NCC 2022 Vol 1, S13C6 (a) (ii) Electrical Switch & Outlet Penetrations
NCC 2022 Vol 1, S13C6 (a) Horizontal Cavity Barrier - Curtain Wall Gap
Multi-Service Transit Box
Mixed Services Firestopping
Vertical Perimeter Barrier Firestop
Floor Movement Joint Firestop
Wall Movement Joint Firestop
NCC 2022 Vol 1, S13C6 (a) Wire & Cable Penetrations
Fire-stop between Service & the Wall, Floor, or Ceiling[1] Wire & Cable Penetration RULES NCC 2022 V7 Class 2 to 9
NCC 2022 S13C5, S13C7, C4D15(c)(iii)
[2019 C3.15.5, C3.15.7]
May 2023
NCC 2022 Vol 1, S13C5 (a) NCC 2022 Vol 1, S13C5 (b) ≥ 50mm Penetration distance to other Services NCC 2022 Vol 1, S13C5 (a) Opening cross-sectional areaNCC 2022 Vol 1, S13C5 (b) ≤ 2000mm² Single Cable Penetration with ≤ 15mm gap between Cable and Penetration edge≤ 500mm² any other caseAlways refer to Manufacturer's Requirements for Fire-stopping Products NCC 2022 Vol 1, S13C5 AAC Wall Penetrations
Concrete Floor Penetrations
Site Tools
Plumbing Overview
Sealant Joint
Masonry & Concrete Wall Penetrations
Adjoining Building
Fire Damper Installation
Type of Construction
Fire Compartmentation
Fire-stop
Must be Concrete, High-temperature Ceramic Fibre or another material that can withstand ≥ 1120°C [1] Fire-stopping RULES NCC 2022 V2 Class 2 to 9
NCC 2022 S13C7 [2019 SC3.15.7]
May 2023
NCC 2022 Vol 1, S13C7 (1) NCC 2022 Vol 1, S13C7 (3) MaterialNCC 2022 Vol 1, S13C7 (1) Concrete, High-temperature Ceramic Fibre, or another material that can withstand ≥ 1120°C Tested as per Standard, and Passed the required FRL , or Resist the incipient spread of fire Hollow Wall Construction NCC 2022 Vol 1, S13C7 (3) ≥ 25mm thk Fire-stop around Service Pipe PenetrationsRestrained from moving Must not detach from linked surfaces of the service, wall, floor, or ceiling NCC 2022 Vol 1, S13C7 (1) Redirecting... (5)