Fire Curtains & Shutters Building Codes & Rules


- Fire Curtains & Shutters : Tools™ simplifies the National Construction Code (NCC) with interactive graphics, including deemed to comply & best practices.


Flexible Fire-resistant Curtain Fabric

Optional Retract Button

Vertical Guide Rail

FRL Bulkhead

AS 1905.2:2005, 5.5

ThresholdAS 1905.2:2005, 5.5

  • Concrete or Non-combustible material
  • Tested as per AS 1530.1

Bushfire Shutter


  • If all external doors are protected, one must be operable from the inside to allow for safe escape[1]


Bushfire Shutter RULES


NCC 2022 V4


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 3.7 (d)

AS 3959:2018, 3.7 (e)

AS 3959:2018, 3.7 (f)

AS 3959:2018, 3.7 (g)

AS 3959:2018, 3.7 (g)

AS 3959:2018, 3.7

AS 3959:2018, 3.7 (a)

AS 3959:2018, 3.7 (b)

Screen RULES


NCC 2022 V1


All Building Classes


NCC 2022 G5, H7D4, & S1

[2019 G5, 3.10.5, Sch 5]


May 2023



AS 3959:2018, 3.6

  • Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to NCC Specification 1, NCC Part G5, & AS 3959
  • Corrosion-resistant Steel or Bronze Perforated Sheet or Mesh with
  • ≤ 2mm aperture size or openingAS 3959:2018, 3.6

AS 3959:2018, 3.7

  • If all external doors are protected, one must be operable from the inside to allow for safe escapeAS 3959:2018, 3.7

AS 1905.2:2005, 5.6

Fusible LinkAS 1905.2:2005, 5.6

  • ≤ 250mm distance from Barrel Assembly
  • ≥ 4m wide openings, they shall have
  • ≥ 2 Fusible link series at both opening ends
  • Installed on the same side as the barrel
  • Exposed to prevailing winds

AS 1905.2:2005, 6

Fire Shutter Metal TagAS 1905.2:2005, 6

  • ≥ 50 x ≥ 25mm tag attached at the bottom rail
  • Information requirements
  • Installation date
  • Identification number
  • Fire Resistance Level
  • Manufacturer or certifier’s name
  • Supplier & Certifier's note complying with AS 1905.2

Manufacturer's Requirement

Possible ObstructionsManufacturer's Requirement

  • ≥ 100mm clearance from any obstructions

Vertical Guide Track

AS 1905.2:2005, 5.3 (b)

≤ 10AS 1905.2:2005, 5.3 (b)

AS 3959:2018, 3.7

Window or Door AssemblyAS 3959:2018, 3.7

  • Fully protected by Fire Shutter
  • As per AS 3959

AS 1905.2:2005, 5.5

≥ 150AS 1905.2:2005, 5.5

Manufacturer's Requirement

Access PanelsManufacturer's Requirement

  • Provide only when Fire Curtain Controller is installed within ceiling cavity

AS 1905.2:2005, 5.3 (b)

≤ 10AS 1905.2:2005, 5.3 (b)

AS 1905.2:2005, 5.5

≥ 150AS 1905.2:2005, 5.5

AS 1905.2:2005, 5.3 (c)

≤ 30AS 1905.2:2005, 5.3 (c)

Manufacturer's Requirement

Opening or Door Assembly

Door Compliance Tagging

AS 1905.2:2005, 5.3

Vertical Guide Track

  • Enables seamless motion of the Fire-resistant Curtain
  • Shall be wall-mounted with the curtain overlapping evenly on both sides of the openingAS 1905.2:2005, 5.3

Bottom Bar

Bottom Rail

NCC 2022 Vol 1, C4D5 (2)

AS 1905.2:2005, 5.7

AS 1905.2:2005, 7

Fire Curtain & Fire Shutter

Rigid Fire-resistant Curtain

AS 1905.2:2005, 5.4

Fire-resistant CurtainAS 1905.2:2005, 5.4

  • Bottom bar should reach threshold
  • ≥ 50% of the Fire Curtain wrap should still be inside the barrel assembly when activated

Tools™ Best Practice

  • Exposed or unobtrusively recessed into the wallTools™ Best Practice
  • On Designer's & Engineer's Specification
  • Check project documentation

Fusible Link

Barrel Assembly

Barrel Assembly

Controller

AS 1905.2:2005, 5.2

Barrel AssemblyAS 1905.2:2005, 5.2

  • Installed with the rolled-up curtain above the guide tracks and secured with brackets
  • If non-combustible roller shutters are larger than the tested model for fire resistance
  • Bracket fixing durability will increase accordingly to the added load