Fire-stopping Penetrations (Benchmark) Building Codes & Rules


- Protect lives! Learn fire-stopping for holes in fire barriers. Tools™ simplifies NCC with interactive graphics. Get expert tips for proper sealing & compliance.


Type of Construction

Masonry & Concrete Wall Penetrations

AAC Wall Penetrations

Adjoining Building

Site Tools

Plumbing Overview

Insulated Spandrel

Insulated Spandrel

Concrete Slab

Concrete Slab

Fire Barrier

Duct Wrap

Fire Sleeves / Fire Coat

Continuously Lagged Metal Pipe

Vertical Cavity Barrier Firestop

Floor Fire Block

HVAC

Fire Damper

Fire Damper Installation

Multi-Service Transit Box

Mixed Services Firestopping

Fire Rated

Service Riser Cupboard

Fire Pillow

with Mastic

Sealant on Gaps

Horizontal Cavity Barrier - Curtain Wall Gap

Insulated Spandrel

Head-of-Wall Firestop

Floor Movement Joint Firestop

Vertical Perimeter Barrier Firestop

Metal Pipe Penetrations


  • Precisely made, cut, or drilled[1]
  • Gaps must be fire-stopped[2]


Metal Pipe Penetrations RULES


NCC 2022 V3


Class 2 to 9


NCC 2022 S13C3, S13C7 [2019 SC3.15.3, SC3.15.7]


May 2023



NCC 2022 Vol 1, S13C3 (1)

NCC 2022 Vol 1, S13C3 (2)

  • Non-liquid Filled Metal Pipe SystemNCC 2022 Vol 1, S13C3 (1)
  • ≥ 100mm Ø x ≥ 2m L from penetration distance to any combustible material
  • Must have a pipe thickness of
  • ≥ 1mm for Copper Alloy or Stainless Steel
  • ≥ 2mm for Cast Iron or Steel (except stainless steel)
  • Single Metal Pipe PenetrationNCC 2022 Vol 1, S13C3 (2)
  • ≥ 200mm distance from other Service Penetrations
  • Precisely made, cut, or drilled
  • Always refer to Manufacturer's Requirements for Fire-stopping Products

NCC 2022 Vol 1, S13C3 (2) (a)

NCC 2022 Vol 1, S13C3 (4)

Fire Damper Types & Inspection

Concrete Floor Penetrations

Fire-stop


  • Must be Concrete, High-temperature Ceramic Fibre or another material that can withstand ≥ 1120°C[1]


Fire-stopping RULES


NCC 2022 V2


Class 2 to 9


NCC 2022 S13C7 [2019 SC3.15.7]


May 2023



NCC 2022 Vol 1, S13C7 (1)

NCC 2022 Vol 1, S13C7 (3)

  • MaterialNCC 2022 Vol 1, S13C7 (1)
  • Concrete, High-temperature Ceramic Fibre, or another material that can withstand ≥ 1120°C
  • Tested as per Standard, and
  • Passed the required FRL, or
  • Resist the incipient spread of fire
  • Hollow Wall ConstructionNCC 2022 Vol 1, S13C7 (3)
  • ≥ 25mm thk Fire-stop around Service Pipe Penetrations
  • Restrained from moving
  • Must not detach from linked surfaces of the service, wall, floor, or ceiling

NCC 2022 Vol 1, S13C7 (1)

Fire Compartmentation