Building on Same Allotment
NCC 2022 HP, 9.2.3 (2) (a) NCC 2022 HP, 9.2.3 (3) (a) NCC 2022 HP, 9.2.1 (a) NCC 2022 HP, 9.2.2 NCC 2022 HP, 9.2.5 NCC 2022 HP, 9.2.5 NCC 2022 HP, 9.2.10 Combustible Roof Lights NCC 2022 HP, 9.2.10
≥ 900mm from Property Boundary≤ 20% A rea of Roof required to be non-combustible NCC 2022 HP, 9.2.5 Protection of External Walls NCC 2022 HP, 9.2.5
≥ 900mm maintained distance to Setback, or Separation, or 60/60/60 FRL Construction to[ A ] Setback, or[ B ] Class 10a Wall, or[ C ] Class 1 Wall NCC 2022 HP, 9.2.3 (1) (a) NCC 2022 HP, 9.2.3 (2) NCC 2022 HP, 9.2.3 (3) (b) NCC 2022 HP, 9.2.3 (3) (a) Fire Resisting Wall Construction < 900mm
NCC 2022 HP, 9.2.9 (4) NCC 2022 HP, 9.2.9 (3) NCC 2022 HP, 9.2.9 (3) NCC 2022 HP, 9.2.9 (4) NCC 2022 HP, 9.2.9 (3) (d) Allowable Encroachments
< 900mm NCC 2022 HP, 9.2.9 (3) Utility meters, Light fittings, Antennas Sun blinds, Water tanks, Pergolas ≤ 1m (H) Landings, Open platforms, Access waysNCC 2022 HP, 9.2.9 (4) ≥ 450mm NCC 2022 HP, 9.2.9 (3) (d) Residential fuel tanks, Flues, Pipes Heating or cooling devices NCC 2022 HP, 9.2.3 (4) Window FRL exemption ≥ 600mm from Boundary NCC 2022 HP, 9.2.3 (4)
≤ 1.2m² Bathroom, Laundry or WC ≤ 0.54m² Non-openable rooms Steel framed, Wired Glass, or Hollow Glass Blocks NCC 2022 HP, 9.2.9 (4) Fire Separation Carports
≥ 2 Open Sides[1] ≥ 2/3 Open PerimeterFire Separation Carport RULES NCC 2022 V1 All Building Classes
NCC 2022 HP 9.2.8 [2019: 3.7.2.6]
May 2023
NCC 2022 HP, 9.2.8 NCC 2022 HP, 9.2.8 (b) NCC 2022 HP, 9.2.8 (f) NCC 2022 HP, 9.2.8 (f) (i) NCC 2022 HP, 9.2.8 (f) (ii) NCC 2022 HP, 9.2.8 (c) NCC 2022 HP, 9.2.8 (c) NCC 2022 HP, 9.2.8 (a) Redirecting... (5)