Bushfire Shutter
- If all external doors are protected, one must be operable from the inside to allow for safe escape[1]
Bushfire Shutter RULES
NCC 2022 V4
All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
AS 3959:2018, 3.7 (d)
AS 3959:2018, 3.7 (e)
AS 3959:2018, 3.7 (f)
AS 3959:2018, 3.7 (g)
AS 3959:2018, 3.7 (g)
AS 3959:2018, 3.7
AS 3959:2018, 3.7 (a)
AS 3959:2018, 3.7 (b)
- Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to NCC Specification 1, NCC Part G5, & AS 3959
- Protect Window & Door assemblyAS 3959:2018, 3.7 (d)AS 3959:2018, 3.7 (e)
- Non-removable & securely attached to the buildingAS 3959:2018, 3.7 (f)
- Able to be closed manually in case of power failureAS 3959:2018, 3.7 (g)
- Gaps & Perforations
- ≤ 2mm gap to Wall, Frame, or SillAS 3959:2018, 3.7 (g)
- ≤ 20% perforated areaAS 3959:2018, 3.7
- ≤ 2mm aperture size openings, evenly distributedAS 3959:2018, 3.7 (a)
- Safe Exit / EgressAS 3959:2018, 3.7 (b)
- ≥ 1 to be openable from inside to allow escape
Screen RULES
NCC 2022 V1
All Building Classes
NCC 2022 G5, H7D4, & S1
[2019 G5, 3.10.5, Sch 5]
May 2023
AS 3959:2018, 3.6
- Building elements within Bushfire-prone Areas to be Bushfire Attack Resistant to NCC Specification 1, NCC Part G5, & AS 3959
- Corrosion-resistant Steel or Bronze Perforated Sheet or Mesh with
- ≤ 2mm aperture size or openingAS 3959:2018, 3.6
AS 3959:2018, 3.7
- If all external doors are protected, one must be operable from the inside to allow for safe escapeAS 3959:2018, 3.7
AS 1905.2:2005, 5.6
Fusible LinkAS 1905.2:2005, 5.6
- ≤ 250mm distance from Barrel Assembly
- ≥ 4m wide openings, they shall have
- ≥ 2 Fusible link series at both opening ends
- Installed on the same side as the barrel
- Exposed to prevailing winds
AS 1905.2:2005, 6
Fire Shutter Metal TagAS 1905.2:2005, 6
- ≥ 50 x ≥ 25mm tag attached at the bottom rail
- Information requirements
- Installation date
- Identification number
- Fire Resistance Level
- Manufacturer or certifier’s name
- Supplier & Certifier's note complying with AS 1905.2
Manufacturer's Requirement
AS 1905.2:2005, 5.3 (b)
AS 3959:2018, 3.7
Window or Door AssemblyAS 3959:2018, 3.7
- Fully protected by Fire Shutter
- As per AS 3959
AS 1905.2:2005, 5.5
Manufacturer's Requirement
AS 1905.2:2005, 5.3 (b)
AS 1905.2:2005, 5.5
AS 1905.2:2005, 5.3 (c)
Manufacturer's Requirement
Door Compliance Tagging
AS 1905.2:2005, 5.3
Vertical Guide Track
- Enables seamless motion of the Fire-resistant Curtain
- Shall be wall-mounted with the curtain overlapping evenly on both sides of the openingAS 1905.2:2005, 5.3
NCC 2022 Vol 1, C4D5 (2)
AS 1905.2:2005, 5.7
AS 1905.2:2005, 7
Fire Curtain & Fire Shutter
Rigid Fire-resistant Curtain
AS 1905.2:2005, 5.4
Fire-resistant CurtainAS 1905.2:2005, 5.4
- Bottom bar should reach threshold
- ≥ 50% of the Fire Curtain wrap should still be inside the barrel assembly when activated
Tools™ Best Practice
- Exposed or unobtrusively recessed into the wallTools™ Best Practice
- On Designer's & Engineer's Specification
- Check project documentation
AS 1905.2:2005, 5.2
Barrel AssemblyAS 1905.2:2005, 5.2
- Installed with the rolled-up curtain above the guide tracks and secured with brackets
- If non-combustible roller shutters are larger than the tested model for fire resistance
- Bracket fixing durability will increase accordingly to the added load