Sliding Fire Door Building Codes & Rules


- Sliding Fire Door : Tools™ simplifies the National Construction Code (NCC) with interactive graphics, including deemed to comply & best practices.


AS 1905.1:2015, 2.4.1

200AS 1905.1:2015, 2.4.1

AS 1905.1:2015, 2.4.1

900AS 1905.1:2015, 2.4.1

Fail Safe Sliding Door

AS 1905.1:2015, 2.4.2

300AS 1905.1:2015, 2.4.2

AS 1905.1:2015, 2.4.2

900AS 1905.1:2015, 2.4.2

Fire Door Track & Bracket

Counter Weight Closer & Cover

AS 1905.1:2015, 2.4.2

Door Directional ArrowAS 1905.1:2015, 2.4.2

  • ≥ 3mm thk recessed or surface mounted
  • At midpoint of the door leaf on both sides

Floor Guide

AS 1905.1:2015, 2.4.1

Recessed Finger Pull or GripAS 1905.1:2015, 2.4.1

  • ≥ 75mm staggered clearance on both door face
  • ≥ 25mm Wide x ≥ 70mm Height x ≥ 20mm Depth
  • ≥ 12mm D inundercut recess finger latch in door direction

AS 1905.1:2015, 6.1.3

Metal TagAS 1905.1:2015, 6.1.3

  • ≥ 50 x ≥ 25mm tags
  • ≈ 1.5m H from FFL
  • Etched, Embossed or Stamped required information

Manufacturer's Requirement

Opening Width + ≥ 200mm

SLIDING DOOR WIDTHManufacturer's Requirement

Opening Width Clearance

NCC 2022 Vol 1, C4D7 (1) (a)

Electromagnetic Hold Open DeviceNCC 2022 Vol 1, C4D7 (1) (a)

  • 20 to 30 seconds fully closed when deactivated in the event of Fire
  • Deactivated when the warning system or fire alarm system is activated by
  • Heat or
  • Smoke detector

Manufacturer's Requirement

≥ 100Manufacturer's Requirement

NCC 2022 Vol 1, C4D7 (1) (d)

Sliding Door SignageNCC 2022 Vol 1, C4D7 (1) (d)

  • ≥ 50mm text height
  • Capital letters in contrast colour background
  • In both sides of the doorway

Door Stop

Wall Bracket

Door Stop

Wall Bracket

Manufacturer's Requirement

≥ 100Manufacturer's Requirement

Speed Control Box & Pulley

AS 1530.4:2014, 7.2.2.2

AS 1905.1:2015, 5.5.5 (a)

Sliding DoorsetAS 1530.4:2014, 7.2.2.2AS 1905.1:2015, 5.5.5 (a)

  • Tested as per AS 1530.4
  • Maximum fire exposure to the Suspension System

Manufacturer's Requirement

Perimeter FirestopManufacturer's Requirement

  • Any additional detail as per Manufacturer's System Requirements

AS 1905.1:2015, 5.5.1 (a)

3AS 1905.1:2015, 5.5.1 (a)

Manufacturer's Recommendation

Sliding Fire Door ApplicationsManufacturer's Recommendation

  • Suitable for larger buildings with heavy foot traffic such
  • Carparks above & below ground
  • Factories & warehouse
  • Shopping centres
  • Medical buildings - Hospitals, aged care facilities, etc.
  • Residential building complexes - Apartments, hotels, units, etc.
  • Educational institutions, universities & colleges

Manufacturer's Requirement

Opening Height + ≥ 100mm

SLIDING DOOR HEIGHTManufacturer's Requirement

AS 1905.1:2015, 2.2

≥ 150AS 1905.1:2015, 2.2

NCC 2022 Vol 1, C4D7 (1) (c)

Audible & Visual AlarmNCC 2022 Vol 1, C4D7 (1) (c)

  • Located near the doorway in each side of the doorway
  • Sufficient intensity of audible warning & red flashing light

Angle Wall Stop

AS 1905.1:2015, 2.2

≥ 100AS 1905.1:2015, 2.2

AS 1905.1:2015, 2.2

≥ 150AS 1905.1:2015, 2.2

AS 1905.1:2015, 5.5.1 (a)

10AS 1905.1:2015, 5.5.1 (a)

Leaf Signage


  • ≥ 20mm tall font, CAPITALISED, in contrasting colour[1]
  • Always visible location


Signage RULES


NCC 2022 V3


Class 2 to 9


NCC 2022 D3D28 [2019 D2.23]


May 2023



NCC 2022 Vol 1, D3D28 (1)

NCC 2022 Vol 1, D3D28 (4)

NCC 2022 Vol 1, D3D28 (2)

NCC 2022 Vol 1, D3D28 (3)

Fixed Locations Based on Fire DoorNCC 2022 Vol 1, D3D28 (4)NCC 2022 Vol 1, D3D28 (2)

  • If auto-closing, on the side facing person seeking egress
  • If with hold open device, on adjacent wall or on both sides of the door
  • If along horizontal exit, on a double swing smoke door, or door leading to open space, on both sides of the door

Signage StatementNCC 2022 Vol 1, D3D28 (3)

  • If auto closing door

FIRE SAFETY DOOR

DO NOT OBSTRUCT

DO NOT KEEP OPEN

  • If door has a hold open device or is a door discharging from a fire -isolated exit

FIRE SAFETY DOOR

DO NOT OBSTRUCT

  • Signage not required for a Class 2, 3 or 4 Sole Occupancy Unit

NCC 2022 Vol 1, D3D28

Threshold


  • Non-combustible material below Door[1]
  • Extends to zone indicated on both sides of the door


Threshold RULES


NCC 2022 V3


All Building Classes


NCC 2022 S12C2 [2019 C3.4:2]


May 2023



AS 1905.1:2015, 2.2

  • Fire Door construction to comply to NCC Specification 12, & AS 1905.1
  • Concrete or other non-combustible materialAS 1905.1:2015, 2.2
  • If a sliding doorset, non-combustible zone must extend
  • ≥ 100mm beyond face of wall, &
  • ≥ 150mm past opening

AS 1905.1:2015, 2.2

  • Non-combustible material below DoorAS 1905.1:2015, 2.2
  • Extends to zone indicated on both sides of the door

Hinged Fire Door

Door Compliance Tagging