All Building Classes
NCC 2022 J5D5, H6D2, & HP13.4.4 [2019 J3.4, 3.12.0, 3.12.3.3]
May 2023
Substrate
- Smooth, clean, dry & dust free surface[1]
Substrate RULES
NCC 2022 V3
All Building Classes
NCC 2022 F1D5, H2D8, & HP10.2 [2019 F1.4, 3.8.1.2, 3.8.1.3]
May 2023
AS 4654.2:2012, 2.5.1
AS 4654.2:2012, 2.5.1
NCC 2022 Vol 1, F1D5
NCC 2022 Vol 2, H2D8
NCC 2022 HP, 10.2.6
Liquid applied membrane PREPARATION
NCC 2022 V2
All Building Classes
NCC 2022 F1D5, H2D8, & HP10.2 [2019 F1.4, 3.8.1.2, 3.8.1.3]
May 2023
AS 4654.2:2012, 2.5.3.1
NCC 2022 Vol 1, F1D5
NCC 2022 Vol 2, H2D8
NCC 2022 HP, 10.2.1
AS 4654.2:2012, 2.5.3.1
Substrate PREPARATION
NCC 2022 V1
Partially bonded membrane PREPARATION
NCC 2022 V2
All Building Classes
NCC 2022 F1D5, H2D8, & HP10.2 [2019 F1.4, 3.8.1.2, 3.8.1.3]
May 2023
AS 4654.2:2012, 2.5.3.2
AS 4654.2:2012, 2.5.3.2
NCC 2022 Vol 1, F1D5
NCC 2022 Vol 2, H2D8
NCC 2022 HP, 10.2.1
Unbonded membrane PREPARATION
NCC 2022 V3
All Building Classes
NCC 2022 F1D5, H2D8, & HP10.2 [2019 F1.4, 3.8.1.2, 3.8.1.3]
May 2023
AS 4654.2:2012, 2.5.3.3
NCC 2022 Vol 1, F1D5
NCC 2022 Vol 2, H2D8
NCC 2022 HP, 10.2.1
AS 4654.2:2012, 2.5.3
Zero Threshold
Termite Control
- Termite control required for Ground Level floor junctions[1]
- ≥ 75mm[2] slab exposure above the external finished floor level to allow easy detection of termites
Termite MANAGEMENT
NCC 2022 V4
Class 1 & 10
NCC 2022 H1D3 & HP3.4.2 [2019 3.1.4.3]
May 2023
NCC 2022 HP, 3.4.2
AS 3660.1:2014, 4.4
NCC 2022 Vol 2, H1D3
- Termite Management compliant to the NCCNCC 2022 HP, 3.4.2
- Inspection ZoneAS 3660.1:2014, 4.4NCC 2022 Vol 2, H1D3
- ≥ 75mm exposed Concrete Face
- Off form, smooth surface, free of Ripples or Honeycombing
- Tiling, Render, Vapour Barrier, Flashings, Structures & the like, not allowed to bridge this Zone
Termite RISK
NCC 2022 V3
Class 1 & 10
NCC 2022, H1D3 & HP3.4.1 [2019 3.1.4.2]
May 2023
NCC 2022 HP, 3.4.1(2)
NCC 2022 HP, 3.4.1 (1) (b)
NCC 2022 HP, 3.4.1
- Termite Management System Required ifNCC 2022 HP, 3.4.1(2)
- Location is identified at Risk of Attack, &
- Any Primary Building Element is susceptible
- Primary Building Elements areNCC 2022 HP, 3.4.1 (1) (b)
- Any member designed to take Loads
- Wall, Roof, Ceiling, Floor, Ramp or Stair Framing
- Any bracing or other framing members
- Materials not susceptible to attackNCC 2022 HP, 3.4.1
- Metals
- Concrete
- Masonry
- Fibre-reinforced Concrete
- Naturally resistant Timber
- Preservative-treated Timber
NCC 2022 HP, 3.4.1
AS 3660.1:2014, 4.4
- Termite control required for Ground Level floor junctionsNCC 2022 HP, 3.4.1
- ≥ 75mmAS 3660.1:2014, 4.4 slab exposure above the external finished floor level to allow easy detection of termites
Floor Finish
- ≥ 1 : 100[1] fall to Drainage
- ≥ P3 or R10 Slip Rating[2]
Surface FINISHES
NCC 2022 V4
All Building Classes
NCC 2022 F1D5, H2D8, & HP10.2 [2019 F1.4, 3.8.1.2, 3.8.1.3]
May 2023
AS 4654.2:2012, 2.15.2
AS 4654.2:2012, 2.15.2
NCC 2022 Vol 1, F1D5
NCC 2022 Vol 2, H2D8
NCC 2022 HP, 10.2.1
AS 4654.2:2012, 2.15.1
AS 4654.2:2012, 2.15.3
AS 4654.2:2012, 2.5.2
HB 198:2014, 5.1
Sub-sill with Set Down
Membrane
- ≥ 1 : 100[1] fall to Drainage
- System compatible & to suit application[2]
Membrane AUDIT
NCC 2022 V1
All building classes
AS 4654.2 2012, 2.16
14 Sep 2012 to Current
Membrane RULES
NCC 2022 V5
All Building Classes
NCC 2022 F1D5, H2D8, & HP10.2 [2019 F1.4, 3.8.1.2, 3.8.1.3]
May 2023
AS 4654.2:2012, 2.5.2
NCC 2022 Vol 1, F1D5
NCC 2022 Vol 2, H2D8
NCC 2022 HP, 10.2.1
AS 4654.2:2012, 2.3
AS 4654.2:2012, 2.5.3
AS 4654.2:2012, 2.7
AS 4654.2:2012, 2.6.2
- Building elements in Wet Areas to be Waterproof or Water Resistant to the NCCAS 4654.2:2012, 2.5.2NCC 2022 Vol 1, F1D5NCC 2022 Vol 2, H2D8
- FallsNCC 2022 HP, 10.2.1
- ≥ 1 : 100 fall in Membrane to Drainage Outlet
- Structural Substrate or Screed to form the required Falls
- Design & installation in accordance with AS 4654.1AS 4654.2:2012, 2.3
- Membrane movement Class I, II, or III
- To suit intended service conditions
- Substrate to be smooth, clean, dry & dust-freeAS 4654.2:2012, 2.5.3
- Fillets & Bond Breakers installed on all cornersAS 4654.2:2012, 2.7
- Lay & allow to cure as per Manufacturer's RecommendationsAS 4654.2:2012, 2.6.2
Waterproof Membrane BEST PRACTICE
NCC 2022 V1
AS 4654.2:2012, 2.5.2
AS 4654.2:2012, 2.5.1
Membrane Height
- Height varies with wind class[1]
Height RULES
NCC 2022 V7
All Building Classes
NCC 2022 F1D5, H2D8, & HP10.2 [2019 F1.4, 3.8.1.2, 3.8.1.3]
May 2023
AS 4654.2:2012, 2.8.1
NCC 2022 Vol 1, F1D5
NCC 2022 Vol 2, H2D8
NCC 2022 HP, 10.2.1
- Building elements in Wet Areas to be Waterproof or Water Resistant to the NCCAS 4654.2:2012, 2.8.1NCC 2022 Vol 1, F1D5NCC 2022 Vol 2, H2D8
- Measured from top of finished external level to height of MembraneNCC 2022 HP, 10.2.1
- FFL in the case of a finish on a Screed Bed, or
- Base of Linear Drain at Zero Threshold Entry, or
- Substrate Membrane where Pavers on Pedestals
- Height sufficient to prevent wind-driven water entry
AS 4654.2:2012, 2.8.1.1
External Waterproofing Overview