ≥ 12V & 200kWh storage
  • On-site Fire Pumps
  • to AS 2419.1
  • Equipment Comprising
  • Emergency generators
  • Central smoke control plant
  • Boilers
  • ≥ 12V & ≥ 200kWh battery system
  • On-site fire pumps
  • Central Smoke Control Plant
  • Excludes Stair Pressurisation to AS 1668.1, &
  • High Temperature Smoke Exhaust Fans

NCC 2022 Vol 1, C3D13 (4)

  •  High Risk Plant must be separated byNCC 2022 Vol 1, C3D13 (4)
  • 120/120/120 FRL unless
  • Higher FRL required by Type of Construction
  • Self closing Door
  • - /120/30
  • Lift Motor Room to Shaft
  • 120/ - / -

Measuring Area & Volume


  • Include[1]
  • Total space of the building, or
  • Space within a Fire Compartment
  • Exclude[2][3]
  • Atrium Well
  • Mechanical & service facilities on top Floor


Volume & Area EXCLUSIONS


NCC 2022 V3


All Building Classes


NCC 2022, C3D3 [2019, C2.2]


May 2023



NCC 2022 Vol 1, C3D3 (2)

NCC 2022 Vol 1, C3D3 (3)

  • Top floor of Building only housingNCC 2022 Vol 1, C3D3 (2)
  • Heating, Ventilation, Lift Equipment
  • Water Tanks
  • Other similar Plant Equipment
  • Volume of an Atrium WellNCC 2022 Vol 1, C3D3 (3)
  • Measured from face of Floor Opening, &
  • from level of 1st Floor above Atrium Floor

NCC 2022 Vol 1, C3D3 (1)

NCC 2022 Vol 1, C3D3 (2)

NCC 2022 Vol 1, C3D3 (3)

Informative

Parts of a Building from Class 1, 2, 3 & 4 Informative

  • Compartmentation not applicable