- Discover essential smoke alarm insights for Class 1a & 1b buildings. Learn about types, placement, and maintenance responsibilities. Tools™ simplifies the NCC
Types of Alarms
Photoelectric (smoke) near Bedrooms
Ionisation (smoke) near bedrooms, if susceptible to false alarms from cooking
Heat type in Garages, commercial kitchens
Fire Alarm TYPES
NCC 2022 V1
Photoelectric (smoke) near Bedrooms
Ionisation (smoke) near bedrooms, if susceptible to false alarms from cooking
The location of smoke alarms is intended to detect smoke before it reaches the sleeping occupants of a buildinggiving enough time for evacuationNCC 2022 HP, 9.5.1
Class 1a
≥ 1 per storey if not containing a bedroom
In every hallway / corridor associated with a bedroom, or
Other location separating bedroom(s) to rest of building
All must be on mains power & be interconnected
Class 1b
≥ 1 per storey if not containing a bedroom
In every bedroom
In every hallway / corridor associated with a bedroom, or
Other location separating bedroom(s) to rest of building
All must be on mains power & be interconnected
Activation of any Alarm must trigger Evacuation Lighting to illuminate pathways from any Bedroom to an Exit Door