NCC 2022 Vol 1, S19C6
Ambient SoundNCC 2022 Vol 1, S19C6
- ≤ 65 dB(A)
- 60 seconds testing for low noise level areas
- Sufficient testing period to characterize all sound sources
NCC 2022 Vol 1, S19C10 (1) (b)
NCC 2022 Vol 1, S19C10 (2) (a)
Additional EquipmentNCC 2022 Vol 1, S19C10 (2) (a)
- Master Emergency Control Panels
- Lift Annunciator Panel
- Gas or electrical remote switches
- Emergency Generator
NCC 2022 Vol 1, S19C10 (1) (e)
NCC 2022 Vol 1, S19C9 (2) (b)
NCC 2022 Vol 1, S19C10 (1) (d)
NCC 2022 Vol 1, S19C10 (1) (c)
NCC 2022 Vol 1, S19C10 (1) (d)
NCC 2022 Vol 1, S19C10 (3) (a)
NCC 2022 Vol 1, S19C10 (3) (a)
NCC 2022 Vol 1, S19C9
External AccessNCC 2022 Vol 1, S19C9
- To a public place
- From a fire-isolated passageway leading to an outdoor space
- Lockable, self-closing & smoke-sealed fire door
- - /120/30 FRL assembly
NCC 2022 Vol 1, S19C10 (1) (c)
NCC 2022 Vol 1, S19C10 (2) (b)
NCC 2022 Vol 1, S19C11 (1) (b)
NCC 2022 Vol 1, S19C11 (1) (b) (iv)
NCC 2022 Vol 1, S19C11 (1) (b) (iii)
Designated Building
Entry Point (DBEP)
NCC 2022 Vol 1, S19C7
NCC 2022 Vol 1, S19C5
ABCB Fire Engineering Guideines 1st Edition March 1996, 3.5
Fire - isolated
Passage Way
NCC 2022 Vol 1, S19C10 (1) (a)
AS 1670.1:2018, 3.9
NCC 2022 Vol 1, S19C12
NCC 2022 Vol 1, S19C9 (1)
Door SwingNCC 2022 Vol 1, S19C9 (1)
- Ideally opens to direction of escape, except when
- Few people use the door
- Door blocks the escape route
- Protecting passersby
NCC 2022 Vol 1, S19C10 (3)
Floor SpaceNCC 2022 Vol 1, S19C10 (3)
- ≥ 10m² floor area with ≥ 2.5m horizontal clearance
- ≥ 8m² if without additional equipment
- ≥ 1.5m² clear space in front of all Control & Indicator Panels
- + ≥ 2m² floor area per additional equipment
NCC 2022 Vol 1, S19C9
NCC 2022 Vol 1, S19C8 (c)
NCC 2022 Vol 1, S19C7
NCC 2022 Vol 1, S19C11 (2)
FCC ConstructionNCC 2022 Vol 1, S19C7
- 120/120/120 FRL enclosure
- Unless used for FCC, NO pipes, ducts, services & the like may pass through
Openable DevicesNCC 2022 Vol 1, S19C11 (2)
- Only the necessary key-operated access
- Doors & windows
- Pressure-controlled Relief Louvres
Location Access from DEBP
- ≤ 5m from attendance point or main building entrance
NCC 2022 Vol 1, S19C13
NCC 2022 Vol 1, S19C7 (a)
Fire Indicator Panel
External Visual Alarm Device
NCC 2022 Vol 1, E4D2 (i)
NCC 2022 Vol 1, E4V1 (5)
NCC 2022 Vol 1, S19C11 (1) (b)
NCC 2022 Vol 1, S19C11 (1) (b) (iv)
NCC 2022 Vol 1, S19C11 (1) (b) (iii)
NCC 2022 Vol 1, S19C4