Concrete Slab Edge Rebate Building Codes & Rules


- Slab Edge Rebate Tools™ simplifies the National Construction Code (NCC) with interactive graphics, including deemed to comply & best practices.


Earth

AS 2870:2011, 5.3.4

NCC 2022 HP, 4.2.9 (a)

≥ 20AS 2870:2011, 5.3.4NCC 2022 HP, 4.2.9 (a)

Vapour Barrier

Vapour Barrier

Earth

Edge Beam

Flashing

AS 3700:2018, 4.7.2

Weepholes

WH

Sand Blinding

Vapour Barrier

Sand Blinding

Termite Sheet

Sand Blinding

Edge Rebate

AS 2870:2011, 5.3.4 (b)

≥ 150 to 200AS 2870:2011, 5.3.4 (b)

AS 2870:2011, 5.3.4 (f)

> 400AS 2870:2011, 5.3.4 (f)

AS 2870:2011, 5.3.4 (c)

≥ 150AS 2870:2011, 5.3.4 (c)

DPC /

Flashing

Termite Sheet

- copy

Finished Ground

DPC /

Flashing

- copy

Bonded Zone

Bonded Zone

Fitment req'd

Edge Rebate

Edge Rebate

- copy

Finished Ground

AS 2870:2011, 5.3.4

External WallAS 2870:2011, 5.3.4

  • Masonry Cavity
  • Veneer Construction

AS 3660.1:2014, 5.3.8.2

≥ 35AS 3660.1:2014, 5.3.8.2

AS 3660.1:2014, 5.3.8.2

≥ 35AS 3660.1:2014, 5.3.8.2

AS 2870:2011, 5.3.4 (b)

FitmentsAS 2870:2011, 5.3.4 (b)

  • Allow reduction in horizontal thickness
  • R10 or N10 Cranked Bar
  • ≤ 900mm spacing
  • ≥ 200mm thk not required

AS 2870:2011, 5.3.4

External WallAS 2870:2011, 5.3.4

  • Masonry Cavity
  • Veneer Construction

AS 3660.1:2014, 4.4

Termite ManagementAS 3660.1:2014, 4.4

  • ≥ 75mm exposed Face
  • Sheet or Granular system

AS 3660.1:2014, 4.4

≥ 75AS 3660.1:2014, 4.4

AS 3660.1:2014, 4.4

Termite ManagementAS 3660.1:2014, 4.4

  • ≥ 75mm exposed Face
  • Sheet or Granular system

AS 2870:2011, 5.3.4

External WallAS 2870:2011, 5.3.4

  • Masonry Cavity
  • Veneer Construction

AS 3660.1:2014, 4.4

≥ 75AS 3660.1:2014, 4.4

AS 2870:2011, 5.3.4 (c)

≥ 150AS 2870:2011, 5.3.4 (c)

AS 2870:2011, 5.3.4

≥ 50AS 2870:2011, 5.3.4

AS 3660.1:2014, 4.4

≥ 75AS 3660.1:2014, 4.4

AS 2870:2011, 5.3.4 (f)

≥ 200AS 2870:2011, 5.3.4 (f)

AS 2870:2011, 5.3.4 (b)

≥ 150

to

400AS 2870:2011, 5.3.4 (b)

Termite Management


  • Where Termite risk is identified
  • ≥ 75mm Wall exposure between ground level & Termite Sheet, to allow visual detection of Termites[1]


Durable Notice RULES


NCC 2022 V1


All Building Classes


NCC 2022, 3.4.3


May 2023



NCC 2022 HP, 3.4.3

NCC 2022 HP, 3.4.3

NCC 2022 HP, 3.4.3 (a)

NCC 2022 HP, 3.4.3 (b)

NCC 2022 HP, 3.4.3 (c)

NCC 2022 HP, 3.4.3 (d)

Termite RISK


NCC 2022 V1


All Building Classes


NCC 2022, H1D3 & 3.4.1 [2019 3.1.4.2]


May 2023



NCC 2022 HP, 3.4.1 (1) (a)

NCC 2022 HP, 3.4.1 (1) (b)

NCC 2022 HP, 3.4.1(2)

  • Termite Management System Required if
  • Location is identified at Risk of Attack, &NCC 2022 HP, 3.4.1 (1) (a)
  • Any Primary Building Element is susceptibleNCC 2022 HP, 3.4.1 (1) (b)
  • Primary Building Elements are
  • Any member designed to take Loads
  • Wall, Roof, Ceiling, Floor, Ramp or Stair Framing
  • Any bracing or other framing members
  • Materials not susceptible to attackNCC 2022 HP, 3.4.1(2)
  • Metals
  • Concrete
  • Masonry
  • Fibre-reinforced Concrete
  • Naturally resistant Timber
  • Preservative-treated Timber

Termite MANAGEMENT


NCC 2022 V3


All Building Classes


NCC 2022 H1D3 & 3.4.2 [2019 3.1.4.3]


May 2023



NCC 2022 HP, 3.4.2

AS 3660.1:2014, 4.4

  • Termite Management compliance to the NCC

Inspection ZoneNCC 2022 HP, 3.4.2AS 3660.1:2014, 4.4

  • ≥ 75mm exposed Concrete Face
  • Off form, smooth surface, free of Ripples or Honeycombing
  • Tiling, Render, Vapour Barrier, Flashings, Structures & the like, not allowed to bridge this Zone

AS 3660.1:2014, 4.4

  • Where Termite risk is identified
  • ≥ 75mm Wall exposure between ground level & Termite Sheet, to allow visual detection of TermitesAS 3660.1:2014, 4.4

Vapour Barrier


  • Continuous under Beams & Waffle Pods[1]
  • Turn up to Ground Level at Slab Edges[2]
  • Protect from & repair any punctures[3]


Moisture Control


NCC 2022 V1


All Building Classes


NCC 2022, F1D7 & Part 4.2.8 [2019 F1.10, 3.2.2.6]


May 2023



AS 2870:2011, 5.3.3.2 (a)

AS 2870:2011, 5.3.3.2 (a) (i)

AS 2870:2011, 5.3.3.2 (a) (ii)

AS 2870:2011, 5.3.3.4 (b)

AS 2870:2011, 5.3.3.4 (a)

AS 2870:2011, 5.3.3.4 (c)

AS 2870:2011, 5.3.3.3 (c)

AS 2870:2011, 5.3.3.4 (a)

AS 2870:2011, 5.3.3.4 (a)

Concrete Benchmark

Concrete Mix


  • N20 Grade to AS 1379[1]
  • ≥ 20 Mpa strength at 28 days[2]
  • ≤ 20mm aggregate size[3]
  • 100mm slump[4]
  • Properly compacted[5]


Concrete Mix RULES


NCC 2022 V3


All Building Classes


NCC 2022, 4.2.10 [2019 3.2.3.1]



May 2023



NCC 2022 HP, 4.2.10

  • Construction of Footings & Slabs to comply with NCC Part 4.2, AS 2870, & AS 3600
  • Concrete to AS 3600NCC 2022 HP, 4.2.10
  • Mixing & Delivery
  • ≤ 1 ½ hrs complete discharge from Concrete truck upon Cement hydration unless a retarder is used
  • Compaction by vibration
  • To remove air pockets
  • Improve contact with Reinforcement & Formwork
  • Enhance durability
  • Avoid over-vibrating
  • Slab Edges
  • Proper finishing & curing of edges improves resistance to moisture damage
  • Chemical Curing
  • Determine if surface finish adhesive to be used is compatible with chemical curing methods

AS 2870:2011, 5.3.1

NCC 2022 HP, 4.2.10 (a) (i)

NCC 2022 HP, 4.2.10 (a) (ii)

NCC 2022 HP, 4.2.10 (a) (iii)

NCC 2022 HP, 4.2.10 (c)

Concrete Cover


  • ≥ 30mm over membrane[1]
  • ≥ 40mm unprotected ground[2]
  • ≥ 20mm internal surface[3]
  • ≥ 40mm external exposure[4]


Concrete COVER


NCC 2022 V3


All Building Classes


NCC 2022 4.2.11 [2019 3.2.3.2]


May 2023



AS 3600:2018, 4.10.3.2

AS 3600:2018, 4.3.1 (c)

  • Concrete must comply with the NCC
  • Cover for standard Formwork & compaction as per tableAS 3600:2018, 4.10.3.2
  • Add thickness where cast against ground
  • Embedded elements must be protected from corrosion or deteriorationAS 3600:2018, 4.3.1 (c)

NCC 2022 HP, 4.2.11 (5) (b)

NCC 2022 HP, 4.2.11 (5) (a)

NCC 2022 HP, 4.2.11 (5) (c)

NCC 2022 HP, 4.2.11 (5) (d)