AAC Panel Wall (FRL) Building Codes & Rules


- FRL Material AAC Panel Tools™ simplifies the National Construction Code (NCC) with interactive graphics, including deemed to comply & best practices


Fire Resistance of Building Elements

  • Consult a Certified Professional for specific FRL requirements

AS 5146.3:2018, 2.6.2 (a)

50AS 5146.3:2018, 2.6.2 (a)

AS 3700:2018, 6.3.2.2

AS 3700:2018, 6.3.2.2

Adhesive at Edge Joints

Continuous Steel Angle

Continuous Steel Channel

DPC

Acoustics

  • Rw + Ctr 31

FRL Brickwork

FRL Plasterboard

FRL Blockwork

Services Chasing


  • Fire Resistance Requirement[1]
  • ≥ ½ of thickness, or
  • ≥ 10,000mm² within any 5m² area


AAC Services Chasing RULES


NCC 2022 V1


All Building Classes


NCC 2022, Specification 1, Specification 5 [2019: Sch 5:1, Spec C1.1:1]


May 2023



AS 5146.1:2015, 2.2.6 (b)

AS 5146.1:2015, 2.2.6 (c) (i)

AS 5146.1:2015, 2.2.6 (c) (ii)

AS 5146.1:2015, 2.2.6

  • Reinforced Autoclaved Aerated Concrete building elements be constructed to NCC Specification 1, 5, & AS 5146
  • If a recess in a reinforced AAC elementAS 5146.1:2015, 2.2.6 (b)
  • ≥ ½ AAC Panel or Block thickness, or
  • ≥ 10,000mm² within any 5m² area
  • Exclude the recess depth when calculating the element's FRL
  • Chasing Restrictions
  • Generally not allowedAS 5146.1:2015, 2.2.6 (c) (i)
  • Chasing is permitted if additional structural support is provided to maintain the required Structural AdequacyAS 5146.1:2015, 2.2.6 (c) (ii)
  • Chasing not requiredAS 5146.1:2015, 2.2.6
  • < 10,000mm² within any 5m² area

AS 5146.1:2015, 2.2.6

  • Fire Resistance RequirementAS 5146.1:2015, 2.2.6
  • ≥ ½ of thickness, or
  • ≥ 10,000mm² within any 5m² area