Tools™ Best Practice Tools™ Best Practice Waterstop Angle at Cavity Tools™ Best Practice
2mm gap to Jamb to allow for movement Mitre cut bottom web & fold 90° to prevent leak into cavity File smooth all edges Sealant to all edges & junctions Finishes
NCC 2022 HP, 10.2.2 (1) (c) AS 3740:2021, 4.11.2 (b) Membrane
Manufacturer's Requirement Industry Recommendation Tools™ Best Practice NCC 2022 HP, 10.2.24 (a) (ii) AS 3740:2021, 4.9.1 (c) (iii) NCC 2022 HP, 10.2.24 (c) AS 3740:2021, 4.9.1 (a) (i) Sealant over anchor screws
Industry Recommendation NCC 2022 HP, 10.2.24 Industry Recommendation Industry Recommendation Internal Waterproofing Overview
Waterstop
≥ 40mm set down[1] ≥ 25mm Screed depth to be maintained when calculating Falls throughout the wet area[2] Sealant beads & fillets to protect Membrane[3] Waterstop RULES NCC 2022 V2 All Building Classes
NCC 2022 F2D2, S26C3, & Part 10.2.11 to 13 [2019 F1.7]
May 2023
AS 3740:2021, 3.3.1 (a) AS 3740:2021, 3.3.3 (a) (iv) AS 3740:2021, 4.9 AS 3740:2021, 3.3.3 (b) (ii) AS 3740:2021, 3.3.1 (c) Step up PROS & CONS NCC 2022 V1 Water Stop INSTALLATION NCC 2022 V1 NCC 2022 HP, 10.2.2 (1) (c) AS 3958.1:2007, 3.3.3.1 (e) AS 3740:2021, 4.9.1 (d) (ii) Substrate
CSP 2 -5 (Concrete Surface Profile)[1] Smooth Wood Float equivalent finish Smooth & clean before waterproofing[2] No ribs, ridges or over-trowelling Substrate MATERIALS NCC 2022 V3 All Building Classes
NCC 2022 F2D2, S26C3, & HP10.2.24 [2019 F1.7, 3.8.1]
May 2023
AS 3740:2021, 3.3.2 (a) AS 3740:2021, 3.3.2 (b) NCC 2022 HP, 10.2.1 NCC 2022 Vol 1, F2D2 NCC 2022 Vol 1, S26C3 (1) Substrate PREPARATION NCC 2022 V1 Substrate PREPARATION NCC 2022 V6 All Building Classes
NCC 2022 F2D2, S26C3, & HP10.2.9 [2019 F1.7]
May 2023
AS 3740:2021, 4.4.1 NCC 2022 Vol 1, F2D2 NCC 2022 Vol 1, S26C3 (1) NCC 2022 HP, 10.2.9 Building elements in Wet Areas to be Waterproof or Water Resistant to the NCCAS 3740:2021, 4.4.1 NCC 2022 Vol 1, F2D2 NCC 2022 Vol 1, S26C3 (1) All surfaces to be prepared for Waterproofing System adhesionNCC 2022 HP, 10.2.9 Smooth, dust-free, clean & dry surface Fill voids Grind smooth any protrusions Free of formwork deformity Prime substrate to prohibit pin-holing during the membrane curing process Moisture test & apply primer as per Manufacturer's Recommendations AS 3740:2021, 4.4.1 AS 3740:2021, 4.4.1 Junctions
≥ 12mm [1] Bond breaker Fillet to all Class III Membrane JunctionsJunction RULES NCC 2022 V4 All Building Classes
NCC 2022 F2D2, S26C3, & Part 10.2.24 [2019 F1.7, 3.8.1]
May 2023
AS 3740:2021, 4.10 AS 3740:2021, 4.13.2.2 NCC 2022 F2D2, S26C3, & Part 10.2.24 [2019 F1.7, 3.8.1] Building elements in Wet Areas to be Waterproof or Water Resistant to NCC Specification 26, NCC Part 10.2, & AS 3740 Backing rod, tape, or sealant should be installed when the membrane is bonded to the substrate Type depending on membrane flexibility classAS 3740:2021, 4.10 Class I Membrane (low extensibility)
Resin systems, or water-based epoxies membranes ≥ 6mm Ø AS 3740:2021, 4.13.2.2 backing rod should be installed to allow the membranes to flex instead of stretch, with a continuous tape between backing rod and membrane to keep it in placeClass II Membrane (medium extensibility)
Acrylic membranes, bitumen-based emulsions or mastics membranes Tape to allow the membrane to stretch Class III Membrane (high extensibility)
Polyurethane, PVC, rubber, or EPDM membrane Fillet or sealant to allow even thickness to the membrane AS 3740:2021, 4.10 Wall Linings
6mm Fibre-cement for typical Tile or Paint finish 8mm gap to Structural Floor Wall Lining NCC 2022 V2 6mm Fibre-cement for typical Tile or Paint finish 8mm gap to Structural Floor Redirecting... (5)