Concrete Slab Edge Rebate Building Codes & Rules


- Discover how rebates and setdowns provide crucial water protection and avoid costly mistakes in your building projects. Learn key tips for success.


AS 3660.1:2014, 4.4

Termite ManagementAS 3660.1:2014, 4.4

  • ≥ 75mm exposed Face
  • Sheet or Granular system

AS 2870:2011, 5.3.4

External WallAS 2870:2011, 5.3.4

  • Masonry Cavity
  • Veneer Construction

AS 3660.1:2014, 4.4

≥ 75AS 3660.1:2014, 4.4

AS 3660.1:2014, 4.4

≥ 75AS 3660.1:2014, 4.4

DPC /

Flashing

Bonded Zone

Termite Sheet

- copy

Fitment req'd

Edge Rebate

- copy

AS 2870:2011, 5.3.4 (b)

FitmentsAS 2870:2011, 5.3.4 (b)

  • Allow reduction in horizontal thickness
  • R10 or N10 Cranked Bar
  • ≤ 900mm spacing
  • ≥ 200mm thk not required

Finished Ground

AS 2870:2011, 5.3.4

External WallAS 2870:2011, 5.3.4

  • Masonry Cavity
  • Veneer Construction

AS 2870:2011, 5.3.4

External WallAS 2870:2011, 5.3.4

  • Masonry Cavity
  • Veneer Construction

AS 3660.1:2014, 4.4

Termite ManagementAS 3660.1:2014, 4.4

  • ≥ 75mm exposed Face
  • Sheet or Granular system

AS 3660.1:2014, 5.3.8.2

≥ 35AS 3660.1:2014, 5.3.8.2

Edge Rebate

AS 3660.1:2014, 5.3.8.2

≥ 35AS 3660.1:2014, 5.3.8.2

Earth

Vapour Barrier

Vapour Barrier

Earth

Flashing

AS 3700:2018, 4.7.2

WeepholesAS 3700:2018, 4.7.2

  • ≥ 1.2m CTS Intervals

WH

Sand Blinding

Vapour Barrier

Sand Blinding

Sand Blinding

Termite Sheet

AS 2870:2011, 5.3.4 (b)

≥ 150

to

400AS 2870:2011, 5.3.4 (b)

AS 3660.1:2014, 4.4

≥ 75AS 3660.1:2014, 4.4

AS 2870:2011, 5.3.4

≥ 50AS 2870:2011, 5.3.4

AS 2870:2011, 5.3.4 (f)

≥ 200AS 2870:2011, 5.3.4 (f)

AS 2870:2011, 5.3.4 (c)

≥ 150AS 2870:2011, 5.3.4 (c)

Edge Rebate

AS 2870:2011, 5.3.4

NCC 2022 HP, 4.2.9 (a)

≥ 20AS 2870:2011, 5.3.4NCC 2022 HP, 4.2.9 (a)

AS 2870:2011, 5.3.4 (f)

> 400AS 2870:2011, 5.3.4 (f)

Edge Beam

Bonded Zone

DPC /

Flashing

Finished Ground

AS 2870:2011, 5.3.4 (b)

≥ 150 to 200AS 2870:2011, 5.3.4 (b)

AS 2870:2011, 5.3.4 (c)

≥ 150AS 2870:2011, 5.3.4 (c)

Vapour Barrier


  • Continuous under Beams & Pods[1]
  • Turn up to Ground Level at Slab Edges[2]
  • Protect from & repair any punctures[3]


Moisture Control


NCC 2022 V1


All Building Classes


NCC 2022, F1D7 & Part 4.2.8 [2019 F1.10, 3.2.2.6]


May 2023



AS 2870:2011, 5.3.3.2 (a)

AS 2870:2011, 5.3.3.2 (a) (i)

AS 2870:2011, 5.3.3.2 (a) (ii)

AS 2870:2011, 5.3.3.4 (b)

AS 2870:2011, 5.3.3.4 (a)

AS 2870:2011, 5.3.3.4 (c)

NCC 2022 HP, 4.2.8

NCC 2022 Vol 1, F1D7

AS 2870:2011, 5.3.3.4 (a)

AS 2870:2011, 5.3.3.4 (a)

AS 2870:2011, 5.3.3.3 (c)

Concrete Benchmark

Concrete Cover


  • ≥ 30mm over membrane[1]
  • ≥ 40mm unprotected ground[2]
  • ≥ 20mm internal surface[3]
  • ≥ 40mm external exposure[4]


Concrete COVER


NCC 2022 V5


All Building Classes


NCC 2022 4.2.11 [2019 3.2.3.2]


May 2023



AS 3600:2018, 4.10.3.2

AS 3600:2018, 4.3.1 (c)

NCC 2022 HP, 4.2.11

NCC 2022 HP, 4.2.11 (5) (b)

NCC 2022 HP, 4.2.11 (5) (a)

NCC 2022 HP, 4.2.11 (5) (c)

NCC 2022 HP, 4.2.11 (5) (d)

Termite Management


  • Termite control required for Ground Level floor junctions
  • ≥ 75mm slab exposure above the external finished floor level to allow easy detection of termites[1]


Durable Notice RULES


NCC 2022 V1


All Building Classes


NCC 2022, 3.4.3


May 2023



NCC 2022 HP, 3.4.3

NCC 2022 HP, 3.4.3

NCC 2022 HP, 3.4.3 (a)

NCC 2022 HP, 3.4.3 (b)

NCC 2022 HP, 3.4.3 (c)

NCC 2022 HP, 3.4.3 (d)

Termite RISK


NCC 2022 V3


Class 1 & 10


NCC 2022, H1D3 & HP3.4.1 [2019 3.1.4.2]


May 2023



NCC 2022 HP, 3.4.1(2)

NCC 2022 HP, 3.4.1 (1) (b)

NCC 2022 HP, 3.4.1

  • Termite Management System Required ifNCC 2022 HP, 3.4.1(2)
  • Location is identified at Risk of Attack, &
  • Any Primary Building Element is susceptible
  • Primary Building Elements areNCC 2022 HP, 3.4.1 (1) (b)
  • Any member designed to take Loads
  • Wall, Roof, Ceiling, Floor, Ramp or Stair Framing
  • Any bracing or other framing members
  • Materials not susceptible to attackNCC 2022 HP, 3.4.1
  • Metals
  • Concrete
  • Masonry
  • Fibre-reinforced Concrete
  • Naturally resistant Timber
  • Preservative-treated Timber

Termite MANAGEMENT


NCC 2022 V5


Class 1 & 10


NCC 2022 H1D3 & HP3.4.2 [2019 3.1.4.3]


May 2023



NCC 2022 HP, 3.4.2

AS 3660.1:2014, 4.4

NCC 2022 Vol 2, H1D3

  • Termite Management compliant to the NCCNCC 2022 HP, 3.4.2
  • Inspection ZoneAS 3660.1:2014, 4.4NCC 2022 Vol 2, H1D3
  • ≥ 75mm exposed Concrete Face
  • Smooth surface, free of Ripples or Honeycombing
  • Tiling, Render, Vapour Barrier, Flashings, Structures & the like, not allowed to bridge this Zone

AS 3660.1:2014, 4.4

  • Termite control required for Ground Level floor junctions
  • ≥ 75mm slab exposure above the external finished floor level to allow easy detection of termitesAS 3660.1:2014, 4.4

Concrete Mix


  • N20 Grade to AS 1379[1]
  • ≥ 20 Mpa strength at 28 days[2]
  • ≤ 20mm aggregate size[3]
  • 100mm slump[4]
  • Properly compacted[5]


Concrete Mix RULES


NCC 2022 V4


All Building Classes


NCC 2022, 4.2.10 [2019 3.2.3.1]



May 2023



NCC 2022 HP, 4.2.10

  • Concrete to comply with NCCNCC 2022 HP, 4.2.10
  • Mixing & Delivery
  • ≤ 1 ½ hrs complete discharge from Concrete truck upon Cement hydration unless a retarder is used
  • Compaction by vibration
  • To remove air pockets
  • Improve contact with Reinforcement & Formwork
  • Enhance durability
  • Avoid over-vibrating
  • Slab Edges
  • Proper finishing & curing of edges improves resistance to moisture damage
  • Chemical Curing
  • Determine if surface finish adhesive to be used is compatible with chemical curing methods

NCC 2022 HP, 4.2.10 (a) (i)

NCC 2022 HP, 4.2.10 (a) (ii)

NCC 2022 HP, 4.2.10 (a) (iii)

NCC 2022 HP, 4.2.10 (c)

AS 2870:2011, 5.3.1