Fire Control Room Building Codes & Rules


- Enhance fire safety with Fire Control Room (FCR) solutions. Tools™ translates NCC and standards into user-friendly graphics, integrating compliance & best pract


NCC 2022 Vol 1, S19C6

Ambient SoundNCC 2022 Vol 1, S19C6

  • ≤ 65 dB(A)
  • 60 seconds testing for low noise level areas
  • Sufficient testing period to characterize all sound sources

Whiteboard/

Blackboard

NCC 2022 Vol 1, S19C10 (1) (b)

TelephoneNCC 2022 Vol 1, S19C10 (1) (b)

  • Link to external telephone exchange

Pin up Board

NCC 2022 Vol 1, S19C10 (2) (a)

Additional EquipmentNCC 2022 Vol 1, S19C10 (2) (a)

  • Master Emergency Control Panels
  • Lift Annunciator Panel
  • Gas or electrical remote switches
  • Emergency Generator

NCC 2022 Vol 1, S19C10 (1) (e)

Raked Plan Layout TableNCC 2022 Vol 1, S19C10 (1) (e)

  • Of suitable size for Tactical Fire Plans
  • Colour-coded
  • Durable

NCC 2022 Vol 1, S19C9 (2) (b)

Fire Isolated EgressNCC 2022 Vol 1, S19C9 (2) (b)

  • ≥ - /120/30 FRL door

NCC 2022 Vol 1, S19C10 (1) (d)

≥ 1.0mNCC 2022 Vol 1, S19C10 (1) (d)

NCC 2022 Vol 1, S19C10 (1) (c)

≥ 1.0mNCC 2022 Vol 1, S19C10 (1) (c)

NCC 2022 Vol 1, S19C10 (1) (d)

≥ 1.2mNCC 2022 Vol 1, S19C10 (1) (d)

NCC 2022 Vol 1, S19C10 (3) (a)

≥ 2.5mNCC 2022 Vol 1, S19C10 (3) (a)

NCC 2022 Vol 1, S19C10 (3) (a)

≥ 2.5mNCC 2022 Vol 1, S19C10 (3) (a)

NCC 2022 Vol 1, S19C9

External AccessNCC 2022 Vol 1, S19C9

  • To a public place
  • From a fire-isolated passageway leading to an outdoor space
  • Lockable, self-closing & smoke-sealed fire door
  • - /120/30 FRL assembly

NCC 2022 Vol 1, S19C10 (1) (c)

≥ 1.2mNCC 2022 Vol 1, S19C10 (1) (c)

NCC 2022 Vol 1, S19C10 (2) (b)

Additional EquipmentNCC 2022 Vol 1, S19C10 (2) (b)

  • Building Security
  • Surveillance & Management System (isolated from other systems)

NCC 2022 Vol 1, S19C11 (1) (b)

NCC 2022 Vol 1, S19C11 (1) (b) (iv)

NCC 2022 Vol 1, S19C11 (1) (b) (iii)

Exhaust Mechanical Vents

Designated Building

Entry Point (DBEP)

NCC 2022 Vol 1, S19C7

NCC 2022 Vol 1, S19C5

ABCB Fire Engineering Guideines 1st Edition March 1996, 3.5

Fire Control Room (FCR)

Fire - isolated

Passage Way

NCC 2022 Vol 1, S19C10 (1) (a)

AS 1670.1:2018, 3.9

Fire Indicator Panel (FIP)NCC 2022 Vol 1, S19C10 (1) (a)

  • Detects fire-related change in environment
  • Contains Control & Indicating Equipment (CIE)AS 1670.1:2018, 3.9

NCC 2022 Vol 1, S19C12

Door SignageNCC 2022 Vol 1, S19C12

  • ≥ 50mm font size
  • In contrasting color

NCC 2022 Vol 1, S19C9 (1)

Door SwingNCC 2022 Vol 1, S19C9 (1)

  • Ideally opens to direction of escape, except when
  • Few people use the door
  • Door blocks the escape route
  • Protecting passersby

NCC 2022 Vol 1, S19C10 (3)

Floor SpaceNCC 2022 Vol 1, S19C10 (3)

  • ≥ 10m² floor area with ≥ 2.5m horizontal clearance
  • ≥ 8m² if without additional equipment
  • ≥ 1.5m² clear space in front of all Control & Indicator Panels
  • + ≥ 2m² floor area per additional equipment

NCC 2022 Vol 1, S19C9

NCC 2022 Vol 1, S19C8 (c)

Internal AccessNCC 2022 Vol 1, S19C9NCC 2022 Vol 1, S19C8 (c)

  • Towards DBEP
  • Not obstruct access to FCC
  • Self-closing & smoke-sealed fire door
  • - /120/30 FRL assembly
  • Lockable

NCC 2022 Vol 1, S19C7

NCC 2022 Vol 1, S19C11 (2)

FCC ConstructionNCC 2022 Vol 1, S19C7

  • 120/120/120 FRL enclosure
  • Unless used for FCC, NO pipes, ducts, services & the like may pass through

Openable DevicesNCC 2022 Vol 1, S19C11 (2)

  • Only the necessary key-operated access
  • Doors & windows
  • Pressure-controlled Relief Louvres

Location Access from DEBP

  • ≤ 5m from attendance point or main building entrance

NCC 2022 Vol 1, S19C13

LightNCC 2022 Vol 1, S19C13

  • ≥ 400 lux over Plan Layout Table

NCC 2022 Vol 1, S19C7 (a)

120 / 120 / 120 FRLNCC 2022 Vol 1, S19C7 (a)

Fire Indicator Panel

External Visual Alarm Device

NCC 2022 Vol 1, E4D2 (i)

NCC 2022 Vol 1, E4V1 (5)

Emergency LightingNCC 2022 Vol 1, E4D2 (i)

NCC 2022 Vol 1, S19C11 (1) (b)

NCC 2022 Vol 1, S19C11 (1) (b) (iv)

NCC 2022 Vol 1, S19C11 (1) (b) (iii)

Supply Mechanical Vents

NCC 2022 Vol 1, S19C4

EgressNCC 2022 Vol 1, S19C4

  • ≤ 300mm aggregate level change to Road or Open Space