Flashing - Cover Building Codes & Rules


- Flashing - Cover Tools™ simplifies the National Construction Code (NCC) with interactive graphics, including deemed to comply & best practices.


Floor System

M

Waterproof

External Wall

Membrane

Fall

Structural Substrate

Screed

Finished Floor

Fall

Sealant

Finish Floor Level

Fillet

AS 4654.2:2012, 2.5.2

≥ 1 : 100AS 4654.2:2012, 2.5.2

AS 4654.2:2012, 2.8.1.3 (iii)

≥ 10AS 4654.2:2012, 2.8.1.3 (iii)

AS 4654.2:2012, 2.8.1.3 (ii)

≥ 75 lapAS 4654.2:2012, 2.8.1.3 (ii)

M

M

Top of Flashing

Top of Membrane

M

AS 4654.2:2012, 2.8.1.3 (i)

≥ 15AS 4654.2:2012, 2.8.1.3 (i)

M

AS 4654.2:2012, 2.5.2

≥ 1 : 100AS 4654.2:2012, 2.5.2

≥ 1 : 80

≥ 1 : 80

Over-Flashing

Sealant

Floor Finish


  • Fall to drainage
  • ≥ 1 : 100[1]
  • ≥ 1 : 80 recommended
  • ≥ P3 or R10 Slip Rating[2]


Surface FINISHES


NCC 2022 V4


All Building Classes


NCC 2022 F1D5, H2D8, & HP10.2 [2019 F1.4, 3.8.1.2, 3.8.1.3]


May 2023



AS 4654.2:2012, 2.15.2

AS 4654.2:2012, 2.15.2

NCC 2022 Vol 1, F1D5

NCC 2022 Vol 2, H2D8

NCC 2022 HP, 10.2.1

AS 4654.2:2012, 2.15.1

AS 4654.2:2012, 2.15.3

AS 4654.2:2012, 2.5.2

HB 198:2014, 5.1

Membrane


  • ≥ 1 : 100[1] fall to drainage
  • System compatible & to suit application[2]


Membrane AUDIT


NCC 2022 V1


All building classes


AS 4654.2 2012, 2.16


14 Sep 2012 to Current



Membrane RULES


NCC 2022 V5


All Building Classes


NCC 2022 F1D5, H2D8, & HP10.2 [2019 F1.4, 3.8.1.2, 3.8.1.3]


May 2023



AS 4654.2:2012, 2.5.2

NCC 2022 Vol 1, F1D5

NCC 2022 Vol 2, H2D8

NCC 2022 HP, 10.2.1

AS 4654.2:2012, 2.3

AS 4654.2:2012, 2.5.3

AS 4654.2:2012, 2.7

AS 4654.2:2012, 2.6.2

Waterproof Membrane BEST PRACTICE


NCC 2022 V1


AS 4654.2:2012, 2.5.2

AS 4654.2:2012, 2.5.1

Pressure Flashing

Film Thickness Test

Concrete Screeds

Fillet


  • 40 x 40mm[1] Sheet Membrane Fillet or Cove
  • 15 x 15mm[2] Liquid Membrane Fillet or Bond Breaker


Fillet RULES


NCC 2022 V4


All Building Classes


NCC 2022 F1D5, H2D8, & HP10.2 [2019 F1.4, 3.8.1.2, 3.8.1.3]


May 2023



AS 4654.2:2012, 2.7

NCC 2022 Vol 1, F1D5

NCC 2022 Vol 2, H2D8

NCC 2022 HP, 10.2.1

  • Building elements in Wet Areas to be Waterproof or Water-resistant to the NCCAS 4654.2:2012, 2.7NCC 2022 Vol 1, F1D5NCC 2022 Vol 2, H2D8
  • Membrane transitions from horizontal to vertical, or vertical to vertical planes, require the implementation of a Fillet, Cove, or Bond BreakerNCC 2022 HP, 10.2.1
  • 40 x 40mm Fillet or cove for Sheet Membrane
  • 15 x 15mm Fillet or Bond Breaker for Liquid Membrane

AS 4654.2:2012, 2.7

AS 4654.2:2012, 2.7

Over-flashing


  • ≤ 150mm[1] CTS Mechanical fixing for Pressure Seal Flashing


Over-flashing INSTALLATION


NCC 2022 V1


All Building Classes


NCC 2022 F1D5, H2D8, & HP10.2 [2019 F1.4, 3.8.1.2, 3.8.1.3]


May 2023



AS 4654.2:2012, 2.8.1.3

NCC 2022 Vol 1, F1D5

NCC 2022 Vol 2, H2D8

NCC 2022 HP, 10.2.1

AS 4654.2:2012, 2.8.1.3 (a)

Membrane Height


  • Height varies with wind class[1][2]


Membrane Height RULES


NCC 2022 V1


All Building Classes


NCC 2022 F1D5 [2019 Table F1.4]


May 2023



NCC 2022 Vol 1, F1D5

AS 4654.2:2012, 2.8.1.1

AS 4654.2:2012, A

  • A roof, balcony, podium or similar horizontal surface part of a building must be provided with a waterproofing membraneNCC 2022 Vol 1, F1D5
  • To AS 4654.1 & AS 4654.2
  • Unless is a deck or perforated or directly above ground
  • Measured from top of surface finish to height of membraneAS 4654.2:2012, 2.8.1.1
  • Height sufficient to prevent wind-driven water entry
  • Varies depending on wind class & level of protection
  • Termination heights to AS 4654.2 2012, Table A1 are minimum & informative onlyAS 4654.2:2012, A
  • Must be specified based on individual project wind classification

AS 4654.2:2012, 2.8.1.1

AS 4654.2:2012, A

Redirecting... (5)
Please wait while we redirect you to the correct page.