Sealer Membrane (Stone Finish only)
AS 3740:2021, 2.3.1 AS 3740:2021, 2.3.5 Waterstop Angle
AS 3958.1:2007, 3.3.3.1 (e) AS 3740:2021, 4.9.2 (b) NCC 2022 Vol 1, F2D4 (2) NCC 2022 HP, 10.2.12 (a) AS 3740:2021, 4.9.1 (c) (ii) Jambs & Architraves
Never embed in Tiles Prime cut ends Seal under ends to Tiles Sealant over anchor screws
Localised levelling compound to align floor finish levels
AS 1428.1:2009, 7.2 (a) Waterstop Angle
Preferred alignment to center of Door Leaf Membrane Substrate
≥ 1 : 100 fall required towards the Floor Waste [1] ≥ 1 : 80 fall required to entire room where Shower unscreened [2] Form falls in Structural Floor or Screed [3] Smooth, clean, dry & dust free surface [4] Substrate PREPARATION NCC 2022 V4 All Building Classes
NCC 2022 F2D2, S26C3, & HP10.2.9 [2019 F1.7]
May 2023
AS 3740:2021, 4.4.1 Building elements in Wet Areas to be Waterproof or Water Resistant to the NCC All surfaces to be prepared for Waterproofing System adhesionAS 3740:2021, 4.4.1 Smooth, dust-free, clean & dry surface Fill voids Grind smooth any protrusions Free of formwork deformity Prime substrate to prohibit pin-holing during the membrane curing process Moisture test & apply primer as per Manufacturer's Recommendations Substrate PREPARATION NCC 2022 V1 AS 3740:2021, 2.3 AS 3740:2021, 4.4.1 AS 3740:2021, 2.3.1 AS 3740:2021, 2.3.5 Swing Door
Stone Threshold
Floor Finish
Tile selection P3 or R10 Slip Rating[1] Movement Joints[2] ≤ 4.5m CTSAlign with Structural movement or Control Joints Above load bearing Beams or Walls Tile TOLERANCE NCC 2022 V2 All Building Classes
NCC 2022 F2D2, S26C3 [2019 F1.7]
NCC 2022 HP10.2.12
May 2023
NCC 2022 Vol 1, F2D4 (2) AS 3740:2021, 2.3.1 AS 3740:2021, 2.3.5 NSW 2017 Guide to Standards & Tolerances, 12.6 AS 3958.1:2007, 5.4.6 (c) AS 3958.1:2007, 5.4.6 (a) NCC 2022 HP, 10.2.12 HB 198:2014, 5.1 AS 3958.1:2007, 5.4.5.2 Waterstop
≥ 40mm set down[1] ≥ 25mm Screed depth to be maintained when calculating Falls throughout the wet area[2] Sealant beads & fillets to protect Membrane[3] Waterstop RULES NCC 2022 V2 All Building Classes
NCC 2022 F2D2, S26C3, & Part 10.2.11 to 13 [2019 F1.7]
May 2023
AS 3740:2021, 3.3.1 (a) AS 3740:2021, 3.3.3 (a) (iv) AS 3740:2021, 4.9 AS 3740:2021, 3.3.3 (b) (ii) AS 3740:2021, 3.3.1 (c) Step up PROS & CONS NCC 2022 V1 Water Stop INSTALLATION NCC 2022 V1 Waterstop Angle NCC 2022 V1 NCC 2022 HP, 10.2.2 (1) (c) AS 3958.1:2007, 3.3.3.1 (e) AS 3740:2021, 4.9.1 (d) (ii) Membrane
Wall Linings
6mm Fibre- cement for typical Tile or paint finish8mm gap to Structural FloorWall Lining INSTALLATION NCC 2022 V1 Wall Lining SELECTION NCC 2022 V3 Refer to Manufacturer's Recommendations for Fixing type & spacing 6mm Fibre-cementPreferred for typical installations ≤ 13mm thick vitrified or ceramic tiles9 to 12mm Fibre-cementWhere thicker stone tiles are to be used WR Plasterboard NOT in shower areas ≤ 6mm Tiles or Paint finish6mm Fibre- cement for typical Tile or paint finish8mm gap to Structural FloorMembrane
Turn the Membrane down into the Leak Control Flange [1] Compatible to suit Substrate & bedding / finishes [2] Test & protect from damage [3] Membrane AUDIT NCC 2022 V2 All Building Classes
NCC 2022 F2D2, S26C3, 10.2.26 [2019 F1.7]
May 2023
AS 3740:2021, 4.5.4 (a) AS 3740:2021, 4.5.4 (b) AS 3740:2021, 4.5.4 (c) AS 3740:2021, 4.5.2 Building elements in Wet Areas to be Waterproof or Water Resistant to NCC Specification 26, Part 10.2, & AS 3740 Curing & protection AS 3740:2021, 4.5.4 (a) Fully cured to manufacturers' recommendations Protect from physical & chemical damage until covered by finishes Flood testing AS 3740:2021, 4.5.4 (b) If any leaks occur, these shall be repaired following the system design & retested Electronic leak detection AS 3740:2021, 4.5.4 (c) If any discontinuities occur, these shall be repaired & retested only on the repaired areas Seam probe testing AS 3740:2021, 4.5.2 If any seam failures occur, these shall be repaired & retested Membrane Curing & Inspection RULES NCC 2022 V2 All Building Classes
NCC 2022 F2D2, S26C3, 10.2.28 [2019 F1.7]
May 2023
AS 3740:2021, 4.5.2 AS 3740:2021, 4.5.3 Building elements in Wet Areas to be Waterproof or Water Resistant to NCC Specification 26, Part 10.2, & AS 3740 Fully cure prior to any testingAS 3740:2021, 4.5.2 Visual inspection conducted prior to application of overlay finishesAS 3740:2021, 4.5.3 AS 3740:2021, 4.3.1 (a) AS 3740:2021, 3.2 AS 3740:2021, 4.17 (b) Redirecting... (5)