AS 1905.1:2015, 2.4.1
AS 1905.1:2015, 2.4.1
Fail Safe Sliding Door
AS 1905.1:2015, 2.4.2
AS 1905.1:2015, 2.4.2
Fire Door Track & Bracket
Counter Weight Closer & Cover
AS 1905.1:2015, 2.4.2
Door Directional ArrowAS 1905.1:2015, 2.4.2
- ≥ 3mm thk recessed or surface mounted
- At midpoint of the door leaf on both sides
AS 1905.1:2015, 2.4.1
Recessed Finger Pull or GripAS 1905.1:2015, 2.4.1
- ≥ 75mm staggered clearance on both door face
- ≥ 25mm Wide x ≥ 70mm Height x ≥ 20mm Depth
- ≥ 12mm D in 5° undercut recess finger latch in door direction
AS 1905.1:2015, 6.1.3
Metal TagAS 1905.1:2015, 6.1.3
- ≥ 50 x ≥ 25mm tags
- ≈ 1.5m H from FFL
- Etched, Embossed or Stamped required information
Manufacturer's Requirement
NCC 2022 Vol 1, C4D7 (1) (a)
Electromagnetic Hold Open DeviceNCC 2022 Vol 1, C4D7 (1) (a)
- 20 to 30 seconds fully closed when deactivated in the event of Fire
- Deactivated when the warning system or fire alarm system is activated by
- Heat or
- Smoke detector
Manufacturer's Requirement
NCC 2022 Vol 1, C4D7 (1) (d)
Sliding Door SignageNCC 2022 Vol 1, C4D7 (1) (d)
- ≥ 50mm text height
- Capital letters in contrast colour background
- In both sides of the doorway
Manufacturer's Requirement
Speed Control Box & Pulley
AS 1530.4:2014, 7.2.2.2
AS 1905.1:2015, 5.5.5 (a)
Manufacturer's Requirement
AS 1905.1:2015, 5.5.1 (a)
Manufacturer's Recommendation
Sliding Fire Door ApplicationsManufacturer's Recommendation
- Suitable for larger buildings with heavy foot traffic such
- Carparks above & below ground
- Factories & warehouse
- Shopping centres
- Medical buildings - Hospitals, aged care facilities, etc.
- Residential building complexes - Apartments, hotels, units, etc.
- Educational institutions, universities & colleges
Manufacturer's Requirement
AS 1905.1:2015, 2.2
NCC 2022 Vol 1, C4D7 (1) (c)
Audible & Visual AlarmNCC 2022 Vol 1, C4D7 (1) (c)
- Located near the doorway in each side of the doorway
- Sufficient intensity of audible warning & red flashing light
AS 1905.1:2015, 2.2
AS 1905.1:2015, 2.2
AS 1905.1:2015, 5.5.1 (a)
Leaf Signage
- ≥ 20mm tall font, CAPITALISED, in contrasting colour[1]
- Always visible location
Signage RULES
NCC 2022 V3
Class 2 to 9
NCC 2022 D3D28 [2019 D2.23]
May 2023
NCC 2022 Vol 1, D3D28 (1)
NCC 2022 Vol 1, D3D28 (4)
NCC 2022 Vol 1, D3D28 (2)
NCC 2022 Vol 1, D3D28 (3)
Fixed Locations Based on Fire DoorNCC 2022 Vol 1, D3D28 (4)NCC 2022 Vol 1, D3D28 (2)
- If auto-closing, on the side facing person seeking egress
- If with hold open device, on adjacent wall or on both sides of the door
- If along horizontal exit, on a double swing smoke door, or door leading to open space, on both sides of the door
Signage StatementNCC 2022 Vol 1, D3D28 (3)
FIRE SAFETY DOOR
DO NOT OBSTRUCT
DO NOT KEEP OPEN
- If door has a hold open device or is a door discharging from a fire -isolated exit
FIRE SAFETY DOOR
DO NOT OBSTRUCT
- Signage not required for a Class 2, 3 or 4 Sole Occupancy Unit
NCC 2022 Vol 1, D3D28
Threshold
- Non-combustible material below Door[1]
- Extends to zone indicated on both sides of the door
Threshold RULES
NCC 2022 V3
All Building Classes
NCC 2022 S12C2 [2019 C3.4:2]
May 2023
AS 1905.1:2015, 2.2
- Fire Door construction to comply to NCC Specification 12, & AS 1905.1
- Concrete or other non-combustible materialAS 1905.1:2015, 2.2
- If a sliding doorset, non-combustible zone must extend
- ≥ 100mm beyond face of wall, &
- ≥ 150mm past opening
AS 1905.1:2015, 2.2
- Non-combustible material below DoorAS 1905.1:2015, 2.2
- Extends to zone indicated on both sides of the door
Hinged Fire Door
Door Compliance Tagging