Linear Shower Drain Building Codes & Rules


- Linear Shower Drain Tools™ simplifies the National Construction Code (NCC) with interactive graphics, including deemed to comply & best practices.


Fall

Foam Expansion Joint

Specify outlet location

Adhesive

Timber Stud

Adhesive

Membrane

Screed

Wall Lining

Fall Substrate Below

NCC 2022 Vol 1, F2D4 (2)

NCC 2022 HP, 10.2.12 (a)

1 : 80 to 1 : 50NCC 2022 Vol 1, F2D4 (2)NCC 2022 HP, 10.2.12 (a)

Sealant

Floor Tiles

Slip Resistance

Sealant

Bead

Fall

Leak Control

Flange

Linear Shower Drain


  • Height set below tile
  • Removable Grate


Strip Drain PLACEMENT


NCC 2022 V1


  • Fabricated 316 Stainless Steel continuous grate & housing
  • Drainage Outlet incorporated in fabrication process
  • Loose fitted Grate
  • Height set below tile
  • Removable Grate

M

M

M

M

M

HB 198:2014, 5.1

P3 or R10HB 198:2014, 5.1

Removable Grate

Non-shrink grout

Fillet

Fall

Wall Tiles

Substrate

AS 3740:2021, 2.3.1

AS 3740:2021, 2.3.5

1 : 100 AS 3740:2021, 2.3.1/ 1 : 80AS 3740:2021, 2.3.5

Recess into substrate

Membrane

M

Linear Shower Drain


  • Height set below tile
  • Removable Grate


Strip Drain PLACEMENT


NCC 2022 V1


  • Height set below tile
  • Removable Grate

Outlet


  • Ø 80 ID for maintenance


Outlet


NCC 2022 V1


  • Provide adequate outlet ID for maintenance
  • Ø 80mm ID typically
  • Ø 100mm ID (ACT)
  • Required clearance for access to trap below
  • Ø 80 ID for maintenance

Membrane Substrate


  • ≥ 1 : 100 fall required towards the Floor Waste[1]
  • ≥ 1 : 80 fall required to entire room where Shower unscreened[2]
  • Form falls in Structural Floor or Screed[3]
  • Smooth, clean, dry & dust free surface[4]


Substrate PREPARATION


NCC 2022 V4


All Building Classes


NCC 2022 F2D2, S26C3, & HP10.2.9 [2019 F1.7]


May 2023



AS 3740:2021, 4.4.1

  • Building elements in Wet Areas to be Waterproof or Water Resistant to the NCC
  • All surfaces to be prepared for Waterproofing System adhesionAS 3740:2021, 4.4.1
  • Smooth, dust-free, clean & dry surface
  • Fill voids
  • Grind smooth any protrusions
  • Free of formwork deformity
  • Prime substrate to prohibit pin-holing during the membrane curing process
  • Moisture test & apply primer as per Manufacturer's Recommendations

Substrate PREPARATION


NCC 2022 V1


AS 3740:2021, 2.3

AS 3740:2021, 4.4.1

AS 3740:2021, 2.3.1

AS 3740:2021, 2.3.5

Floor Tiles


  • Tile selection
  • P3 or R10 Slip Rating[1]
  • Movement Joints[2]
  • ≤ 4.5m CTS
  • Align with Structural movement or Control Joints
  • Above load bearing Beams or Walls


Slip RATING


NCC 2022 V2


All Building Classes


NCC 2022 D1P2


May 2023



Tile TOLERANCE


NCC 2022 V2


All Building Classes


NCC 2022 F2D2, S26C3 [2019 F1.7]

NCC 2022 HP10.2.12


May 2023



NCC 2022 Vol 1, F2D4 (2)

AS 3740:2021, 2.3.1

AS 3740:2021, 2.3.5

NSW 2017 Guide to Standards & Tolerances, 12.6

AS 3958.1:2007, 5.4.6 (c)

AS 3958.1:2007, 5.4.6 (a)

NCC 2022 HP, 10.2.12

HB 198:2014, 5.1

AS 3958.1:2007, 5.4.5.2

Substrate


  • Form falls in Structural Floor or Screed[1]
  • Smooth, clean, dry & dust free surface[2]


Substrate FALLS


NCC 2022 V3


All Building Classes


NCC 2022 F2D2, S26C3, 10.2.9, & 10.2.12 [2019 F1.7]


May 2023



AS 3740:2021, 2.3.1

AS 3740:2021, 2.3.5

  • Building elements in Wet Areas to be Waterproof or Water Resistant to NCC Specification 26, Part 10.2, & AS 3740
  • ≥ 1 : 100 fall required approaching Floor WasteAS 3740:2021, 2.3.1
  • ≥ 1 : 80 fall required to entire room where Shower unscreenedAS 3740:2021, 2.3.5

Substrate PREPARATION


NCC 2022 V4


All Building Classes


NCC 2022 F2D2, S26C3, & HP10.2.9 [2019 F1.7]


May 2023



AS 3740:2021, 4.4.1

  • Building elements in Wet Areas to be Waterproof or Water Resistant to the NCC
  • All surfaces to be prepared for Waterproofing System adhesionAS 3740:2021, 4.4.1
  • Smooth, dust-free, clean & dry surface
  • Fill voids
  • Grind smooth any protrusions
  • Free of formwork deformity
  • Prime substrate to prohibit pin-holing during the membrane curing process
  • Moisture test & apply primer as per Manufacturer's Recommendations

Substrate PREPARATION


NCC 2022 V1


AS 3740:2021, 4.4.1

AS 3740:2021, 2.3

Wall linings


  • 6mm fibre cement for typical tile or paint finish
  • 8mm gap to structural floor


Wall Lining


NCC 2019 V1


  • Refer to Manufacturer's recommendations for Fixing type & spacing
  • 6mm Fibre-cement
  • Preferred for typical installations
  • ≤ 13mm thk Vitrified or Ceramic tiles
  • 9 to 12mm Fibre-cement
  • Where thicker stone tiles are to be used
  • WR Plasterboard NOT Allowed
  • 8mm Movement gap to slab
  • WATERPROOFER to seal gap with Polyurethane Sealant
  • 6mm fibre cement for typical tile or paint finish
  • 8mm gap to structural floor

Outlet


  • Ø 80 ID for maintenance


Maintenance ACCESS


NCC 2022 V1


  • Ø 80 ID for maintenance

Outlet


  • Ø 80 ID for maintenance


Outlet


NCC 2022 V1


  • Provide adequate outlet ID for maintenance
  • Ø 80mm ID typically
  • Ø 100mm ID (ACT)
  • Required clearance for access to trap below
  • Ø 80 ID for maintenance

Linear Shower Drain


  • Height set below tile
  • Top of grout flush to finish to prevent water retention in between tiles
  • Locate at shower door or opposite wall
  • Parallel to shower door to improve falls in floor


Strip Drain PLACEMENT


NCC 2022 V1


  • Height set below tile
  • Top of grout flush to finish to prevent water retention in between tiles
  • Locate at shower door or opposite wall
  • Parallel to shower door to improve falls in floor

NCC 2022 HP, 10.2.12

NCC 2022 Vol 1, F2D4 (2) (a)

Wall linings


  • 6mm fibre cement for typical tile or paint finish
  • 8mm gap to structural floor


Wall Lining


NCC 2022 V3


  • Refer to Manufacturer's recommendations for Fixing type & spacing
  • 6mm Fibre-cement
  • Preferred for typical installations
  • ≤ 13mm thk Vitrified or Ceramic tiles
  • 9 to 12mm Fibre-cement
  • Where thicker stone tiles are to be used
  • WR Plasterboard NOT Allowed
  • 8mm Movement gap to slab
  • WATERPROOFER to seal gap with Polyurethane Sealant
  • 6mm fibre cement for typical tile or paint finish
  • 8mm gap to structural floor

Wall linings


  • 6mm fibre cement for typical tile or paint finish
  • 8mm gap to structural floor


Wall Lining SELECTION


NCC 2022 V4


  • 6mm fibre cement for typical tile or paint finish
  • 8mm gap to structural floor

Concrete Screeds