Planter Box Building Codes & Rules


- Planter Box Tools™ simplifies the National Construction Code (NCC) with interactive graphics, including deemed to comply & best practices.


Finished Floor

Fillet around

Starter Bar

Leak Control

Flange

Membrane Height

Compatible

Sealant

Overflow Relief


  • Suitable overflow with Screw Cap for inspection
  • Finish height to be below upper edge of Membrane


Overflow Relief


NCC 2022 V1


All Building Classes


AS 4654.2 2012, 2.13


14 Sep 2012 to Current



  • The Planter Box should be provided with a suitable Overflow & be designed for an appropriate rainfall intensity
  • Screw Cap for clearing access
  • Suitable overflow with Screw Cap for inspection
  • Finish height to be below upper edge of Membrane

75

Fall

M

M

Drainage

Outlet

M

M

Substrate

Membrane

Fillet Surround

to Penetration

Cast in Clamp

Floor Waste

Pressure or Over Flashing

Fall

Fillet

Drainage Cell

Capping

Geo-Filter Fabric

Fall

Inspection

Opening

Fillet

Wall

Over

Flashing

M

M

Fall

- copy

Reinforcement

Membrane

20

Membrane

Substrate

PVC Conduit

M

M

Install Protection Board to

minimise root damage to

the Membrane

AS 4654.2:2012, 2.13

≥ 100AS 4654.2:2012, 2.13

AS 4654.2:2012, 2.5.2

AS 4654.2:2012, 2.13

≥ 1:100AS 4654.2:2012, 2.5.2AS 4654.2:2012, 2.13

AS 4654.2:2012, 2.5.2

AS 4654.2:2012, 2.13

≥ 1:100AS 4654.2:2012, 2.5.2AS 4654.2:2012, 2.13

Bond Breaker

  • ≥ 12mm depth for Bond Breakers at Floor/Wall Junction & intersections

AS 4654.2:2012, 2.13

Account for Mulch thickness when measuring the actual Soil LevelAS 4654.2:2012, 2.13

Geo-Filter Fabric to

turn up & secure

M

M

Membrane

Fill Level

Fall

M

M

M

Protection Board

Fillet

Leak Control

Flange

Site Tools

Exposed Walls


  • Fully waterproofed to prevent failure of the internal Planter Box Membrane
  • Terminate Membrane with Capping to provide protection for exposed top surface


Planter Box Walls


NCC 2022 V2


  • Concrete Wall
  • ≥ r 12mm arrised edge all external corners
  • Concrete Wall to structural engineers' details
  • Blockwork Wall
  • Elastomeric coating to rendered planter wall Capping
  • Blockwork Wall to structural engineers' details
  • Trim render short of Slab & Seal
  • Sawn Reglet
  • 20mm deep & filled with compatible Sealant
  • PVC coated Flashing sealed & mechanically fastened into Sawn Reglet
  • Membrane termination under Flashing
  • Polyester Bandage over Flashing to properly seal all gaps
  • Fully waterproofed to prevent failure of the internal Planter Box Membrane
  • Terminate Membrane with Capping to provide protection for exposed top surface

Over Flashing

Membrane


  • ≥ 100mm from top of the soil surface[1]
  • Class III[2] Membrane has High Extensibility & allows for even thickness


Movement


NCC 2022 V1


All Building Classes


NCC 2022 F1D5, H2D8, & HP10.2 [2019 F1.4, 3.8.1.2, 3.8.1.3]


May 2023



AS 4654.2:2012, 2.3

NCC 2022 Vol 1, F1D5

NCC 2022 Vol 2, H2D8

NCC 2022 HP, 10.2.1

Membrane Application


NCC 2022 V1


AS 4654.2:2012, 2.13

AS 4654.1:2012, A2

Pressure Flashing

Falls


  • ≥ 1:100 to Drainage Outlet[1]


Fall RULES


NCC 2022 V3


All Building Classes


NCC 2022 F1D5, H2D8, & HP10.2 [2019 F1.4, 3.8.1.2, 3.8.1.3]


May 2023



AS 4654.2:2012, 2.5.2

NCC 2022 Vol 1, F1D5

NCC 2022 Vol 2, H2D8

NCC 2022 HP, 10.2.1

AS 4654.2:2012, 2.5.2

Fillet


  • 40x40mm Sheet Membrane[1]
  • 15x15mm Liquid Membrane[2]


Fillet RULES


NCC 2022 V4


All Building Classes


NCC 2022 F1D5, H2D8, & HP10.2 [2019 F1.4, 3.8.1.2, 3.8.1.3]


May 2023



AS 4654.2:2012, 2.7

NCC 2022 Vol 1, F1D5

NCC 2022 Vol 2, H2D8

NCC 2022 HP, 10.2.1

  • Building elements in Wet Areas to be Waterproof or Water-resistant to the NCCAS 4654.2:2012, 2.7NCC 2022 Vol 1, F1D5NCC 2022 Vol 2, H2D8
  • Membrane transitions from horizontal to vertical, or vertical to vertical planes, require the implementation of a Fillet, Cove, or Bond BreakerNCC 2022 HP, 10.2.1
  • 40 x 40mm Fillet or cove for Sheet Membrane
  • 15 x 15mm Fillet or Bond Breaker for Liquid Membrane

AS 4654.2:2012, 2.7

AS 4654.2:2012, 2.7

Drainage


  • Pipe perforation for vertical drainage slits[1]
  • Discharge to the Storm Water Collection System[2]


Drainage RULES


NCC 2022 V1


All Building Classes


NCC 2022 F1D5, H2D8, & HP10.2 [2019 F1.4, 3.8.1.2, 3.8.1.3]


May 2023



AS 4654.2:2012, 2.13

NCC 2022 Vol 1, F1D5

NCC 2022 Vol 2, H2D8

NCC 2022 HP, 10.2.1

  • Building elements in Wet Areas to be Waterproof or Water-resistant to the NCCAS 4654.2:2012, 2.13NCC 2022 Vol 1, F1D5NCC 2022 Vol 2, H2D8
  • Drainage Outlet to be connected to Storm Water System for proper dischargeNCC 2022 HP, 10.2.1
  • Membranes shall be sealed to Drainage Outlet
  • Pipe is perforated with vertical slots to function as drainage conduit
  • Geo-filter fabric extends up & is fixed to the Pipe above the Drainage Outlet
  • Finished base of Planter Box to be sloped with a gradual incline leading to Drainage Outlet

Planter Drainage


NCC 2022 V1


AS 4654.2:2012, 2.13

AS 4654.2:2012, 2.13

Penetrations


  • Conduit size to suit contents
  • All Joints watertight


  • Conduit size to suit contents
  • All Joints watertight