Smoke Alarm Building Codes & Rules


- Discover essential smoke alarm insights for Class 1a & 1b buildings. Learn about types, placement, and maintenance responsibilities. Tools™ simplifies the NCC


Types of Alarms


  • Photoelectric (smoke) near Bedrooms
  • Ionisation (smoke) near bedrooms, if susceptible to false alarms from cooking
  • Heat type in Garages, commercial kitchens


Fire Alarm TYPES


NCC 2022 V1


  • Photoelectric (smoke) near Bedrooms
  • Ionisation (smoke) near bedrooms, if susceptible to false alarms from cooking
  • Heat type in Garages, commercial kitchens

NCC 2022 HP, 9.5.4 (a) (ii)

≥ 500NCC 2022 HP, 9.5.4 (a) (ii)

AS 1670.1:2018, 4.1.4

≥ 400AS 1670.1:2018, 4.1.4

AS 1670.1:2018, 5.1.4

≥ 400AS 1670.1:2018, 5.1.4

NCC 2022 HP, 9.5.4 (a) (i)

≥ 300NCC 2022 HP, 9.5.4 (a) (i)

NCC 2022 HP, 9.5.4 (b)

≥ 300NCC 2022 HP, 9.5.4 (b)

Smoke Alarm

Raked Ceiling

Fan

NCC 2022 HP, 9.5.4 (b)

≥ 500NCC 2022 HP, 9.5.4 (b)

NCC 2022 HP, 9.5.4 (b)

Wall InstallationNCC 2022 HP, 9.5.4 (b)

  • Only if ceiling space unavailable
  • Ensure alarm is suitable for wall mounting

A/C

AS 1670.1:2018, 3.27.1 (b)

≥ 300AS 1670.1:2018, 3.27.1 (b)

Prohibited Location

NCC 2022 HP, 9.5.4 (a) (ii)

≥ 1.5mNCC 2022 HP, 9.5.4 (a) (ii)

NCC 2022 HP, 9.5.4

Exposed JoistsNCC 2022 HP, 9.5.4

Ceiling

Wall

AS 1670.1:2018, 5.1.4

≥ 900AS 1670.1:2018, 5.1.4

Light

Adjoining Building

Locating Smoke Alarms



Location RULES


NCC 2022 V1


All Building Classes


NCC 2022 Part 9.5.1


May 2023



NCC 2022 HP, 9.5.1

  • The location of smoke alarms is intended to detect smoke before it reaches the sleeping occupants of a building giving enough time for evacuationNCC 2022 HP, 9.5.1
  • Class 1a
  • ≥ 1 per storey if not containing a bedroom
  • In every hallway / corridor associated with a bedroom, or
  • Other location separating bedroom(s) to rest of building
  • All must be on mains power & be interconnected
  • Class 1b
  • ≥ 1 per storey if not containing a bedroom
  • In every bedroom
  • In every hallway / corridor associated with a bedroom, or
  • Other location separating bedroom(s) to rest of building
  • All must be on mains power & be interconnected
  • Activation of any Alarm must trigger Evacuation Lighting to illuminate pathways from any Bedroom to an Exit Door

Smoke Alarm RULES NSW


NCC 2022 V1


All Building Classes


NCC 2022 Part 9.5.1


May 2023



NCC 2022 HP, 9.5.1 NSW

  • Additional RequirementsNCC 2022 HP, 9.5.1 NSW
  • Heat alarm installed in a Class 10a private garage if beneath a non-associated Class 1a dwelling
  • Heat alarm must be interlinked with the alarm(s) of the dwelling above
  • Connected to consumer mains power where available
  • Interconnected when more than 1 alarm

Location BEST PRACTICE


NCC 2022 V1


Responsibilities


  • Who is responsible for installation & maintenance
  • Builder
  • Owner
  • Landlord
  • Tenant


Install & Maintenance RESPONSIBILITIES


NCC 2022 V1


  • Who is responsible for installation & maintenance
  • Builder
  • Owner
  • Landlord
  • Tenant

Industry Recommendation

Smoke Alarm RequirementsIndustry Recommendation

  • There are many varying requirements depending on a building's age for Every State & Territory
  • Fire Safety Legislation may call for extra work above what is required by the NCC in some states
  • Applies retroactively to attributes that already exist in the property
  • Consult professionals to assist in designing system to your specific projects

Heat Detector