Travel Width (Egress)
Luminance Contrast
AS/NZS 2293.1:2018, 5.6
AS/NZS 2293.1:2018, 4.8.2 (a)
AS/NZS 2293.1:2018, 4.5 (a)
AS/NZS 2293.1:2018, 5.8
AS/NZS 2293.1:2018, 5.6
AS/NZS 2293.1:2018, Figure 4.3
AS/NZS 2293.1:2018, Figure 4.3
AS/NZS 2293.1:2018, 4.5
AS/NZS 2293.1:2018, Appendix E, Table E4
AS/NZS 2293.1:2018, Appendix F, Table F4
AS/NZS 2293.1:2018, 4.8.2
Emergency Light at Stair LandingsAS/NZS 2293.1:2018, 4.8.2
- Not required at every stair landing if alternate landings meet spacing & lux requirements
AS/NZS 2293.1:2018, 5.6
AS/NZS 2293.1:2018, 5.6
- Height of Pictorial element may depend on viewing distanceAS/NZS 2293.1:2018, 5.6
- If viewing distance is ≥ 32m
- ≥ Pictorial height = ≤ Viewing Distance ÷ 160
Labelling & Identification
- ≥ 3mm tall font, in contrasting colour[1]
- Clearly visible
- Permanently fixed and adjacent to the light/sign
Emergency Light & Exit Sign LABELLING & CLASSIFICATION
NCC 2022 V1
All Building Classes
NCC 2022 E4D2 [2019:E4.2]
May 2023
AS/NZS 2293.1:2018, 2.5
AS/NZS 2293.1:2018, 2.6
Label IdentifierAS/NZS 2293.1:2018, 2.5
- Each emergency light or sign shall have a unique label or identifier
- Use logical numbering or identification system for easier inspection
Classification & MarkingAS/NZS 2293.1:2018, 2.6
- Each emergency light or sign shall be marked with its illumination classification on its casing
- Compliant with AS/NZS 2293.3
- If the emergency light or sign lacks the required identification symbol, symbol should be
- Positioned adjacent to it
- Avoid placing on detachable ceiling tiles
AS/NZS 2293.1:2018, 2.5
- ≥ 3mm tall font, in contrasting colourAS/NZS 2293.1:2018, 2.5
- Clearly visible
- Permanently fixed and adjacent to the light/sign
Emergency Lighting on Stairwell
- Required in stairways to ensure adequate lighting for safety[1]
- Direct & Indirect Lighting
- Refer to table for light classification & spacing
Emergency Lighting in Stairway
NCC 2022 V1
All Building Classes
NCC 2022 E4D2 [2019:E4.2]
May 2023
AS/NZS 2293.1:2018, 4.8.2
AS/NZS 2293.1:2018, 4.8.3
AS/NZS 2293.1:2018, 4.8.4
Industry Recommendation
- Direct LightingAS/NZS 2293.1:2018, 4.8.2AS/NZS 2293.1:2018, 4.8.3
- Light source shines directly on surface of stairs & landings
- Place ≥1 emergency light with ≥1 lux of brightness at every landing
- Use grid points spaced ≤ 0.5m apart across the stair steps and landings
- Shall not exceed to maximum spacing referred in Table below
- Indirect LightingAS/NZS 2293.1:2018, 4.8.4
- Light source shines on reflective surfaces such as ceiling & walls to spread across the stairway
- Place emergency light with ≥1 lux of brightness
- Use grid points spaced ≤ 0.5m apart across the stairway
- Avoid glare by using screened lights, which prevent the light-emitting parts from being visible to people
- Use of Class D emergency lighting for safe evacuation layoutsIndustry Recommendation
AS/NZS 2293.1:2018, 4.8
- Required in stairways to ensure adequate lighting for safetyAS/NZS 2293.1:2018, 4.8
- Direct & Indirect Lighting
- Refer to table for light classification & spacing
Maximum Spacing of Emergency Lighting
- Determined by classification & mounting height from FFL[1]
Spacing of Emergency Lighting in Corridors
NCC 2022 V1
All Building Classes
NCC 2022 E4D2 [2019:E4.2]
May 2023
AS/NZS 2293.1:2018, 4.5
- Place emergency light within 2m in the ff. areasAS/NZS 2293.1:2018, 4.5
- From the approach side of the Exit door
- In every intersecting corridors & turns
- Varies depending on lighting situation
- Any change of floor level
Emergency Lighting SPACING
NCC 2022 V1
All Building Classes
NCC 2022 E4D2 [2019:E4.2]
May 2023
AS/NZS 2293.1:2018, 4.6.1.2 (a)
AS/NZS 2293.1:2018, 4.6.1.2 (b)
Industry Recommendation
- Spacing between Emergency LightingAS/NZS 2293.1:2018, 4.6.1.2 (a)
- Shall not exceed the values given from the Table below
- Positioned based on their type and mounting height
- If the lights have different classifications
- Consider light orientation if coverage differs in Transverse & Longitudinal planes
- If lights are not parallel or at different angles
- Ensure that their lighted areas overlap enough to fully cover the designated area
- Availability of range shall be checked by Suppliers
- Spacing between Emergency Lighting & WallsAS/NZS 2293.1:2018, 4.6.1.2 (b)
- ≤ 1/2 of the spacing in accordance with the Table below
- Use of Class D emergency lighting for safe evacuation layoutsIndustry Recommendation
AS/NZS 2293.1:2018, 4.6.1.2
Emergency Light
- Required in fire-isolated stairways, passageways, & ramps[1]
- Compliance with AS/NZS 2293.1[2]
Emergency Lighting REQUIREMENTS
NCC 2022 V2
All Building Classes
NCC 2022 E4D2 [2019:E4.2]
May 2023
AS/NZS 2293.1:2018, 4.2
AS/NZS 2293.1:2018, 4.4
AS/NZS 2293.1:2018, 4.3
- Provision & InstallationAS/NZS 2293.1:2018, 4.2
- Ensure lights are not blocked by structural elements like beams or coffered ceilings
- Place directional emergency lights to avoid glare or vision impairment
- Mounted at ≤ 2.4m high in Public Areas
- Use non-removable lamps, wire guards, or diffusers to safeguard lights
- Dual-Function Exit SignsAS/NZS 2293.1:2018, 4.4
- Acceptable if they meet all relevant standards
- Follows AS/NZS 2293.3 installation guidelinesAS/NZS 2293.1:2018, 4.3
- ≤ 500m² area coverage for each light
- Consider room surfaces & smoke effects
Emergency Lighting & Exit OPERATION & CONTROL
NCC 2022 V3
All Building Classes
NCC 2022 E4D8 [2019: E4.8]
May 2023
AS/NZS 2293.1:2018, 2.2
AS/NZS 2293.1:2018, 2.3.4
AS/NZS 2293.1:2018, 2.1
AS/NZS 2293.1:2018, 2.4
- Emergency lighting systems must perform reliably during their lifetime with proper installation, maintenance, & testingAS/NZS 2293.1:2018, 2.2
- Duration of OperationAS/NZS 2293.1:2018, 2.3.4
- Initial Testing
- Test for 1.33 times the required duration, during initial set up to account for future battery degradation
- In-Service
- Operable for ≥ 90 minutes during emergencies, unless building regulations specify a shorter time
- Remote Self-contained Emergency LightAS/NZS 2293.1:2018, 2.1
- If the light or sign is ≥ 2m away from its control gear
- Ensure the cable design & setup maintain proper operation according to the standard
- If the cable is ≥ 10m or it crosses ≥ 1 fire compartment
- Provide Class WS4X protection as per AS/NZS 3013
- Labelling Control DevicesAS/NZS 2293.1:2018, 2.4
- Any control device (e.g., circuit breakers, fuses) affecting emergency lighting must display this warning:
"WARNING: INTERRUPTING SUPPLY WILL DISCHARGE EMERGENCY LIGHTING BATTERIES."
Emergency Lighting LOCATION
NCC 2022 V2
All Building Classes
NCC 2022 E4D2 [2019 E4.2]
May 2023
NCC 2022 Vol 1, E4D2
Installed inNCC 2022 Vol 1, E4D2
- Large Storeys in Buildings (Class 5, 6, 7, 8, or 9)
- ≥ 300m² areas in storeys
- Corridors or paths leading to exits
- Rooms ≥ 100m² that don’t open to emergency-lit areas, roads, or open spaces
- Rooms ≥ 300m²
- Residential Buildings (Class 2, 3, or 4 Units)
- ≥ 6m long corridors between unit doorways & the nearest exit leading to:
- Fire-isolated or external stairways, or
- Balconies, roads, or open spaces
- Non-Fire-isolated Stairs
- Large SOU (Class 5, 6, 9)
- ≥ 300m² units without direct exit to safe areas
- Public Areas (Class 6, 9b)
- ≥ 300m² within that storey,
- ≥ 20m from exits,
- With ≥ 1.5m high vertical egress, or
- To any vertical rise if natural light is insufficient
- Health-Care (Class 9a)
- ≥ 120m² rooms & treatment/ward corridors
- Aged Care (Class 9c)
- In all areas except SOUs
- Fire Control Centre
NCC 2022 Vol 1, E4D4
NCC 2022 Vol 1, E4D2 (a)
Emergency Exit Signs
- Exit & direction signs ensure clear paths to safety[1]
- Follow specific visibility and labeling rules
Emergency Exit & Direction Signs
NCC 2022 V1
NCC 2022 Vol 1, E4D5
NCC 2022 Vol 1, E4D6
NCC 2022 Vol 1, E4D7
NCC 2022 Vol 1, E4D8
- Exit SignsNCC 2022 Vol 1, E4D5
- Clearly visible near exits
- Install them on, above, or next to doors that
- Lead to stairs, ramps, or balconies used as exits
- Open to roads or open spaces at ground level
- Serve as emergency exits in areas requiring emergency lighting
- Direction SignsNCC 2022 Vol 1, E4D6
- Guide people to the nearest exits that are not easily seen
- Installed in hallways, corridors, or lobbies
- Exemptions for Residential Buildings (Class 2, 3, & 4)NCC 2022 Vol 1, E4D7
- Clearly labeled with the word "EXIT" in
- ≥ 25mm high capitalized letters, &
- Contrasting color to the background
- Exit Sign StandardsNCC 2022 Vol 1, E4D8
- As per AS/NZS 2293.1 & NCC
NCC 2022 Vol 1, E4D8
- Exit & direction signs ensure clear paths to safetyNCC 2022 Vol 1, E4D8
- Follow specific visibility and labeling rules
Fire Door Signage

Redirecting... (5)
Please wait while we redirect you to the correct page.