Fire Hose Reel Building Codes & Rules


- Explore fire hose reel solutions with Tools™: Find guidance on location, access, protection, signage, water supply, and valve interlock for compliance.


Plumbing Overview

AS 2441:2005, 11 (b)

≥ 75AS 2441:2005, 11 (b)

AS 2441:2005, 12 (b)

AS 2441:2005, 11 (e)

Hose Guide

AS 2441:2005, 11 (b)

1.4m

to

2.4mAS 2441:2005, 11 (b)

Valve

Interlock

AS 2441:2005, 10.1

AccessAS 2441:2005, 10.1

  • No obstructions
  • No non-firefighting items or services in recess or cabinet
  • Doors when open must not obstruct path of travel to an exit

AS 2441:2005, 11 (b)

≥ 150AS 2441:2005, 11 (b)

AS 2441:2005, 10.1

ProtectionAS 2441:2005, 10.1

  • Cabinet or shelter required if exposed to
  • Weather
  • Coastal / corrosive environments
  • Dusty / high moisture

AS 2441:2005, 11 (d)

100AS 2441:2005, 11 (d)

AS 2441:2005, 10.4.2

AS 2441:2005, 10.4.4

Signage

1m

clear

AS 2441:2005, 10.4.4

225AS 2441:2005, 10.4.4

AS 2441:2005, 10.4.3

≥ 2mAS 2441:2005, 10.4.3

AS 2441:2005, 5

NCC 2022 Vol 1, E1D3

NCC 2022 Vol 1, E1P1

Fire Hose Reel

Fire Door

AS 2441:2005, 6.2 (a)

AS 2441:2005, 6.1

AS 2441:2005, 7

Water Supply

  • ≥ 25 DN metered supplyAS 2441:2005, 6.2 (a)
  • 2 FHR farthest from the supply working concurrentlyAS 2441:2005, 6.1
  • ≥ 0.33 L/S delivery if Ø 19 hose
  • ≥ 0.41 L/S delivery if Ø 25 hose
  • Connection to be rigid or,
  • If flexible, must be part of a FHR to AS/NZS 1221AS 2441:2005, 7

AS 2441:2005, 11 (b)

900

to

1.1mAS 2441:2005, 11 (b)

Fire Hydrant Booster Assembly

AS 2441:2005, 11 (d)

100AS 2441:2005, 11 (d)

AS 2441:2005, 10.4.4

150AS 2441:2005, 10.4.4

AS 2441:2005, 11 (d)

100AS 2441:2005, 11 (d)