R ≤ 4.2mAS 2118.1:2017, 5.2
Rows
Prohibited Use of PipingAS 2118.1:2017, 7.9.8
Ordinary Hazard
Ordinary Hazard
Spacing
Ordinary Hazard
Deflectors parallel to Ceiling
Raked Ceiling
Open-joist Ceiling
Ordinary Hazard
S x R
3S / 4AS 2118.1:2017, 5.2
Spacing
To Deflectors
3S / 4AS 2118.1:2017, 5.2
Clearance Below Sprinkler HeadsAS 2118.1:2017, 5.7.7
Minimum SpacingAS 2118.1:2017, 5.3
Sprinkler Spacing measured horizontallyAS 2118.1:2017, 5.5.3 (b)
Sprinkler Spacing measured horizontallyAS 2118.1:2017, 5.5.3 (b)
All Building Classes
NCC 2022 C1V3, Specification 17, Specification 18
[2019 CV3, Spec E1.5,Spec E1.5a]
May 2022
Class 2 to 9
NCC 2022 Vol 1, S17C2 [2019 E1.5: 1]
May 2023
S / 2AS 2118.1:2017, 5.2
Class 2 to 9
NCC 2022 Vol 1, S17C2 [2019 E1.5: 1]
May 2023
S ≤ 4.6mAS 2118.1:2017, 5.2
S / 4AS 2118.1:2017, 5.2
S / 2AS 2118.1:2017, 5.2
S ≤ 4.6mAS 2118.1:2017, 5.2
R / 2AS 2118.1:2017, 5.2
S / 4AS 2118.1:2017, 5.2