Pavers on Pedestal Supports Building Codes & Rules



Fall

Angle

Membrane

Substrate

AS 4654.2:2012, 2.8.3

WaterstopAS 4654.2:2012, 2.8.3

  • Rebate, or
  • Waterstop angle

M

M

M

Gasket to

protect

Membrane

Membrane

Fillet

M

AS 4654.2:2012, 2.5.2

≥ 1:100AS 4654.2:2012, 2.5.2

Water Holding Surface

End Cap

Reveal

Pedestal

Support

M

Sub-sill

Waterstop Angle

Membrane Height


  • Height sufficient to prevent wind-driven water entry[1]


Membrane Height INTERPRETATION


NCC 2022 V1


NCC 2022 Vol 1, F1D5

AS 4654.2:2012, 2.8.1.1

AS 4654.2:2012, 2.8.3 (b)

The following Tools™ interpretation should be confirmed as DtS or Performance Solution

  • A roof, balcony, podium or similar horizontal surface part of a building must be provided with a waterproofing membrane to AS 4654.1 & 2NCC 2022 Vol 1, F1D5
  • AS 4654.2-2012, 2.8.1.1 states Membrane height above finished surface is sufficient to prevent wind-driven water entering the buildingAS 4654.2:2012, 2.8.1.1
  • Termination heights are given in the Standard as a guide only, so
  • The heights given are not mandatory
  • The "finished surface level" is implied as a solid non-draining surface
  • AS 4654.2-2012, 2.8.3 (b) states where the floor finishes do not allow an upturn, the membrane must terminate into the stormwater system, this is backed up by a Zero Threshold diagramAS 4654.2:2012, 2.8.3 (b)
  • Pavers on pedestals are a similar solution
  • The free draining pavers are the grate
  • The membraned balcony with falls is the drain to stormwater
  • The membrane termination height is provided above the "water holding surface" which is also protected from wind driven rain by the pavers

Membrane Vertical Termination CERTIFICATION


NCC 2022 V1


  • Confirm with Waterproofing Consultant to confirm installation is considered DtS or Performance Solution
  • Mirvac's current position is considered DtS with Vertical Termination measured from Overflow Level
  • If horizontally discharged, taken vertically from the invert of the Overflow, or
  • If vertically discharged, taken vertically from the top of the Overflow

Membrane Height RULES


NCC 2022 V1


All Building Classes


NCC 2022 F1D5 [2019 Table F1.4]


May 2023



NCC 2022 Vol 1, F1D5

AS 4654.2:2012, 2.8.1.1

AS 4654.2:2012, A

  • A roof, balcony, podium or similar horizontal surface part of a building must be provided with a waterproofing membraneNCC 2022 Vol 1, F1D5
  • To AS 4654.1 & AS 4654.2
  • Unless is a deck or perforated or directly above ground
  • Measured from top of surface finish to height of membraneAS 4654.2:2012, 2.8.1.1
  • Height sufficient to prevent wind-driven water entry
  • Varies depending on wind class & level of protection
  • Termination heights to AS 4654.2 2012, Table A1 are minimum & informative onlyAS 4654.2:2012, A
  • Must be specified based on individual project wind classification

AS 4654.2:2012, 2.8.1.1

Fixings


  • ≤ 600mm CTS[1]
  • Seal to prevent water ingress[2]


Fixing RULES


NCC 2022 V3


All Building Classes


NCC 2022 J5D5, H6D2, & HP13.4.4 [2019 J3.4, 3.12.0, 3.12.3.3]


May 2023



NCC 2022 HP, 13.4.4

NCC 2022 Vol 1, J5D5 (1)

NCC 2022 Vol 2, H6D2 (1)

AS 4654.2:2012, 2.8.3

Fixing BEST PRACTICE


NCC 2022 V1


AS 4654.2:2012, 2.8.1.1

Manufacturer's Requirement

Subsill Installations - Mirvac Requirement

  • Design reviews should capture how the subsill drainage tracks to a drain point, ensuring no potential obstructions exist
  • All fixings through subsills are to be appropriately sealed
  • Backing rod/caulking of subsills to internal habitable side of the glazing/window suite

Subsill Installations


  • Physical stop ends (i.e. End Dams or Caps) are required to be documented, installed, and sealed on the inside face of Sub-sills


End Cap


NCC 2022 V1


null
  • Physical stop ends (i.e. End Dams or Caps) are required to be documented, installed, and sealed on the inside face of Sub-sills

Finished Floor

End Cap


  • Press in cap preferred
  • Fully seal to sub-sill
  • ≥ 3mm gap to reveal


End Cap WATERPROOFING


NCC 2022 V1


null
  • Press in cap preferred
  • Fully seal to sub-sill
  • ≥ 3mm gap to reveal

Fillet

Floor System

M

M

Pedestal

Support