NCC 2022 Vol 1, C2D4 (2)
- If topmost FloorNCC 2022 Vol 1, C2D4 (2)
- Takes on the Class adjacent, or
- Class immediately below Class 4 occupies whole Storey
NCC 2022 Vol 1, Glossary
- Vertically mixed = Requires higher Fire Resisting Type to all Storeys
- Type of Construction determined by classification of Upper Level
- Horizontally mixed = Requires higher Fire Resisting Type to all Storeys
- Separate by a fire wall between different Types of Construction
NCC 2022 Vol 1, C2D3 (2) (b)
NCC 2022 Vol 1, C2D3 (2) (a)
NCC 2022 Vol 1, C2D3 (4)
NCC 2022 Vol 1, C2D3 (4)
NCC 2022 Vol 1, C2D3 (1)
NCC 2022 Vol 1, C2D3 (1) (a)
NCC 2022 Vol 1, C2D3 (2) (b)
NCC 2022 Vol 1, Glossary
Count Storeys in a vertical line above finished Ground Level
Include:
Exclude:
NCC 2022 Vol 1, C2D6 (a)
- 2 Storey Building can reduce the fire resistance from Type B to Type C if all Sole Occupancy UnitsNCC 2022 Vol 1, C2D6 (a)
- Have 2 exits, or
- 1 exit opens to a road or open space
NCC 2022 Vol 1, C2D3 (3)
Floors with high Ceiling
- > 6mNCC 2022 Vol 1, C2D3 (3) internal height ............................................................................
NCC 2022 Vol 1, C2D3 (3)
NCC 2022 Vol 1, S5C7 (2)
MezzanineNCC 2022 Vol 1, S5C7 (2)
- Is a Storey if Mezzanine floor area is
- > 200m² floor area, or 1/3 of the room it is in
- The above applies to 1 Mezzanine or the sum of multiple Mezzanines within same floor level & within the same part of a building
NCC 2022 Vol 1, C2D2 (1)
NCC 2022 Vol 1, C2D5
NCC 2022 Vol 1, C2D4
NCC 2022 Vol 1, C2D2 (1)
NCC 2022 Vol 1, S5C21 (1)
NCC 2022 Vol 1, S5C24 (1)
NCC 2022 Vol 1, S5C21 (1)
NCC 2022 Vol 1, S5C11 (1)
NCC 2022 Vol 1, S5C21 (1)
NCC 2022 Vol 1, S5C24 (1)
NCC 2022 Vol 1, S5C21 (1)
NCC 2022 Vol 1, S5C24 (1)
NCC 2022 Vol 1, S5C24 (1)
NCC 2022 Vol 1, S5C11 (1)
NCC 2022 Vol 1, S5C24 (1)
NCC 2022 Vol 1, S5C11 (1)
NCC 2022 Vol 1, C2D3 (2) (b)
NCC 2022 Vol 1, C2D3 (3)
NCC 2022 Vol 1, C2D3 (2) (b)
2 Storeys, or
1 Storey if the only Storey above ground