Formwork Finish Classes (Concrete) Building Codes & Rules


- Concrete Surface Finish Classes Tools™ simplifies the National Construction Code (NCC) with interactive graphics, including deemed to comply & best practices.


Straight Edge (a - b)

AS 3610.1:2018, 3.3.5.2

10 to 15mAS 3610.1:2018, 3.3.5.2

AS 3610.1:2018, Figure 3.3.5.2 (D)

1.25mAS 3610.1:2018, Figure 3.3.5.2 (D)

AS 3610.1:2018, Figure 3.3.5.2 (D)

300AS 3610.1:2018, Figure 3.3.5.2 (D)

AS 3610.1:2018, 3.3.5.2 (c)

10mAS 3610.1:2018, 3.3.5.2 (c)

AS 3610.1:2018, 3.3.5.2 (c)

5mAS 3610.1:2018, 3.3.5.2 (c)

AS 3610.1:2018, 3.3.5.2 (d)

300AS 3610.1:2018, 3.3.5.2 (d)

AS 3610.1:2018, 3.3.5.2 (c)

10mAS 3610.1:2018, 3.3.5.2 (c)

AS 3610.1:2018, 3.3.3.2

≥ 2mAS 3610.1:2018, 3.3.3.2

AS 3610.1:2018, Figure 3.3.5.2 (D)

1.25mAS 3610.1:2018, Figure 3.3.5.2 (D)

AS 3610.1:2018, Figure 3.3.5.2 (D)

1.25mAS 3610.1:2018, Figure 3.3.5.2 (D)

Straightedge

AS 3610.1:2018, Figure 3.3.5.2 (A)

bAS 3610.1:2018, Figure 3.3.5.2 (A)

AS 3610.1:2018, 3.3.5.2 (d)

Out of Plumb - Rectangular ColumnAS 3610.1:2018, 3.3.5.2 (d)

  • 300mm plumb vertical distance from top & bottom surface
  • ≥ 2 readings on adjacent faces

AS 3610.1:2018, Figure 3.3.5.2 (C)

fAS 3610.1:2018, Figure 3.3.5.2 (C)

AS 3610.1:2018, Figure 3.3.5.2 (C)

fAS 3610.1:2018, Figure 3.3.5.2 (C)

AS 3610.1:2018, Figure 3.3.5.2 (C)

fAS 3610.1:2018, Figure 3.3.5.2 (C)

AS 3610.1:2018, 3.3.5.2 (d)

300AS 3610.1:2018, 3.3.5.2 (d)

AS 3610.1:2018, 3.3.5.2 (d)

300AS 3610.1:2018, 3.3.5.2 (d)

AS 3610.1:2018, Figure 3.3.5.2 (B)

sAS 3610.1:2018, Figure 3.3.5.2 (B)

AS 3610.1:2018, Figure 3.3.5.2 (D)

1.25mAS 3610.1:2018, Figure 3.3.5.2 (D)

Concealed Cupboard

AS 3610.1:2018, Figure 3.3.5.2 (A)

aAS 3610.1:2018, Figure 3.3.5.2 (A)

Straightedge

AS 3610.1:2018, 3.3.4.2

≥ 300AS 3610.1:2018, 3.3.4.2

AS 3610.1:2018, Figure 3.3.5.2 (D)

300AS 3610.1:2018, Figure 3.3.5.2 (D)

Component Length

AS 3610.1:2018, Figure 3.3.5.2 (D)

1.25mAS 3610.1:2018, Figure 3.3.5.2 (D)

AS 3610.1:2018, Figure 3.3.5.2 (C)

fAS 3610.1:2018, Figure 3.3.5.2 (C)

AS 3610.1:2018, 3.3.5.2 (d)

300AS 3610.1:2018, 3.3.5.2 (d)

AS 3610.1:2018, Figure 3.3.5.2 (C)

fAS 3610.1:2018, Figure 3.3.5.2 (C)

Ceiling Soffit

Uniform Tie Rod Hole Pattern

AS 3610.1:2018, 3.3.5.2 (b)

Face StepAS 3610.1:2018, 3.3.5.2 (b)

  • ≥ 200mm straightedge intervals over whole visible step
  • "s" tolerable gap between straightedge & finished concrete

AS 3610.1:2018, Table 3.3.5.1

Tolerable gapAS 3610.1:2018, Table 3.3.5.1

  • ≤ 5mm 95% surface reading
  • ≤ 7mm 100% surface reading

AS 3610.1:2018, 3.3.5.2 (d)

Out of Plumb - Circular ColumnAS 3610.1:2018, 3.3.5.2 (d)

  • 300mm plumb vertical distance from top & bottom surface
  • At 90° angles from each other

AS 3610.1:2018, 3.3.5.2 (c)

Flatness (Grid)AS 3610.1:2018, 3.3.5.2 (c)

  • Patterned Surface
  • 1.25m x 1.25m grid pattern
  • 300mm clearance on plane's edge

d

AS 3610.1:2018, 3.3.5.2 (a)

≥ 1.5mAS 3610.1:2018, 3.3.5.2 (a)

AS 3610.1:2018, Table 3.3.5.1

Tolerance Gap

≥ 3m to < 8m Ht.AS 3610.1:2018, Table 3.3.5.1

  • ≤ 6mm 95% surface reading
  • ≤ 8mm 100% surface reading

AS 3610.1:2018, Table 3.3.5.1

Tolerance Gap

< 3m Ht.AS 3610.1:2018, Table 3.3.5.1

  • ≤ 3mm 95% surface reading
  • ≤ 5mm 100% surface reading

AS 3610.1:2018, Figure 3.3.5.2 (A)

aAS 3610.1:2018, Figure 3.3.5.2 (A)

AS 3610.1:2018, 3.3.5.2 (a)

≥ 300AS 3610.1:2018, 3.3.5.2 (a)

Straight Edge (a - b)

AS 3610.1:2018, Table 3.3.5.1

Tolerance GapAS 3610.1:2018, Table 3.3.5.1

  • ≤ 2mm 95% surface reading
  • ≤ 4mm 100% surface reading

AS 3610.1:2018, 3.2.3

Class 1 Formwork Finish Fact SheetAS 3610.1:2018, 3.2.3

AS 3610.1:2018, 3.3.3.2

≥ 2mAS 3610.1:2018, 3.3.3.2

AS 3610.1:2018, 3.3.3.2

≥ 2mAS 3610.1:2018, 3.3.3.2

AS 3610.1:2018, 3.3.3.2 (a)

Blowholes ImperfectionAS 3610.1:2018, 3.3.3.2 (a)

  • Small holes on the surface
  • ≥ 2m viewing distance
  • 1:1 scale photo comparison for blowholes evaluation to AS 3610.1

AS 3610.1:2018, Table 3.3.5.1

Tolerable gapAS 3610.1:2018, Table 3.3.5.1

  • ≤ 4mm 95% surface reading
  • ≤ 5mm 100% surface reading

AS 3610.1:2018, 3.3.4.1

≤ 2mm or Span/360AS 3610.1:2018, 3.3.4.1

AS 3610.1:2018, 3.3.4.2

Form Face DeflectionAS 3610.1:2018, 3.3.4.2

  • ≥ 10 readings at ≥ 300mm intervals in the same direction of the span
  • "d", tolerable distance between straightedge & finished concrete

AS 3610.1:2018, Table 3.3.5.1

Tolerance GapAS 3610.1:2018, Table 3.3.5.1

  • Within Element
  • ≤ 1mm 95% surface reading
  • ≤ 2mm 100% surface reading
  • On Construction Joints
  • ≤ 2mm 95% surface reading
  • ≤ 3mm 100% surface reading

AS 3610.1:2018, Figure 3.3.5.2 (B)

≥ 200AS 3610.1:2018, Figure 3.3.5.2 (B)

AS 3610.1:2018, Figure 3.3.5.2 (B)

sAS 3610.1:2018, Figure 3.3.5.2 (B)

AS 3610.1:2018, 3.3.5.2 (a)

Surface UndulationsAS 3610.1:2018, 3.3.5.2 (a)

  • 300mm & 1.5m Straightedges
  • ≥ 30 readings of elements with ≥ 2m in either direction
  • ( a - b ) reading evaluation

AS 3610.1:2018, Table 3.3.5.1

Tolerance GapAS 3610.1:2018, Table 3.3.5.1

  • ≤ 1mm 95% surface reading
  • ≤ 2mm 100% surface reading

AS 3610.1:2018, Figure 3.3.5.2 (A)

bAS 3610.1:2018, Figure 3.3.5.2 (A)

AS 3610.1:2018, 3.3.5.2 (d)

Out of Plumb - WallAS 3610.1:2018, 3.3.5.2 (d)

  • 300mm plumb vertical distance from top & bottom surface
  • ≥ 2 readings at ≤ 5m CTS wall length

AS 3610.1:2018, 3.3.5.2 (d)

≤ 5mAS 3610.1:2018, 3.3.5.2 (d)

AS 3610.1:2018, 3.3.5.2 (d)

300AS 3610.1:2018, 3.3.5.2 (d)

AS 3610.1:2018, 3.3.5.2 (c)

FlatnessAS 3610.1:2018, 3.3.5.2 (c)

  • Non-pattern Surfaces
  • 10m w/ overlapping 5m reading along straight line
  • "f" tolerable gap between string line & finished concrete

AS 3610.1:2018, 3.3.5.2 (c)

10mAS 3610.1:2018, 3.3.5.2 (c)

AS 3610.1:2018, 3.3.5.2 (c)

10mAS 3610.1:2018, 3.3.5.2 (c)

AS 3610.1:2018, 3.3.5.2 (c)

5mAS 3610.1:2018, 3.3.5.2 (c)

AS 3610.1:2018, Figure 3.3.5.2 (C)

fAS 3610.1:2018, Figure 3.3.5.2 (C)

AS 3610.1:2018, Figure 3.3.5.2 (C)

fAS 3610.1:2018, Figure 3.3.5.2 (C)

AS 3610.1:2018, Figure 3.3.5.2 (C)

fAS 3610.1:2018, Figure 3.3.5.2 (C)

AS 3610.1:2018, Figure 3.3.5.2 (C)

fAS 3610.1:2018, Figure 3.3.5.2 (C)

AS 3610.1:2018, Figure 3.3.5.2 (C)

fAS 3610.1:2018, Figure 3.3.5.2 (C)

AS 3610.1:2018, Figure 3.3.5.2 (C)

fAS 3610.1:2018, Figure 3.3.5.2 (C)

AS 3610.1:2018, Figure 3.3.5.2 (D)

300AS 3610.1:2018, Figure 3.3.5.2 (D)

AS 3610.1:2018, Figure 3.3.5.2 (D)

300AS 3610.1:2018, Figure 3.3.5.2 (D)

AS 3610.1:2018, Figure 3.3.5.2 (C)

fAS 3610.1:2018, Figure 3.3.5.2 (C)

AS 3610.1:2018, 3.3.5.2 (d)

300AS 3610.1:2018, 3.3.5.2 (d)