or wider Opening Angle may
reduce Hinge Side Clearance
AS 1670.1:2018, 3.9.1
AS 1670.1:2018, 3.9.3
AS 1670.1:2018, 3.9.1
Fire Panel LocationAS 1670.1:2018, 3.9.1
- 750mm to 1.85m AFFL Controls & Indicators
- Wall-mounted or in Recessed Cupboard
- Operation / Maintenance Clearance must not clash with Path of Egress
- Locate in minimum risk area for
- Equipment damage
- Personnel injury during emergency
AS 1670.1:2018, 3.9.3
Control & Indicator Height
AS 1670.1:2018, 3.9.3
AS 1670.1:2018, 3.9.3
AS 1670.1:2018, 3.22.3
AS 1670.1:2018, 3.9.3
AS 1670.1:2018, 3.9.2
AS 1670.1:2018, 3.9.1
AS 1670.1:2018, 3.10
AS 1670.4:2018, 3.3.5
Fire (Zone) Block PlanAS 1670.1:2018, 3.10AS 1670.4:2018, 3.3.5
- Permanent diagram clearly showing
- Building layout
- Areas covered by detection
- Each emergency zone
- Fire or Emergency Control Panels
- Main Electrical Switchboard
- ≥ 5mm font size Notice stating
In the event of fire,
ring 000 to ensure fire service response
- 'YOU ARE HERE' clearly marked and oriented correctly
- Year of installation & latest revision
- ≥ 3mm font size water & fade-resistant
- Used by the fire brigade
- To locate the FIP
- To determine fire risk area
- Used by fire services company
- For testing of detectors during annual testing
Manufacturer's Recommendation - -, -
AS 1670.1:2018, 3.1
Fire Indicator Panel (FIP)
- Synonymous to Fire Detection Control & Indicating Equipment (FDCIE)
- Is the integrated system for the Control & Indicating Equipment (CIE)
- ≥ IP30 CIE ratingManufacturer's Recommendation - -, -
- Functions as the 'Brain' of the Fire Detection & Alarm System (FDAS)
- Provides mass alert & communication to building occupants in the event of an emergencyAS 1670.1:2018, 3.1
Visual Alarm Device - External