Fire Hydrant Booster Assembly
AS 2419.1:2021, 3.2.2.2 (c)
AS 2419.1:2021, 3.2.2.2 (c)
NCC 2022 Vol 1, D3D26 (1) (a)
AS 1905.1:2015, 5.5.2
NCC 2022 Vol 1, D3D16
Allowed Step & Ramp on ThresholdsNCC 2022 Vol 1, D3D16
- Doorways opening to
- An open space
- External stair landing
- External balcony
- Door sill ≤ 190mm above FFL where doorway opens
- Class 9a in patient care areas of a health-care building
- ≤ 25mm Door Sill height above FFL where doorway opens
- Class 9c in Residential use areas
- ≥ 1:8 gradient ramp with ≤ 25mm (H)
- Accessible Buildings where
- Doorways open to an open space
- Threshold or Step Ramps are compliant to AS 1428.1
AS 2419.1:2021, 3.2.2.2 (a)
AS 2419.1:2021, 3.2.2.1 (c)
Tools™ Best Practice
AS 2419.1:2021, H.2
AS 1905.1:2015, 5.5.1
AS 1905.1:2015, 5.5.2
AS 1905.1:2015, 5.5.1
AS 2419.1:2021, 3.2.2.2 (b)
AS 1905.1:2015, 2.3.2.2
Door Operational ForceAS 1905.1:2015, 2.3.2.2
- Apply force 700mm from pivot centre of the door
- ≤ 2 N force
- From closed position to full open door position
- Back to the strike
- ≤ 20 N force
- Door leaf in fully latched position
AS 1905.1:2015, 5.5.1
AS 1905.1:2015, 5.5.2
AS 1905.1:2015, 5.5.2
AS 1905.1:2015, 5.5.2
AS 1905.1:2015, 5.5.2
AS 1905.1:2015, 5.5.2
AS 1905.1:2015, 5.5.2
AS 1905.1:2015, 5.5.2
AS 1905.1:2015, 5.5.1
AS 1905.1:2015, 5.3
Metal Door Frames in Masonry WallsAS 1905.1:2015, 5.3
- ≥ 75mm (D) corrosion-resistant Metal Anchors fixed to mortar joints
- ≤ 400mm vertical spacing
- Fill jamb cavities completely with
- Cement mortar, non-shrink grout, or concrete
- At ≥ 1000°C fusion temperature
- Comply to AS 3600 or AS 3700
Plumbing Overview
Site Tools
Seals
- To full perimeter of Door frame[1]
- Drop seals at floor
Door Seal RULES
NCC 2022 V2
All Building Classes
NCC 2022 S12C2 [2019 C3.4:2]
May 2023
NCC 2022 Vol 1, S12C2 (a)
NCC 2022 Vol 1, S14C2 (f)
NCC 2022 Vol 1, S12C4 (c)
NCC 2022 Vol 1, S12C2 (a)
Fire Hose Reel
Door Leaf Clearances
- Leaf Perimeter[1]
- ≤ 3mm gap at head & jamb
- 3 to 10mm gap at threshold
- Face of Leaf to Door Stop Rebate[2]
- ≤ 3mm mean (μ) clearance
- ≤ 5mm allowed for minor warping
How to Measure
NCC 2022 V2
All Building Classes
NCC 2022 S12C2 [2019 C3.4:2]
May 2023
NCC 2022 Vol 1, S12C2 (a)
AS 1905.1:2015, 5.5.1
AS 1905.1:2015, 5.5.3
- Fire Door construction to comply to NCCNCC 2022 Vol 1, S12C2 (a)
- Leaf PerimeterAS 1905.1:2015, 5.5.1
- 2 locations near corners of leaf
- Plus mid location near latch & hinge
- 3mm feeler gauge should tightly fit or not be able to enter gap between leaf & reveal
- 10mm feeler gauge should not fit under leaf
- Face of Leaf to Door Stop RebateAS 1905.1:2015, 5.5.3
- 3mm feeler gauge should tightly fit or not be able to enter gap between leaf & reveal in majority of locations
- 5mm feeler gauge no more than a tight fit in any location
Best Practice
NCC 2022 V1
AS 1905.1:2015, 5.5.1
AS 1905.1:2015, 5.5.3
Magnetic Door Hold Open
- Fail Safe Device connected to Fire Alarm System[1][2]
- Holds door open & releases via remote switch & Fire Alarm System activation
- Release Button to allow manual closing when not activated by fire system
Hold Open RULES
NCC 2022 V3
All Building Classes
NCC 2022 S12C2 [2019 C3.4:2]
May 2023
NCC 2022 Vol 1, S12C2 (a)
AS 1905.1:2015, 2.1.7
AS 1905.1:2015, 2.1.7
Industry Recommendation
- Fail Safe Device connected to Fire Alarm SystemAS 1905.1:2015, 2.1.7Industry Recommendation
- Holds door open & releases via remote switch & Fire Alarm System activation
- Release Button to allow manual closing when not activated by fire system
Tagging
Door Stop
- Locate at latch end to prevent damage to leaf & hardware[1]
Travel Limiting Device RULES
NCC 2022 V1
All Building Classes
NCC 2022 S12C2 [2019 C3.4:2]
May 2023
NCC 2022 Vol 1, S12C2 (a)
AS 1905.1:2015, 5.6.4
AS 1905.1:2015, 5.6.4
AS 1905.1:2015, 5.6.4
Sliding Fire Door
Closer
- Close & latch Door from any angle[1]
- Back checking set ≥ 70° open to last 5°[2]
Door Closer RULES
NCC 2022 V3
All Building Classes
NCC 2022 S12C2 [2019 C3.4:2]
May 2023
NCC 2022 Vol 1, S12C2 (a)
AS 1905.1:2015, 2.3.4
AS 1905.1:2015, 2.1.4.2
- Fire Door construction to comply to NCCNCC 2022 Vol 1, S12C2 (a)
- Ensure the closer is AS 1905.1 compliant
- Pressure ReliefAS 1905.1:2015, 2.3.4
- Must have a vent plug fused under 100°C heat
- Above oil level inside hydraulic chamber
- Self-latch MechanismAS 1905.1:2015, 2.1.4.2
- Self-latching bolt to engage with striking plate when closed
- Remain closed when forces are applied from the opening direction
- No hardware or fittings to impede self-latching mechanism
AS 1905.1:2015, 2.3.5
AS 1905.1:2015, 2.1.4.3
Exit Door Clearances
- ≥ 1.98m unobstructed Door height[1]
- Door width to be 250mm less than the required unobstructed Exit width[2]
Door Clearances RULES
NCC 2022 V2
Class 2 to 9
NCC 2022 D2D7 to D2D11 [2019 D1.6]
May 2023
NCC 2022 Vol 1, D2D7
NCC 2022 Vol 1, D2D9
NCC 2022 Vol 1, D2D9 (a)
NCC 2022 Vol 1, D2D9 (b)
NCC 2022 Vol 1, D2D9 (d)
Door WidthNCC 2022 Vol 1, D2D9
- Dependent on path of travel & exit width
- Door width = Required unobstructed exit width - 250mm
- Width increases where width of unobstructed exit > 1m
- No requirements if access is only to a sanitary compartment or bathroom
Patient Care Area
- Where patients are transported in bed, the width shall beNCC 2022 Vol 1, D2D9 (a)
- ≥ 1.2m in a corridor < 2.2m wide, or
- ≥ 1.07m in a corridor ≥ 2.2m wide, or
- ≥ 800mm for a Double Door leaf (not necessarily a fire or smoke door) with one leaf fixed but readily openable
- ≥ 1.25m for Fire Doors separating two parts of a buildingNCC 2022 Vol 1, D2D9 (b)
Class 9cNCC 2022 Vol 1, D2D9 (d)
- ≥ 870mm for Doors in residential use area, &
- ≥ 800mm for Doors in non-residential use area
- ≥ 1.07m for Doors opening from public corridors to SOU
NCC 2022 Vol 1, D2D7
NCC 2022 Vol 1, D2D9 (c)
Electrified Latch Locks
- ≤ 15 N force applied to latch handle to open[1]
- Fail Safe Device connected to Fire Alarm System[2]
- Self-latching mechanism able to self-close from any position
- Escape side handle to be openable without a key (exceptions apply)
Fire Door Lock HEIGHTS
NCC 2022 V2
All Building Classes
NCC 2022 D3D26 [2019: D2.21]
May 2023
NCC 2022 Vol 1, D3D26 (6 VIC)
AS 1428.1:2009, 13.5.3 (a)
AS 1428.1:2009, 13.5.3 (b)
Panic Hardware RULES
NCC 2022 V2
All Building Classes
NCC 2022 D3D26(1)(b)
May 2023
NCC 2022 Vol 1, D3D26 (1) (b)
NCC 2022 Vol 1, D3D26
- Latch operation of Panic Hardware (Crash Bars or Push Bars)NCC 2022 Vol 1, D3D26 (1) (b)
- 900 to 1.2m above FFLNCC 2022 Vol 1, D3D26
- Single hand pushing action
- Provides fast & easy egress in an emergency
- Necessary to reduce risk of "Crowd Crush"
- The uncontrolled volume of people surging against an exit door during an emergency
Latch MATERIALS
NCC 2022 V3
All Building Classes
NCC 2022 S12C2 [2019 C3.4:2]
May 2023
NCC 2022 Vol 1, S12C2 (a)
AS 1905.1:2015, 2.3.3
AS 1905.1:2015, 2.3.6
Industry Recommendation
- ≤ 15 N force applied to latch handle to openAS 1905.1:2015, 2.3.6
- Fail Safe Device connected to Fire Alarm SystemIndustry Recommendation
- Self-latching mechanism able to self-close from any position
- Escape side handle to be openable without a key (exceptions apply)
Door Swing
- Door shall swing in the direction of egress, or[1]
- ≤ 500mm encroachment into required width[2]
Door Swing RULES
NCC 2022 V2
All Building Classes
NCC 2022 S12C2, D3D25 [2019 C3.4:2, D2.20]
May 2023
NCC 2022 Vol 1, S12C2 (a)
NCC 2022 Vol 1, D3D25
NCC 2022 Vol 1, D3D25 (1) (a) (i)
NCC 2022 Vol 1, D3D25 (1) (a) (ii)
NCC 2022 Vol 1, D3D25
NCC 2022 Vol 1, D3D25 (1) (a) (i)
Signage
- ≥ 20mm tall font, CAPITALISED, in contrasting colour[1]
- Always visible location
Signage RULES
NCC 2022 V1
Class 2 to 9
NCC 2022 D3D28 [2019 D2.23]
May 2023
NCC 2022 Vol 1, D3D28 (1)
NCC 2022 Vol 1, D3D28 (4)
NCC 2022 Vol 1, D3D28 (2)
NCC 2022 Vol 1, D3D28 (3)
FIRE SAFETY DOOR
DO NOT OBSTRUCT
DO NOT KEEP OPEN
- If door has a hold open device or is a door discharging from a fire -isolated exit
FIRE SAFETY DOOR
DO NOT OBSTRUCT
- Signage not required for a Class 2, 3 or 4 Sole Occupancy Unit
NCC 2022 Vol 1, D3D28
Fail Safe Hinged Door Devices
Vision Panels
Vision Panel RULES
NCC 2022 V1
All Building Classes
NCC 2022 S12C2 [2019 C3.4]
May 2023
AS 1905.1:2015, 2.5
NCC 2022 Vol 1, S12C2 (a)
- Fire Door construction to comply to NCCAS 1905.1:2015, 2.5
- Allowed on Fire DoorNCC 2022 Vol 1, S12C2 (a)
- Successfully assessed to AS 1530.4
- Opening shall not overstep on door leaf structural framework
- If ≥ 0.065m² size for each Panel
- Deem radiation & insulation specifications to AS 1530.4
AS 1905.1:2015, 2.5