Wet Area Safety (Electrical) Building Codes & Rules


- Wet Area Electrical Safety Tools™ simplifies the National Construction Code (NCC) with interactive graphics, including deemed to comply & best practices.


AS/NZS 3000:2018, 6.2.2.1 (d) (i)

r 600AS/NZS 3000:2018, 6.2.2.1 (d) (i)

AS/NZS 3000:2018, 6.2.2.2 (b) (ii)

400AS/NZS 3000:2018, 6.2.2.2 (b) (ii)

AS/NZS 3000:2018, 6.2.2.1 (c) (ii)

≥ 1.8mAS/NZS 3000:2018, 6.2.2.1 (c) (ii)

AS/NZS 3000:2018, 6.2.2.1 (e) (i)

2.4mAS/NZS 3000:2018, 6.2.2.1 (e) (i)

Zone 3

AS/NZS 3000:2018, 6.2.2.1 (b) (iv)

AS/NZS 3000:2018, 6.2.2.1 (c) (ii)

Bathtub ZONE 1

If contains a shower AS/NZS 3000:2018, 6.2.2.1 (c) (ii)

  • r 1.2m from Wall fixed Shower
  • ≥ 1.8m fixed Screen can limit ZONE 1

AS/NZS 3000:2018, 6.2.2.1 (d) (i)

Shower ZONE 2

AS/NZS 3000:2018, 6.2.2.1 (e) (i)

Shower ZONE 3

AS/NZS 3000:2018, 6.2.2.1 (e) (ii)

AS/NZS 3000:2018, 6.2.2.1 (e) (iv)

Shower ZONE 3

AS/NZS 3000:2018, 6.2.2.1 (c) (ii)

AS/NZS 3000:2018, 6.2.2.1 (c) (iii) (A)

Shower ZONE 1

AS/NZS 3000:2018, 6.2.2.1 (d) (ii)

Shower ZONE 2

AS/NZS 3000:2018, 6.2.2.1 (e) (iv)

AS/NZS 3000:2018, 6.2.2.1 (e) (i)

Bathtub ZONE 3

AS/NZS 3000:2018, 6.2.2.1 (d) (ii)

2.25mAS/NZS 3000:2018, 6.2.2.1 (d) (ii)

AS/NZS 3000:2018, 6.2.2.1 (d) (i)

600AS/NZS 3000:2018, 6.2.2.1 (d) (i)

AS/NZS 3000:2018, 6.2.2.1 (a)

Shower ZONE 0

AS/NZS 3000:2018, 6.2.2.1 (d) (ii)

AS/NZS 3000:2018, 6.2.2.1 (d) (i)

Bathtub ZONE 2

AS/NZS 3000:2018, 2.6.2.2.1 (e) (i)

Bathtub ZONE 3

≤ 40L

Zone 0

AS/NZS 3000:2018, 6.2.2.2 (b) (i)

150AS/NZS 3000:2018, 6.2.2.2 (b) (i)

Zone 2

Flexible Hose

Tapware

AS/NZS 3000:2018, 6.2.2.1 (d) (i)

Bathtub ZONE 2

Must be above

shower head

Zone 2

AS/NZS 3000:2018, 6.2.4.7

300AS/NZS 3000:2018, 6.2.4.7

Zone 3

Zone 3

Zone 2

Zone 1

Zone 2

Ceiling

  • No restrictions if > 2.5m

AS/NZS 3000:2018, 6.2.2.1 (c) (iv)

AS/NZS 3000:2018, 6.2.2.1 (c) (ii)

Shower ZONE 1

≥ 40L

AS/NZS 3000:2018, 6.2.2.1 (a)

Bathtub ZONE 0

Zone 2

Zone 0

Zone 0

AS/NZS 3000:2018, 6.2.2.2 (c) (ii)

1mAS/NZS 3000:2018, 6.2.2.2 (c) (ii)

Outdoor Safety (Electrical)

AS/NZS 3000:2018, 6.2.2.1 (c) (iii) (A)

r 600AS/NZS 3000:2018, 6.2.2.1 (c) (iii) (A)

AS/NZS 3000:2018, 6.2.2.1 (c) (iv)

2.5mAS/NZS 3000:2018, 6.2.2.1 (c) (iv)

AS/NZS 3000:2018, 6.2.2.1 (c) (ii)

r 1.2mAS/NZS 3000:2018, 6.2.2.1 (c) (ii)

AS/NZS 3000:2018, 6.2.2.1 (c) (iii) (A)

600AS/NZS 3000:2018, 6.2.2.1 (c) (iii) (A)

Zone 2

Zone 2

Zone 1

AS/NZS 3000:2018, 6.2.2.2 (b) (i)

150AS/NZS 3000:2018, 6.2.2.2 (b) (i)

AS/NZS 3000:2018, 6.2.2.2 (c) (i)

500AS/NZS 3000:2018, 6.2.2.2 (c) (i)

AS/NZS 3000:2018, 6.2.2.2 (b) (i)

150AS/NZS 3000:2018, 6.2.2.2 (b) (i)

AS/NZS 3000:2018, 6.2.2.2 (b) (i)

150AS/NZS 3000:2018, 6.2.2.2 (b) (i)

AS/NZS 3000:2018, 6.2.2.2 (b) (ii)

400AS/NZS 3000:2018, 6.2.2.2 (b) (ii)

AS/NZS 3000:2018, 6.2.2.2 (b) (i)

150AS/NZS 3000:2018, 6.2.2.2 (b) (i)

AS/NZS 3000:2018, 6.2.2.2 (b) (i)

150AS/NZS 3000:2018, 6.2.2.2 (b) (i)

AS/NZS 3000:2018, 6.2.2.2 (c) (ii)

1mAS/NZS 3000:2018, 6.2.2.2 (c) (ii)

AS/NZS 3000:2018, 6.2.2.2 (c) (ii)

1mAS/NZS 3000:2018, 6.2.2.2 (c) (ii)

AS/NZS 3000:2018, 6.2.2.2 (c) (ii)

1mAS/NZS 3000:2018, 6.2.2.2 (c) (ii)

AS/NZS 3000:2018, 6.2.2.2 (c) (i)

500AS/NZS 3000:2018, 6.2.2.2 (c) (i)

Zone 0

Zone 2

AS/NZS 3000:2018, 6.2.2.1 (d) (ii)

2.25mAS/NZS 3000:2018, 6.2.2.1 (d) (ii)

AS/NZS 3000:2018, 6.2.2.1 (d) (i)

600AS/NZS 3000:2018, 6.2.2.1 (d) (i)

AS/NZS 3000:2018, 6.2.2.1 (c) (iii) (A)

600AS/NZS 3000:2018, 6.2.2.1 (c) (iii) (A)

AS/NZS 3000:2018, 6.2.2.2 (c) (i)

500AS/NZS 3000:2018, 6.2.2.2 (c) (i)

Zone 2

Zone 2

Shower Zone 3


  • < 300mm Socket Outlets & Switches from FFL are prohibited[1]


Zone 3 Electrical RULES


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (e) (i)

AS/NZS 3000:2018, 2.6.2.2.1 (e) (ii)

AS/NZS 3000:2018, 2.6.2.2.1 (e) (iv)

Shower ZONE 3


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (e) (i)

AS/NZS 3000:2018, 6.2.2.1 (e) (i)

AS/NZS 3000:2018, 6.2.2.1 (e) (ii)

AS/NZS 3000:2018, 6.2.2.1 (e) (iv)

AS/NZS 3000:2018, 6.2.4.7

Fixed

Tapware

Socket Outlets


  • < 300mm from FFL is prohibited[1]


Zone 3 Electrical RULES


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (e) (i)

AS/NZS 3000:2018, 2.6.2.2.1 (e) (ii)

AS/NZS 3000:2018, 2.6.2.2.1 (e) (iv)

AS/NZS 3000:2018, 6.2.4.7

Designer & Construction Set Out

Socket Outlets


  • < 300mm from FFL are prohibited[1]


Zone 3 Electrical RULES


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (e) (i)

AS/NZS 3000:2018, 2.6.2.2.1 (e) (ii)

AS/NZS 3000:2018, 2.6.2.2.1 (e) (iv)

AS/NZS 3000:2018, 6.2.4.7

Washbasin Zone 2


  • Socket outlets AS/NZS 3194 compliant[1]
  • IPX4 Switches, Luminaires & Exhaust Fans[2]


Washbasin ZONE 2


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.2 (c) (i)

AS/NZS 3000:2018, 6.2.2.2 (c) (ii)

Zone 2 Electrical RULES


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (d) (i)

AS/NZS 3000:2018, 6.2.2.1 (d) (ii)

AS/NZS 3000:2018, 6.2.2.2 (b) (i)

AS/NZS 3000:2018, 6.2.2.2 (b) (ii)

AS/NZS 3000:2018, 6.2.2.2 (c) (i)

AS/NZS 3000:2018, 6.2.2.2 (c) (ii)


AS/NZS 3000:2018, 6.2.4.7

AS/NZS 3000:2018, 6.2.4.7

Bathtub Zone 3


  • < 300mm Socket Outlets & Switches from FFL are prohibited[1]


Bathtub ZONE 3


NCC 2022 V2


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (e) (i)

AS/NZS 3000:2018, 6.2.2.1 (e) (i)

AS/NZS 3000:2018, 6.2.2.1 (e) (ii)

AS/NZS 3000:2018, 6.2.2.1 (e) (iv)

Zone 3 Electrical RULES


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (e) (i)

AS/NZS 3000:2018, 2.6.2.2.1 (e) (ii)

AS/NZS 3000:2018, 2.6.2.2.1 (e) (iv)

AS/NZS 3000:2018, 6.2.4.7

Shower Zone 1


  • Socket outlets are prohibited[1]
  • IPX4 for Switches, Luminaires & Exhaust Fans[2]


Shower ZONE 1


NCC 2022 V1


All Building Classes


NCC 2022 S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, C2.13, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (c) (i)

AS/NZS 3000:2018, 6.2.2.1 (c) (ii)

AS/NZS 3000:2018, 6.2.2.1 (c) (ii)

AS/NZS 3000:2018, 6.2.2.1 (c) (iii) (A)

AS/NZS 3000:2018, 6.2.2.1 (c) (iv)

ZONE 1 Electrical RULES


NCC 2022 V2


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (b) (iv)

AS/NZS 3000:2018, 6.2.2.1 (c) (iv)

AS/NZS 3000:2018, 6.2.2.1 (b) (iii)

AS/NZS 3000:2018, 6.2.2.1 (c) (ii)

AS/NZS 3000:2018, 6.2.2.1 (c) (ii)

AS/NZS 3000:2018, 6.2.2.1 (c) (iii) (A)

AS/NZS 3000:2018, 6.2.4.7

AS/NZS 3000:2018, 6.2.4.7

Shower Zone 0


  • Socket & switches outlets not permitted[1]
  • IPX7 for Luminaires & Exhaust Fans[2]


Shower ZONE 0


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (a)

  • Building elements requiring energy use to be protected, secure, & energy efficient to NCC Specifications 1 & 13, Parts C3D14, C4D15, J2D2, 13.4, & AS/NZS 3000
  • Defines the interior area of the Shower or recessAS/NZS 3000:2018, 6.2.2.1 (a)

Zone 0 Electrical RULES


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (a)

  • Building elements requiring energy use to be protected, secure, & energy efficient to NCC Specifications 1 & 13, Parts C3D14, C4D15, J2D2, 13.4, & AS/NZS 3000
  • Bath & Shower Limits
  • ZONE 0 Defines Shower base or inside of a BathAS/NZS 3000:2018, 6.2.2.1 (a)

AS/NZS 3000:2018, 6.2.4.7

AS/NZS 3000:2018, 6.2.4.7

Bathtub Zone 1


  • Socket outlets are prohibited[1]
  • IPX4 for Switches, Luminaires & Exhaust Fans[2]


Bathtub ZONE 1


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (b) (i)

AS/NZS 3000:2018, 6.2.2.1 (b) (iv)

AS/NZS 3000:2018, 6.2.2.1 (b) (iii)

AS/NZS 3000:2018, 6.2.2.1 (b) (vi)

ZONE 1 Electrical RULES


NCC 2022 V2


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (b) (iv)

AS/NZS 3000:2018, 6.2.2.1 (c) (iv)

AS/NZS 3000:2018, 6.2.2.1 (b) (iii)

AS/NZS 3000:2018, 6.2.2.1 (c) (ii)

AS/NZS 3000:2018, 6.2.2.1 (c) (ii)

AS/NZS 3000:2018, 6.2.2.1 (c) (iii) (A)

AS/NZS 3000:2018, 6.2.4.7

AS/NZS 3000:2018, 6.2.4.7

Bathtub Zone 2


  • Socket outlet AS/NZS 3194 compliant[1]
  • IPX4 for Switches, Luminaires & Exhaust Fans[2]


Zone 2 Electrical RULES


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (d) (i)

AS/NZS 3000:2018, 6.2.2.1 (d) (ii)

AS/NZS 3000:2018, 6.2.2.2 (b) (i)

AS/NZS 3000:2018, 6.2.2.2 (b) (ii)

AS/NZS 3000:2018, 6.2.2.2 (c) (i)

AS/NZS 3000:2018, 6.2.2.2 (c) (ii)


Bathtub ZONE 2


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 2.6.2.2.1 (d) (i)

AS/NZS 3000:2018, 6.2.2.1 (d) (i)

AS/NZS 3000:2018, 6.2.2.1 (d) (ii)

AS/NZS 3000:2018, 6.2.4.7

AS/NZS 3000:2018, 6.2.4.7

Socket Outlets


  • < 300mm from FFL is prohibited[1]


Zone 3 Electrical RULES


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (e) (i)

AS/NZS 3000:2018, 2.6.2.2.1 (e) (ii)

AS/NZS 3000:2018, 2.6.2.2.1 (e) (iv)

AS/NZS 3000:2018, 6.2.4.7

Bathtub Zone 3


  • < 300mm Socket Outlets & Switches from FFL are prohibited[1]


Bathtub ZONE 3


NCC 2022 V2


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (e) (i)

AS/NZS 3000:2018, 6.2.2.1 (e) (i)

AS/NZS 3000:2018, 6.2.2.1 (e) (ii)

AS/NZS 3000:2018, 6.2.2.1 (e) (iv)

Zone 3 Electrical RULES


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (e) (i)

AS/NZS 3000:2018, 2.6.2.2.1 (e) (ii)

AS/NZS 3000:2018, 2.6.2.2.1 (e) (iv)

AS/NZS 3000:2018, 6.2.4.7

Washbasin Zone 2


  • Socket outlets AS/NZS 3194 compliant[1]
  • IPX4 Switches, Luminaires & Exhaust Fans[2]


Zone 2 Electrical RULES


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (d) (i)

AS/NZS 3000:2018, 6.2.2.1 (d) (ii)

AS/NZS 3000:2018, 6.2.2.2 (b) (i)

AS/NZS 3000:2018, 6.2.2.2 (b) (ii)

AS/NZS 3000:2018, 6.2.2.2 (c) (i)

AS/NZS 3000:2018, 6.2.2.2 (c) (ii)


Washbasin ZONE 2


NCC 2022 V2


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.2 (b) (i)

AS/NZS 3000:2018, 6.2.2.2 (b) (ii)

AS/NZS 3000:2018, 6.2.4.7

AS/NZS 3000:2018, 6.2.4.7

Shower Zone 1


  • Socket Outlets are prohibited[1]
  • IPX4 Switches, Luminaires & Exhaust Fans[2]


Shower ZONE 1


NCC 2022 V1


All Building Classes


NCC 2022 S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, C2.13, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (c) (i)

AS/NZS 3000:2018, 6.2.2.1 (c) (ii)

AS/NZS 3000:2018, 6.2.2.1 (c) (ii)

AS/NZS 3000:2018, 6.2.2.1 (c) (iii) (A)

AS/NZS 3000:2018, 6.2.2.1 (c) (iv)

ZONE 1 Electrical RULES


NCC 2022 V2


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (b) (iv)

AS/NZS 3000:2018, 6.2.2.1 (c) (iv)

AS/NZS 3000:2018, 6.2.2.1 (b) (iii)

AS/NZS 3000:2018, 6.2.2.1 (c) (ii)

AS/NZS 3000:2018, 6.2.2.1 (c) (ii)

AS/NZS 3000:2018, 6.2.2.1 (c) (iii) (A)

AS/NZS 3000:2018, 6.2.4.7

AS/NZS 3000:2018, 6.2.4.7

Bathtub Zone 0


  • Socket & Switches outlets are prohibited[1]
  • IPX7 for Luminaires & Exhaust Fans[2]


Zone 0 Electrical RULES


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (a)

  • Building elements requiring energy use to be protected, secure, & energy efficient to NCC Specifications 1 & 13, Parts C3D14, C4D15, J2D2, 13.4, & AS/NZS 3000
  • Bath & Shower Limits
  • ZONE 0 Defines Shower base or inside of a BathAS/NZS 3000:2018, 6.2.2.1 (a)

Bathtub ZONE 0


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (a)

  • Building elements requiring energy use to be protected, secure, & energy efficient to NCC Specifications 1 & 13, Parts C3D14, C4D15, J2D2, 13.4, & AS/NZS 3000
  • Defines the internal area of the bathtubAS/NZS 3000:2018, 6.2.2.1 (a)

AS/NZS 3000:2018, 6.2.4.7

AS/NZS 3000:2018, 6.2.4.7

Washbasin Zone 0


  • Socket outlets & Switches are prohibited[1]
  • IPX7 for Luminaires & Exhaust Fans[2]


Zone 0 Electrical RULES


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (a)

  • Building elements requiring energy use to be protected, secure, & energy efficient to NCC Specifications 1 & 13, Parts C3D14, C4D15, J2D2, 13.4, & AS/NZS 3000
  • Bath & Shower Limits
  • ZONE 0 Defines Shower base or inside of a BathAS/NZS 3000:2018, 6.2.2.1 (a)

Washbasin ZONE 0


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (a)

  • Building elements requiring energy use to be protected, secure, & energy efficient to NCC Specifications 1 & 13, Parts C3D14, C4D15, J2D2, 13.4, & AS/NZS 3000
  • Defines the internal area of the sinkAS/NZS 3000:2018, 6.2.2.1 (a)

AS/NZS 3000:2018, 6.2.4.7

AS/NZS 3000:2018, 6.2.4.7

Bathtub Zone 2


  • Socket outlet AS/NZS 3194 compliant[1][2]
  • IPX4 for Switches, Luminaires & Exhaust Fans[3]


Zone 2 Electrical RULES


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (d) (i)

AS/NZS 3000:2018, 6.2.2.1 (d) (ii)

AS/NZS 3000:2018, 6.2.2.2 (b) (i)

AS/NZS 3000:2018, 6.2.2.2 (b) (ii)

AS/NZS 3000:2018, 6.2.2.2 (c) (i)

AS/NZS 3000:2018, 6.2.2.2 (c) (ii)


Bathtub ZONE 2


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 2.6.2.2.1 (d) (i)

AS/NZS 3000:2018, 6.2.2.1 (d) (i)

AS/NZS 3000:2018, 6.2.2.1 (d) (ii)

AS/NZS 3000:2018, 6.2.4.7

AS/NZS 3000:2018, 6.2.4.7

AS/NZS 3000:2018, 4.4.1.1.2 (a)

Basin Zone 2


  • Shaver outlets AS/NZS 3194 compliant[1][2]
  • IPX4 Switches & Luminaires[3]


Zone 2 Electrical RULES


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (d) (i)

AS/NZS 3000:2018, 6.2.2.1 (d) (ii)

AS/NZS 3000:2018, 6.2.2.2 (b) (i)

AS/NZS 3000:2018, 6.2.2.2 (b) (ii)

AS/NZS 3000:2018, 6.2.2.2 (c) (i)

AS/NZS 3000:2018, 6.2.2.2 (c) (ii)


Shower ZONE 2


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (d) (i)

AS/NZS 3000:2018, 6.2.2.1 (d) (i)

AS/NZS 3000:2018, 2.6.2.2.1 (d) (ii)

AS/NZS 3000:2018, 6.2.4.7

AS/NZS 3000:2018, 6.2.4.7

AS/NZS 3000:2018, 4.4.1.1.2 (a)

Shower Zone 2


  • IPX4 Switches, Luminaires & Exhaust Fans[1]


Zone 2 Electrical RULES


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (d) (i)

AS/NZS 3000:2018, 6.2.2.1 (d) (ii)

AS/NZS 3000:2018, 6.2.2.2 (b) (i)

AS/NZS 3000:2018, 6.2.2.2 (b) (ii)

AS/NZS 3000:2018, 6.2.2.2 (c) (i)

AS/NZS 3000:2018, 6.2.2.2 (c) (ii)


Shower ZONE 2


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (d) (i)

AS/NZS 3000:2018, 6.2.2.1 (d) (i)

AS/NZS 3000:2018, 2.6.2.2.1 (d) (ii)

AS/NZS 3000:2018, 6.2.4.7

Washbasin Zone 0


  • Socket outlets & Switches are prohibited[1]
  • IPX7 for Luminaires & Exhaust Fans[2]


Zone 0 Electrical RULES


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (a)

  • Building elements requiring energy use to be protected, secure, & energy efficient to NCC Specifications 1 & 13, Parts C3D14, C4D15, J2D2, 13.4, & AS/NZS 3000
  • Bath & Shower Limits
  • ZONE 0 Defines Shower base or inside of a BathAS/NZS 3000:2018, 6.2.2.1 (a)

Washbasin ZONE 0


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (a)

  • Building elements requiring energy use to be protected, secure, & energy efficient to NCC Specifications 1 & 13, Parts C3D14, C4D15, J2D2, 13.4, & AS/NZS 3000
  • Defines the internal area of the sinkAS/NZS 3000:2018, 6.2.2.1 (a)

AS/NZS 3000:2018, 6.2.4.7

AS/NZS 3000:2018, 6.2.4.7

Shower Zone 2


  • Socket outlets AS/NZS 3194 compliant[1][2]
  • IPX4 Switches, Luminaires & Exhaust Fans[3]


Zone 2 Electrical RULES


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (d) (i)

AS/NZS 3000:2018, 6.2.2.1 (d) (ii)

AS/NZS 3000:2018, 6.2.2.2 (b) (i)

AS/NZS 3000:2018, 6.2.2.2 (b) (ii)

AS/NZS 3000:2018, 6.2.2.2 (c) (i)

AS/NZS 3000:2018, 6.2.2.2 (c) (ii)


Shower ZONE 2


NCC 2022 V1


All Building Classes


NCC 2022 S1, S13, C3D14, C4D15, J2D2, 13.4

[2019 Sch 5, Spec C3.15, C2.3, C3.15, J0.1, 3.12]


May 2023



AS/NZS 3000:2018, 6.2.2.1 (d) (i)

AS/NZS 3000:2018, 6.2.2.1 (d) (i)

AS/NZS 3000:2018, 2.6.2.2.1 (d) (ii)

AS/NZS 3000:2018, 6.2.4.7

AS/NZS 3000:2018, 4.4.1.1.2 (a)

AS/NZS 3000:2018, 6.2.4.7