Parapet - Cavity Wall Building Codes & Rules


- Parapet - Cavity Wall Tools™ simplifies the National Construction Code (NCC) with interactive graphics, including deemed to comply & best practices.


M

M

Sealant

Top of Membrane

Finished Level

Screed

Weephole centres

DPC

Fall

Fall

- copy

AS 3700:2018, 4.7.2

≤ 1.2mAS 3700:2018, 4.7.2

Flashing

DPC if Parapet above

Roof Cladding

Concrete Screeds

Weepholes


  • ≤ 1.2m spacing[1]
  • Clear of building debris
  • Proprietary insert


Weephole RULES


NCC 2022 V3


Class 1 & 10


NCC 2022 H1D5 & HP5.7.5

[2019 3.3.1-3.3.3, 3.3.5-3.3.6, 3.3.5.9]


May 2023



AS 3700:2018, 4.7.2

NCC 2022 Vol 2, H1D5

NCC 2022 HP, 5.7.5

AS 3700:2018, 4.7.2

Gap Below

Flashing

DPC Embedded

in Mortar

Roof Structure

1 : 60

AS 4654.2:2012, 2.5.2

≥ 1 : 100AS 4654.2:2012, 2.5.2

Membrane

AS 4654.2:2012, 2.8.2.2

≥ 300AS 4654.2:2012, 2.8.2.2

AS 4654.2:2012, 2.8.1.3 (c)

≥ 10AS 4654.2:2012, 2.8.1.3 (c)

Coping

Fillet

AS 4654.2:2012, 2.5.2

≥ 1 : 100AS 4654.2:2012, 2.5.2

DPC

Flashing

M

M

M

Example

Roof Finish

Substrate

1 : 80

Fillet


  • 40 x 40mm[1] Sheet Membrane Fillet or Cove
  • 15 x 15mm[2] Liquid Membrane Fillet or Bond Breaker


Fillet RULES


NCC 2022 V4


All Building Classes


NCC 2022 F1D5, H2D8, & HP10.2 [2019 F1.4, 3.8.1.2, 3.8.1.3]


May 2023



AS 4654.2:2012, 2.7

NCC 2022 Vol 1, F1D5

NCC 2022 Vol 2, H2D8

NCC 2022 HP, 10.2.1

  • Building elements in Wet Areas to be Waterproof or Water-resistant to the NCCAS 4654.2:2012, 2.7NCC 2022 Vol 1, F1D5NCC 2022 Vol 2, H2D8
  • Membrane transitions from horizontal to vertical, or vertical to vertical planes, require the implementation of a Fillet, Cove, or Bond BreakerNCC 2022 HP, 10.2.1
  • 40 x 40mm Fillet or cove for Sheet Membrane
  • 15 x 15mm Fillet or Bond Breaker for Liquid Membrane

AS 4654.2:2012, 2.7

AS 4654.2:2012, 2.7

Membrane Height


  • Height varies with wind class[1][2]
  • Terminate with flashing, reglet or at drip groove[3][4]


Membrane Height RULES


NCC 2022 V1


All Building Classes


NCC 2022 F1D5 [2019 Table F1.4]


May 2023



NCC 2022 Vol 1, F1D5

AS 4654.2:2012, 2.8.1.1

AS 4654.2:2012, A

  • A roof, balcony, podium or similar horizontal surface part of a building must be provided with a waterproofing membraneNCC 2022 Vol 1, F1D5
  • To AS 4654.1 & AS 4654.2
  • Unless is a deck or perforated or directly above ground
  • Measured from top of surface finish to height of membraneAS 4654.2:2012, 2.8.1.1
  • Height sufficient to prevent wind-driven water entry
  • Varies depending on wind class & level of protection
  • Termination heights to AS 4654.2 2012, Table A1 are minimum & informative onlyAS 4654.2:2012, A
  • Must be specified based on individual project wind classification

AS 4654.2:2012, 2.8.1.1

AS 4654.2:2012, A

AS 4654.2:2012, 2.8.1.3

AS 4654.2:2012, 2.8.2.1

Floor Finish


  • Fall to drainage
  • ≥ 1 : 100[1]
  • ≥ 1 : 80 recommended
  • ≥ P3 or R10 Slip Rating[2]


Surface FINISHES


NCC 2022 V4


All Building Classes


NCC 2022 F1D5, H2D8, & HP10.2 [2019 F1.4, 3.8.1.2, 3.8.1.3]


May 2023



AS 4654.2:2012, 2.15.2

AS 4654.2:2012, 2.15.2

NCC 2022 Vol 1, F1D5

NCC 2022 Vol 2, H2D8

NCC 2022 HP, 10.2.1

AS 4654.2:2012, 2.15.1

AS 4654.2:2012, 2.15.3

HB 198:2014, 5.1

AS 4654.2:2012, 2.5.2

Membrane


  • ≥ 1 : 100[1] fall to drainage
  • ≥ 1 : 60 recommended
  • System compatible & to suit application[2]


Membrane AUDIT


NCC 2022 V1


All building classes


AS 4654.2 2012, 2.16


14 Sep 2012 to Current



Waterproof Membrane BEST PRACTICE


NCC 2022 V1


Membrane RULES


NCC 2022 V5


All Building Classes


NCC 2022 F1D5, H2D8, & HP10.2 [2019 F1.4, 3.8.1.2, 3.8.1.3]


May 2023



AS 4654.2:2012, 2.5.2

NCC 2022 Vol 1, F1D5

NCC 2022 Vol 2, H2D8

NCC 2022 HP, 10.2.1

AS 4654.2:2012, 2.3

AS 4654.2:2012, 2.5.3

AS 4654.2:2012, 2.7

AS 4654.2:2012, 2.6.2

AS 4654.2:2012, 2.5.1

AS 4654.2:2012, 2.5.2