Prohibited Use of PipingAS 2118.1:2017, 7.9.8
Sprinkler Spacing measured horizontallyAS 2118.1:2017, 5.5.3 (b)
Raked Ceiling
High Hazard
Row Centres
Spacing
S x R
Deflectors parallel to Ceiling
≤ 12m²AS 2118.1:2017, 5.1
R / 2AS 2118.1:2017, 5.1
S / 2AS 2118.1:2017, 5.1
Ordinary Hazard
Sprinkler near Wall
Ordinary Hazard
Light Hazard
Open-joist Ceiling
Minimum SpacingAS 2118.1:2017, 5.3
Distance from Walls
High Hazard
S ≤ 4.2mAS 2118.1:2017, 5.1
S ≤ 4.6mAS 2118.1:2017, 5.1
Class 2 to 9
NCC 2022 Vol 1, S17C2 [2019 E1.5: 1]
May 2023
Class 2 to 9
NCC 2022 Vol 1, S17C2 [2019 E1.5: 1]
May 2023
R / 2AS 2118.1:2017, 5.1
Clearance Below Sprinkler HeadsAS 2118.1:2017, 5.7.7
All Building Classes
NCC 2022 C1V3, Specification 17, Specification 18
[2019 CV3, Spec E1.5,Spec E1.5a]
May 2022
To Deflectors
≤ 21m²AS 2118.1:2017, 5.1
Light Hazard
R ≤ 3.7mAS 2118.1:2017, 5.1
Sprinkler Spacing measured horizontallyAS 2118.1:2017, 5.5.3 (b)
≤ 9m²AS 2118.1:2017, 5.1
≥ 100AS 2118.1:2017, 5.4