Staggered Spacing (Fire Sprinklers) Building Codes & Rules


- Fire Sprinkler Staggered Spacing Tools™ simplifies the National Construction Code (NCC) with interactive graphics, including deemed to comply & best practices.


AS 2118.1:2017, 5.2

SAS 2118.1:2017, 5.2

AS 2118.1:2017, 5.2

R ≤ 4.2mAS 2118.1:2017, 5.2

AS 2118.1:2017, 5.2

12m²AS 2118.1:2017, 5.2

Rows

AS 2118.1:2017, 7.9.8

Prohibited Use of PipingAS 2118.1:2017, 7.9.8

  • As earthing to an electrical system
  • As a support to other services

Ordinary Hazard

Ordinary Hazard

Spacing

Ordinary Hazard

Deflectors parallel to Ceiling

Raked Ceiling

Open-joist Ceiling

Ordinary Hazard

S x R

AS 2118.1:2017, 5.2

SAS 2118.1:2017, 5.2

AS 2118.1:2017, 5.2

3S / 4AS 2118.1:2017, 5.2

Spacing

To Deflectors

AS 2118.1:2017, 5.2

3S / 4AS 2118.1:2017, 5.2

AS 2118.1:2017, 5.7.7

Clearance Below Sprinkler HeadsAS 2118.1:2017, 5.7.7

  • ≥ 900mm for High Hazard Storage
  • ≥ 100mm for rolling storage cabinets
  • ≥ 250mm for washrooms & toilet cubicles
  • ≥ 500mm for general cases
  • ≤ 3.0m room height
  • Required clearance maintained on sloping ceiling or roofs

AS 2118.1:2017, 5.3

Minimum SpacingAS 2118.1:2017, 5.3

  •  ≥ 2m Standard Coverage, or
  • ≥ 2.4m Extended Coverage Type
  • Baffles allow spacing to be reduced
  • ≥ 200 (W) x 150mm (D)
  • ≤ 1/2 design spacing from Sprinkler

AS 2118.1:2017, 5.5.3 (b)

Sprinkler Spacing measured horizontallyAS 2118.1:2017, 5.5.3 (b)

AS 2118.1:2017, 5.5.3 (b)

Sprinkler Spacing measured horizontallyAS 2118.1:2017, 5.5.3 (b)

AS 2118.1:2017, 5.5.3 (h)

≤ 150AS 2118.1:2017, 5.5.3 (h)

Sprinklers Near Column


  • Applies on column face both directions


Sprinklers Near Columns


NCC 2022 V3


All Building Classes


NCC 2022 C1V3, Specification 17, Specification 18

[2019 CV3, Spec E1.5,Spec E1.5a]



May 2022



AS 2118.1:2017, 5.7.4

AS 2118.1:2017, 5.1

  • Applies on column face both directions

Shadowed Areas


  • ≤ 1.4m² per Sprinkler


Shadowed Areas RULES


NCC 2022 V2


Class 2 to 9


NCC 2022 Vol 1, S17C2 [2019 E1.5: 1]



May 2023



NCC 2022 Vol 1, S17C2

NCC 2022 Vol 1, S17C1

AS 2118.1:2017, 1

AS 2118.1:2017, 5.7.10

  • ≤ 1.4m² per Sprinkler

AS 2118.1:2017, 5.2

S / 2AS 2118.1:2017, 5.2

Cupboards & Wardrobes


  • Sprinklers not required[1]
  • ≤ 2.5m² floor area
  • No flammable liquid stored


Cupboards RULES


NCC 2022 V2


Class 2 to 9


NCC 2022 Vol 1, S17C2 [2019 E1.5: 1]


May 2023



NCC 2022 Vol 1, S17C2

NCC 2022 Vol 1, S17C1

AS 2118.1:2017, 1

AS 2118.1:2017, 5.9.17

  • Fire Sprinkler Systems as per NCCNCC 2022 Vol 1, S17C2
  • Requirements for Fire Sprinklers within Cupboards to NCCNCC 2022 Vol 1, S17C1 & Australian StandardsAS 2118.1:2017, 1
  • Sprinklers within Cupboards are not required ifAS 2118.1:2017, 5.9.17
  • ≤ 2.5m² floor area
  • Non-combustible Walls & Ceiling
  • Not used for storage of flammable liquids
  • Sprinklers in the adjacent area positioned to cover the unprotected area
  • Obstructions are not taken into consideration in this scenario

AS 2118.1:2017, 5.9.17

AS 2118.1:2017, 5.2

AS 2118.1:2017, 5.2

AS 2118.1:2017, 5.2

AS 2118.1:2017, 5.2

AS 2118.1:2017, 5.2

AS 2118.1:2017, 5.2